(1)
Applicability
(a) The requirements of
335-14-2-.10 apply to tank
systems for storing or treating hazardous secondary material excluded under the
remanufacturing exclusion at
335-14-2-.01(4)(a)27.
(b) Tank systems, including sumps,
as defined in
335-14-1-.02(1),
that serve as part of a secondary containment system to collect or contain
releases of hazardous secondary materials are exempted from the requirements in
335-14-2-.10(4)(a).
(2) Assessment of existing tank system's
integrity.
(a) Tank systems must meet the
secondary containment requirements of
335-14-2-.10(4),
or the remanufacturer or other person that handles the hazardous secondary
material must determine that the tank system is not leaking or is unfit for
use. Except as provided in
335-14-2-.10(2)(c),
a written assessment reviewed and certified by a qualified Professional
Engineer must be kept on file at the remanufacturer's facility or other
facility that stores or treats the hazardous secondary material that attests to
the tank system's integrity.
(b)
This assessment must determine that the tank system is adequately designed and
has sufficient structural strength and compatibility with the material(s) to be
stored or treated, to ensure that it will not collapse, rupture, or fail. At a
minimum, this assessment must consider the following:
1. Design standard(s), if available,
according to which the tank and ancillary equipment were constructed;
2. Hazardous characteristics of the
material(s) that have been and will be handled;
3. Existing corrosion protection
measures;
4. Documented age of the
tank system, if available (otherwise, an estimate of the age); and
5. Results of a leak test, internal
inspection, or other tank integrity examination such that:
(i) For non-enterable underground tanks, the
assessment must include a leak test that is capable of taking into account the
effects of temperature variations, tank end deflection, vapor pockets, and high
water table effects, and
(ii) For
other than non-enterable underground tanks and for ancillary equipment, this
assessment must include either a leak test, as described above, or other
integrity examination that is certified by a qualified Professional Engineer
that addresses cracks, leaks, corrosion, and erosion.
[Note: The practices described in the American Petroleum
Institute (API) Publication, Guide for Inspection of Refinery Equipment,
Chapter XIII, "Atmospheric and Low-Pressure Storage Tanks," 4th edition, 1981,
may be used, where applicable, as guidelines in conducting other than a leak
test.]
(c) If, as a result of the assessment
conducted in accordance with
335-14-2-.10(2)(a),
a tank system is found to be leaking or unfit for use, the remanufacturer or
other person that stores or treats the hazardous secondary material must comply
with the requirements of
335-14-2-.10(7).
(3) [Reserved].
(4) Containment and detection of releases.
(a) Secondary containment systems must be:
1. Designed, installed, and operated to
prevent any migration of materials or accumulated liquid out of the system to
the soil, ground water, or surface water at any time during the use of the tank
system; and
2. Capable of detecting
and collecting releases and accumulated liquids until the collected material is
removed.
[Note: If the collected material is a hazardous waste under
335-14-2, it is subject to management as a hazardous waste in accordance with
all applicable requirements of 335-14-3 through 335-14-6, 335-14-7 and
335-14-9. If the collected material is discharged through a point source to
waters of the United States, it is subject to the requirements of sections 301,
304, and 402 of the Clean Water Act, as amended. If discharged to a Publicly
Owned Treatment Works (POTW), it is subject to the requirements of section 307
of the Clean Water Act, as amended. If the collected material is released to
the environment, it may be subject to the reporting requirements of
40 CFR part
302.]
(b) To meet the requirements of
335-14-2-.10(4)(a),
secondary containment systems must be at a minimum:
1. Constructed of or lined with materials
that are compatible with the materials(s) to be placed in the tank system and
must have sufficient strength and thickness to prevent failure owing to
pressure gradients (including static head and external hydrological forces),
physical contact with the material to which it is exposed, climatic conditions,
and the stress of daily operation (including stresses from nearby vehicular
traffic).
