Exterior walls.

Exterior walls. Exterior walls must be provided with a system or method to manage moisture and vapor accumulation with one of the elements in paragraphs (b)(1) through (4) of this section. For purposes of the requirement in this paragraph (b), the fire separation wall between each attached manufactured home must be considered to be an exterior wall. See subpart K of this part.
(1) Exterior walls shall have a vapor barrier no greater than 1 perm (dry cup method) installed on the living space side of the wall, or
(2) Unventilated wall cavities must have an external covering and/or sheathing that forms the pressure envelope. The covering and/or sheathing must have a combined permeance of not less than 5.0 perms. In the absence of test data, combined permeance is permitted to be computed using the following formula: P total = (1/[(1/P1) + (1/P2)]), where P1 and P2 are the permeance values of the exterior covering and sheathing in perms. Formed exterior siding applied in sections with joints not caulked or sealed, are not considered to restrict water vapor transmission; or
(3) Wall cavities must be constructed so that ventilation is provided to dissipate any condensation occurring in these cavities; or
(4) Homes manufactured to be sited in “humid climates” or “fringe climates” as shown on the Humid and Fringe Climate Map in this paragraph are permitted to have a vapor retarder specified in paragraph (b)(1) of this section installed on the exterior side of the wall insulation or be constructed with an external covering and sheathing with a combined permeance of not greater than 1.0 perms, provided the interior finish and interior wall panel materials have a combined permeance of not less than 5.0 perms. The following need not meet the minimum combined permeance rating of not less than 5.0 perms for interior finish or wall panel materials:
(i) Kitchen back splash materials, less than 50 square feet in area installed around countertops, sinks, and ranges;
(ii) Bathroom tub areas, shower compartments;
(iii) Cabinetry and built-in furniture;
(iv) Trim materials;
(v) Hardboard wall paneling of less than 50 square feet in area under chair rails.
(5) The following areas of local governments (counties or similar areas, unless otherwise specified), listed by state are deemed to be within the humid and fringe climate areas shown on the Humid and Fringe Climate Map in paragraph (b)(4) of this section, and the vapor retarder or construction methods specified in paragraph (b)(4) of this section may be applied to homes built to be sited within these jurisdictions:
(1) Exterior walls shall have a vapor barrier no greater than 1 perm (dry cup method) installed on the living space side of the wall, or
(2) Unventilated wall cavities must have an external covering and/or sheathing that forms the pressure envelope. The covering and/or sheathing must have a combined permeance of not less than 5.0 perms. In the absence of test data, combined permeance is permitted to be computed using the following formula: P total = (1/[(1/P1) + (1/P2)]), where P1 and P2 are the permeance values of the exterior covering and sheathing in perms. Formed exterior siding applied in sections with joints not caulked or sealed, are not considered to restrict water vapor transmission; or
(3) Wall cavities must be constructed so that ventilation is provided to dissipate any condensation occurring in these cavities; or
(4) Homes manufactured to be sited in “humid climates” or “fringe climates” as shown on the Humid and Fringe Climate Map in this paragraph are permitted to have a vapor retarder specified in paragraph (b)(1) of this section installed on the exterior side of the wall insulation or be constructed with an external covering and sheathing with a combined permeance of not greater than 1.0 perms, provided the interior finish and interior wall panel materials have a combined permeance of not less than 5.0 perms. The following need not meet the minimum combined permeance rating of not less than 5.0 perms for interior finish or wall panel materials:
(i) Kitchen back splash materials, less than 50 square feet in area installed around countertops, sinks, and ranges;
(ii) Bathroom tub areas, shower compartments;
(iii) Cabinetry and built-in furniture;
(iv) Trim materials;
(v) Hardboard wall paneling of less than 50 square feet in area under chair rails.
(5) The following areas of local governments (counties or similar areas, unless otherwise specified), listed by state are deemed to be within the humid and fringe climate areas shown on the Humid and Fringe Climate Map in paragraph (b)(4) of this section, and the vapor retarder or construction methods specified in paragraph (b)(4) of this section may be applied to homes built to be sited within these jurisdictions: