§ 431.82 Definitions concerning commercial packaged boilers.
The following definitions apply for purposes of this subpart E, and of subparts A and J through M of this part. Any words or terms not defined in this section or elsewhere in this part shall be defined as provided in 42 U.S.C. 6311.
Basic model means all units of a given type of covered product (or class thereof) manufactured by one manufacturer, having the same primary energy source, and which have essentially identical electrical, physical, and functional (or hydraulic) characteristics that affect energy consumption, energy efficiency, water consumption, or water efficiency.
Btu/h or Btu/hr means British thermal units per hour.
Combustion efficiency for a commercial packaged boiler is determined using test procedures prescribed under § 431.86 and is equal to 100 percent minus percent flue loss (percent flue loss is based on input fuel energy).
Commercial packaged boiler means a type of packaged low pressure boiler that is industrial equipment with a capacity, (rated maximum input) of 300,000 Btu per hour (Btu/hr) or more which, to any significant extent, is distributed in commerce:
(1) For heating or space conditioning applications in buildings; or
(2) For service water heating in buildings but does not meet the definition of “hot water supply boiler” in this part.
Condensing boiler means a commercial packaged boiler that condenses part of the water vapor in the flue gases, and that includes a means of collecting and draining this condensate from its heat exchanger section.
Flue condensate means liquid formed by the condensation of moisture in the flue gases.
Manufacturer of a commercial packaged boiler means any person who manufactures, produces, assembles or imports such a boiler, including any person who:
(1) Manufactures, produces, assembles or imports a commercial packaged boiler in its entirety;
(2) Manufactures, produces, assembles or imports a commercial packaged boiler in part, and specifies or approves the boiler's components, including burners or other components produced by others, as for example by specifying such components in a catalogue by make and model number or parts number; or
(3) Is any vendor or installer who sells a commercial packaged boiler that consists of a combination of components that is not specified or approved by a person described in paragraph (1) or (2) of this definition.
Packaged boiler means a boiler that is shipped complete with heating equipment, mechanical draft equipment and automatic controls; usually shipped in one or more sections and does not include a boiler that is custom designed and field constructed. If the boiler is shipped in more than one section, the sections may be produced by more than one manufacturer, and may be originated or shipped at different times and from more than one location.
Packaged high pressure boiler means a packaged boiler that is:
(1) A steam boiler designed to operate at a steam pressure higher than 15 psi gauge (psig); or
(2) A hot water boiler designed to operate at a water pressure above 160 psig or at a water temperature exceeding 250 °F, or both; or
(3) A boiler that is designed to be capable of supplying either steam or hot water, and designed to operate under the conditions in paragraphs (1) and (2) of this definition.
Packaged low pressure boiler means a packaged boiler that is:
(1) A steam boiler designed to operate at or below a steam pressure of 15 psig; or
(2) A hot water boiler designed to operate at or below a water pressure of 160 psig and a temperature of 250 °F; or
(3) A boiler that is designed to be capable of supplying either steam or hot water, and designed to operate under the conditions in paragraphs (1) and (2) of this definition.
Thermal efficiency for a commercial packaged boiler is determined using test procedures prescribed under § 431.86 and is the ratio of the heat absorbed by the water or the water and steam to the higher heating value in the fuel burned.
[69 FR 61960, Oct. 21, 2004, as amended at 74 FR 36354, July 22, 2009; 76 FR 12503, Mar. 7, 2011]

Title 10 published on 2014-01-01

The following are only the Rules published in the Federal Register after the published date of Title 10.

For a complete list of all Rules, Proposed Rules, and Notices view the Rulemaking tab.

  • 2014-12-03; vol. 79 # 232 - Wednesday, December 3, 2014
    1. 79 FR 71624 - Energy Conservation Program: Test Procedures for Commercial Clothes Washers
      GPO FDSys XML | Text
      DEPARTMENT OF ENERGY, Office of Energy Efficiency and Renewable Energy
      Final rule.
      The effective date of this rule is January 2, 2015.
      10 CFR Parts 429 and 431

Title 10 published on 2014-01-01

The following are ALL rules, proposed rules, and notices (chronologically) published in the Federal Register relating to 10 CFR 431 after this date.

  • 2014-12-10; vol. 79 # 237 - Wednesday, December 10, 2014
    1. 79 FR 73246 - Energy Conservation Standards for Commercial and Industrial Fans and Blowers: Availability of Provisional Analysis Tools
      GPO FDSys XML | Text
      DEPARTMENT OF ENERGY, Office of Energy Efficiency and Renewable Energy
      Notice of data availability.
      Comments: DOE will accept comments, data, and information regarding this notice of data availability (NODA) no later than January 26, 2015.
      10 CFR Part 431