2. Placed on a foundation
or base capable of providing support to the secondary containment system,
resistance to pressure gradients above and below the system, and capable of
preventing failure due to settlement, compression, or uplift;
3. Provided with a leak-detection system that
is designed and operated so that it will detect the failure of either the
primary or secondary containment structure or the presence of any release of
hazardous secondary material or accumulated liquid in the secondary containment
system at the earliest practicable time; and
4. Sloped or otherwise designed or operated
to drain and remove liquids resulting from leaks, spills, or precipitation.
Spilled or leaked material and accumulated precipitation must be removed from
the secondary containment system within 24 hours, or in as timely a manner as
is possible to prevent harm to human health and the
environment.
(c)
Secondary containment for tanks must include one or more of the following
devices:
1. A liner (external to the
tank);
2. A vault; or
3. A double-walled tank.
(d) In addition to the requirements of
335-14-2-.10(4)(a), (b), and
(c), secondary containment systems must
satisfy the following requirements:
1.
External liner systems must be:
(i) Designed
or operated to contain 100 percent of the capacity of the largest tank within
its boundary;
(ii) Designed or
operated to prevent run-on or infiltration of precipitation into the secondary
containment system unless the collection system has sufficient excess capacity
to contain run-on or infiltration. Such additional capacity must be sufficient
to contain precipitation from a 25-year, 24-hour rainfall event.
(iii) Free of cracks or gaps; and
(iv) Designed and installed to surround the
tank completely and to cover all surrounding earth likely to come into contact
with the material if the material is released from the tank(s) (i.e., capable
of preventing lateral as well as vertical migration of the material).
2. Vault systems must be:
(i) Designed or operated to contain 100
percent of the capacity of the largest tank within its boundary;
(ii) Designed or operated to prevent run-on
or infiltration of precipitation into the secondary containment system unless
the collection system has sufficient excess capacity to contain run-on or
infiltration. Such additional capacity must be sufficient to contain
precipitation from a 25-year, 24-hour rainfall event;
(iii) Constructed with chemical-resistant
water stops in place at all joints (if any);
(iv) Provided with an impermeable interior
coating or lining that is compatible with the stored material and that will
prevent migration of material into the concrete;
(v) Provided with a means to protect against
the formation of and ignition of vapors within the vault, if the material being
stored or treated is ignitable or reactive; and
(vi) Provided with an exterior moisture
barrier or be otherwise designed or operated to prevent migration of moisture
into the vault if the vault is subject to hydraulic pressure.
3. Double-walled tanks must be:
(i) Designed as an integral structure (i.e.,
an inner tank completely enveloped within an outer shell) so that any release
from the inner tank is contained by the outer shell;
(ii) Protected, if constructed of metal, from
both corrosion of the primary tank interior and of the external surface of the
outer shell; and
(iii) Provided
with a built-in continuous leak detection system capable of detecting a release
within 24 hours, or at the earliest practicable time.
[Note: The provisions outlined in the Steel Tank Institute's
(STI) "Standard for Dual Wall Underground Steel Storage Tanks" may be used as
guidelines for aspects of the design of underground steel doublewalled
tanks.]
(e) [Reserved].
(f) Ancillary equipment must be provided with
secondary containment (e.g., trench, jacketing, double-walled piping) that
meets the requirements of
335-14-2-.10(4)(a) and
(b) except for:
1. Aboveground piping (exclusive of flanges,
joints, valves, and other connections) that are visually inspected for leaks on
a daily basis;
2. Welded flanges,
welded joints, and welded connections that are visually inspected for leaks on
a daily basis;
3. Sealless or
magnetic coupling pumps and sealless valves that are visually inspected for
leaks on a daily basis; and
4.
Pressurized aboveground piping systems with automatic shut-off devices (e.g.,
excess flow check valves, flow metering shutdown devices, loss of pressure
actuated shut-off devices) that are visually inspected for leaks on a daily
basis.
(5)
General operating requirements
(a) Hazardous
secondary materials or treatment reagents must not be placed in a tank system
if they could cause the tank, its ancillary equipment, or the containment
system to rupture, leak, corrode, or otherwise fail.
