40 CFR Appendix Table 8 to Subpart VVVVVV of Part 63, Emission Limits and Compliance Requirements for Heat Exchange Systems

Table 8 to Subpart VVVVVV of Part 63 - Emission Limits and Compliance Requirements for Heat Exchange Systems

[As required in § 63.11499, you must comply with the requirements for heat exchange systems as shown in the following table]

For . . . You must . . . Except . . .
1. Each heat exchange system with a cooling water flow rate ≥8,000 gal/min and not meeting one or more of the conditions in § 63.104(a) a. Comply with the monitoring requirements in § 63.104(c) , the leak repair requirements in § 63.104(d) and (e) , and the recordkeeping and reporting requirements in § 63.104(f) ; or i. The reference to monthly monitoring for the first 6 months in § 63.104(b)(1) and (c)(1)(iii) does not apply. Monitoring shall be no less frequent than quarterly;
ii. The reference in § 63.104(f)(1) to record retention requirements in § 63.103(c)(1) does not apply. Records must be retained as specified in §§ 63.10(b)(1) and 63.11501(c); and
iii. The reference in § 63.104(f)(2) to “the next semi-annual periodic report required by § 63.152(c)” means the next semi-annual compliance report required by § 63.11501(f).
b. Comply with the heat exchange system requirements in § 63.104(b) and the requirements referenced therein. i. Not applicable.
[ 77 FR 75762, Dec. 21, 2012]