46 CFR 169.682 - Distribution and circuit loads.

§ 169.682 Distribution and circuit loads.
(a) Except as provided in paragraph (b) of this section, the connected load on a lighting branch circuit must not exceed 80 percent of the rating of the overcurrent protective device, computed using the greater of—
(1) The lamp sizes to be installed; or
(2) 50 watts per outlet.
(b) Circuits supplying electrical discharge lamps must be computed using the ballast input current.
(c) The branch circuit cables for motor and lighting loads must be no smaller than No. 14 AWG.

Title 46 published on 2014-10-01

no entries appear in the Federal Register after this date.

This is a list of United States Code sections, Statutes at Large, Public Laws, and Presidential Documents, which provide rulemaking authority for this CFR Part.

This list is taken from the Parallel Table of Authorities and Rules provided by GPO [Government Printing Office].

It is not guaranteed to be accurate or up-to-date, though we do refresh the database weekly. More limitations on accuracy are described at the GPO site.


United States Code
U.S. Code: Title 33 - NAVIGATION AND NAVIGABLE WATERS
U.S. Code: Title 46 - SHIPPING
Statutes at Large