(b) The remanufacturer or other person that
stores or treats the hazardous secondary material must use appropriate controls
and practices to prevent spills and overflows from tank or containment systems.
These include at a minimum:
1. Spill
prevention controls (e.g., check valves, dry disconnect couplings);
2. Overfill prevention controls (e.g., level
sensing devices, high level alarms, automatic feed cutoff, or bypass to a
standby tank); and
3. Maintenance
of sufficient freeboard in uncovered tanks to prevent overtopping by wave or
wind action or by precipitation.
(c) The remanufacturer or other person that
stores or treats the hazardous secondary material must comply with the
requirements of
335-14-2-.10(7)
if a leak or spill occurs in the tank system.
(6) [Reserved].
(7) Response to leaks or spills and
disposition of leaking or unfit-for-use tank systems. A tank system or
secondary containment system from which there has been a leak or spill, or
which is unfit for use, must be removed from service immediately, and the
remanufacturer or other person that stores or treats the hazardous secondary
material must satisfy the following requirements:
(a)
Cessation of use; prevent flow or
addition of materials. The remanufacturer or other person that stores
or treats the hazardous secondary material must immediately stop the flow of
hazardous secondary material into the tank system or secondary containment
system and inspect the system to determine the cause of the release.
(b)
Removal of material from tank
system or secondary containment system.
1. If the release was from the tank system,
the remanufacturer or other person that stores or treats the hazardous
secondary material must, within 24 hours after detection of the leak or, if the
remanufacturer or other person that stores or treats the hazardous secondary
material demonstrates that it is not possible, at the earliest practicable
time, remove as much of the material as is necessary to prevent further release
of hazardous secondary material to the environment and to allow inspection and
repair of the tank system to be performed.
2. If the material released was to a
secondary containment system, all released materials must be removed within 24
hours or in as timely a manner as is possible to prevent harm to human health
and the environment.
(c)
Containment of visible releases to the environment. The
remanufacturer or other person that stores or treats the hazardous secondary
material must immediately conduct a visual inspection of the release and, based
upon that inspection:
1. Prevent further
migration of the leak or spill to soils or surface water; and
2. Remove, and properly dispose of, any
visible contamination of the soil or surface water.
(d)
Notifications, reports.
1. Any release to the environment, except as
provided in
335-14-2-.10(7)(d)2.,
must be reported to the Department within 24 hours of its detection. If the
release has been reported pursuant to 40 CFR part
302, that report will satisfy
this requirement.
2. A leak or
spill of hazardous secondary material is exempted from the requirements of this
requirement if it is:
(i) Less than or equal
to a quantity of 1 pound, and
(ii)
Immediately contained and cleaned up.
3. Within 30 days of detection of a release
to the environment, a report containing the following information must be
submitted to the Department:
(i) Likely route
of migration of the release;
(ii)
Characteristics of the surrounding soil (soil composition, geology,
hydrogeology, climate);
(iii)
Results of any monitoring or sampling conducted in connection with the release
(if available). If sampling or monitoring data relating to the release are not
available within 30 days, these data must be submitted to the Department as
soon as they become available.
(iv)
Proximity to downgradient drinking water, surface water, and populated areas;
and
(v) Description of response
actions taken or planned.
(e)
Provision of secondary
containment, repair, or closure.
1.
Unless the remanufacturer or other person that stores or treats the hazardous
secondary material satisfies the requirements of
335-14-2-.10(7)(e)2.
through 4., the tank system must cease to operate under the remanufacturing
exclusion at
335-14-2-.01(4)(a)27.
2. If the cause of the release was
a spill that has not damaged the integrity of the system, the remanufacturer or
other person that stores or treats the hazardous secondary material may return
the system to service as soon as the released material is removed and repairs,
if necessary, are made.
3. If the
cause of the release was a leak from the primary tank system into the secondary
containment system, the system must be repaired prior to returning the tank
system to service.
