42 USC § 6313 - Standards
| Number of poles | Nominal Full-Load Efficiency | Open Motors | 6 | 4 | 2 | Closed Motors | 6 | 4 | 2 |
|---|---|---|---|---|---|---|---|---|---|
| Motor Horsepower | |||||||||
| 1 | 80.0 | 82.5 | 80.0 | 82.5 | 75.5 | ||||
| 1.5 | 84.0 | 84.0 | 82.5 | 85.5 | 84.0 | 82.5 | |||
| 2 | 85.5 | 84.0 | 84.0 | 86.5 | 84.0 | 84.0 | |||
| 3 | 86.5 | 86.5 | 84.0 | 87.5 | 87.5 | 85.5 | |||
| 5 | 87.5 | 87.5 | 85.5 | 87.5 | 87.5 | 87.5 | |||
| 7.5 | 88.5 | 88.5 | 87.5 | 89.5 | 89.5 | 88.5 | |||
| 10 | 90.2 | 89.5 | 88.5 | 89.5 | 89.5 | 89.5 | |||
| 15 | 90.2 | 91.0 | 89.5 | 90.2 | 91.0 | 90.2 | |||
| 20 | 91.0 | 91.0 | 90.2 | 90.2 | 91.0 | 90.2 | |||
| 25 | 91.7 | 91.7 | 91.0 | 91.7 | 92.4 | 91.0 | |||
| 30 | 92.4 | 92.4 | 91.0 | 91.7 | 92.4 | 91.0 | |||
| 40 | 93.0 | 93.0 | 91.7 | 93.0 | 93.0 | 91.7 | |||
| 50 | 93.0 | 93.0 | 92.4 | 93.0 | 93.0 | 92.4 | |||
| 60 | 93.6 | 93.6 | 93.0 | 93.6 | 93.6 | 93.0 | |||
| 75 | 93.6 | 94.1 | 93.0 | 93.6 | 94.1 | 93.0 | |||
| 100 | 94.1 | 94.1 | 93.0 | 94.1 | 94.5 | 93.6 | |||
| 125 | 94.1 | 94.5 | 93.6 | 94.1 | 94.5 | 94.5 | |||
| 150 | 94.5 | 95.0 | 93.6 | 95.0 | 95.0 | 94.5 | |||
| 200 | 94.5 | 95.0 | 94.5 | 95.0 | 95.0 | 95.0 |
| Refrigerators with solid doors | 0.10 V 2.04 |
| Refrigerators with transparent doors | 0.12 V 3.34 |
| Freezers with solid doors | 0.40 V 1.38 |
| Freezers with transparent doors | 0.75 V 4.10 |
| Refrigerators/freezers with solid doors the greater of | 0.27 AV – 0.71 or 0.70. |
| Equipment Type | Type of Cooling | Harvest Rate (lbs ice/24 hours) | Maximum Energy Use (kWh/100 lbs Ice) | Maximum Condenser Water Use (gal/100 lbs Ice) |
|---|---|---|---|---|
| Ice Making Head | Water | 500 | 7.80–0.0055H | 200–0.022H |
| 500 and 1436 | 5.58–0.0011H | 200–0.022H | ||
| 1436 | 4.0 | 200–0.022H | ||
| Ice Making Head | Air | 450 | 10.26–0.0086H | Not Applicable |
| 450 | 6.89–0.0011H | Not Applicable | ||
| Remote Condensing (but not remote compressor) | Air | 1000 | 8.85–0.0038H | Not Applicable |
| 1000 | 5.10 | Not Applicable | ||
| Remote Condensing and Remote Compressor | Air | 934 | 8.85–0.0038H | Not Applicable |
| 934 | 5.3 | Not Applicable | ||
| Self Contained | Water | 200 | 11.40–0.019H | 191–0.0315H |
| 200 | 7.60 | 191–0.0315H | ||
| Self Contained | Air | 175 | 18.0–0.0469H | Not Applicable |
| 175 | 9.80 | Not Applicable | ||
| H = Harvest rate in pounds per 24 hours. | ||||
| Water use is for the condenser only and does not include potable water used to make ice. |
[1] See References in Text note below.
[2] So in original. No cls. (i) and (ii) have been enacted.
[3] So in original. Probably should be followed by “than”.
The table below lists the classification updates, since Jan. 3, 2012, for this section. Updates to a broader range of sections may be found at the update page for containing chapter, title, etc.
The most recent Classification Table update that we have noticed was Thursday, January 3, 2013
An empty table indicates that we see no relevant changes listed in the classification tables. If you suspect that our system may be missing something, please double-check with the Office of the Law Revision Counsel.
| 42 USC | Description of Change | Session Year | Public Law | Statutes at Large |
|---|---|---|---|---|
| § 6313 | 2012 | 112-210 [Sec.] 10(a)(3), (4) | 126 Stat. 1522, 1524 | |
| § 6313 | 2012 | 112-210 [Sec.] 5(b) | 126 Stat. 1518 | |
| § 6313 | 2012 | 112-210 [Sec.] 4 | 126 Stat. 1516 | |
| § 6313 | 2012 | 112-210 [Sec.] 2 | 126 Stat. 1514 |
This is a list of parts within the Code of Federal Regulations for which this US Code section provides rulemaking authority.
This list is taken from the Parallel Table of Authorities and Rules provided by GPO [Government Printing Office].
It is not guaranteed to be accurate or up-to-date, though we do refresh the database weekly. More limitations on accuracy are described at the GPO site.