4. If the source
of the release was a leak to the environment from a component of a tank system
without secondary containment, the remanufacturer or other person that stores
or treats the hazardous secondary material must provide the component of the
system from which the leak occurred with secondary containment that satisfies
the requirements of
335-14-2-.10(4)
before it can be returned to service, unless the source of the leak is an
aboveground portion of a tank system that can be inspected visually. If the
source is an aboveground component that can be inspected visually, the
component must be repaired and may be returned to service without secondary
containment as long as the requirements of
335-14-2-.10(7)(f)
are satisfied. Additionally, if a leak has occurred in any portion of a tank
system component that is not readily accessible for visual inspection (e.g.,
the bottom of an inground or onground tank), the entire component must be
provided with secondary containment in accordance with
335-14-2-.10(4)
prior to being returned to use.
(f) Certification of major repairs. If the
remanufacturer or other person that stores or treats the hazardous secondary
material has repaired a tank system in accordance with
335-14-2-.10(7)(e),
and the repair has been extensive (e.g., installation of an internal liner;
repair of a ruptured primary containment or secondary containment vessel), the
tank system must not be returned to service unless the remanufacturer or other
person that stores or treats the hazardous secondary material has obtained a
certification by a qualified Professional Engineer that the repaired system is
capable of handling hazardous secondary materials without release for the
intended life of the system. This certification must be kept on file at the
facility and maintained until closure of the facility.
[Note: The Department may, on the basis of any information
received that there is or has been a release of hazardous secondary material or
hazardous constituents into the environment, issue an order under RCRA section
7003(a) or Code of Alabama 1975, §
22-30-19(a)
requiring corrective action or such other response as deemed necessary to
protect human health or the environment.]
[Note: 40 CFR part 302 may require the owner or operator to
notify the National Response Center of certain releases.]
(8) Termination of remanufacturing
exclusion. Hazardous secondary material stored in units more than 90 days after
the unit ceases to operate under the remanufacturing exclusion at
335-14-2-.01(4)(a)27
or otherwise ceases to be operated for manufacturing, or for storage of a
product or a raw material, then becomes subject to regulation as hazardous
waste under 335-14-2 through 9, as applicable.
(9) Special requirements for ignitable or
reactive materials.
(a) Ignitable or reactive
material must not be placed in tank systems, unless the material is stored or
treated in such a way that it is protected from any material or conditions that
may cause the material to ignite or react.
(b) The remanufacturer or other person that
stores or treats hazardous secondary material which is ignitable or reactive
must store or treat the hazardous secondary material in a tank that is in
compliance with the requirements for the maintenance of protective distances
between the material management area and any public ways, streets, alleys, or
an adjoining property line that can be built upon as required in Tables 2-1
through 2-6 of the National Fire Protection Association's "Flammable and
Combustible Liquids Code," (1977 or 1981)(incorporated by reference, see
40 CFR
260.11).
(10) Special requirements for incompatible
materials.
(a) Incompatible materials must not
be placed in the same tank system.
(b) Hazardous secondary material must not be
placed in a tank system that has not been decontaminated and that previously
held an incompatible material.
(11) Air emission standards. The
remanufacturer or other person that stores or treats the hazardous secondary
material shall manage all hazardous secondary material placed in a tank in
accordance with the applicable requirements of subparts AA [incorporated by
reference in
335-14-2-.27], BB [incorporated
by reference in
335-14-2-.28], and CC
[incorporated by reference in
335-14-2-.29] .
Notes
Ala. Admin.
Code r. 335-14-2-.10
Amended by
Alabama
Administrative Monthly Volume XXXIV, Issue No. 05, February 29,
2016, eff. 4/8/2016.
Amended by
Alabama
Administrative Monthly Volume XXXVIII, Issue No. 05, February 28,
2020, eff. 4/13/2020.
Amended by
Alabama
Administrative Monthly Volume XLI, Issue No. 07, April 28, 2023,
eff. 6/12/2023.
Author: Bradley N. Curvin, Metz P. Duites,
Sonja B. Favors, Brent A Watson, Jonah L. Harris.
Statutory Authority:
Code of Ala.
1975, §§
22-30-11.