(1)
Applicability. The requirements of apply to owners and
operators of facilities that use tank systems for storing or treating hazardous
waste, except as otherwise provided in 335-14-6-.10(1) (a), (b), and (c) or in
rule
335-14-6-.01.
(a) Tank systems that are used to store or
treat hazardous waste which contains no free liquids and that are situated
inside a building with an impermeable floor are exempted from the requirements
of 335-14-6-.10(4). To demonstrate the absence or presence of free liquids in
the stored/treated waste, the following test must be used: Method 9095B (Paint
Filter Liquids Test) as described in "Test Methods for Evaluating Solid Waste,
Physical/Chemical Methods," EPA Publication SW-846, as incorporated by
reference in rule
335-14-1-.02(2).
(b) Tank systems, including sumps, as defined
in rule
335-14-1-.02,
that serve as part of a secondary containment system to collect or contain
releases of hazardous wastes are exempted from the requirements in
335-14-6-.10(4) (a).
(c) Tanks,
sumps, and other collection devices used in conjunction with drip pads, as
defined in
335-14-1-.02
and regulated under Rule
335-14-6-.23, must meet
the requirements of 335-14-6-.10.
(2)
Assessment of existing tank
system's integrity.
(a) For each
existing tank system that does not have secondary containment meeting the
requirements of 335-14-6-.10(4), the owner or operator must determine that the
tank system is not leaking or is unfit for use. Except as provided in
335-14-6-.10(2)(c), the owner or operator must obtain and keep on file at the
facility a written assessment reviewed and certified by a qualified
professional engineer in accordance with 335 14-8-.02(2)(d) that attests to the
tank system's integrity by January 12, 1988.
(b) This assessment must determine that the
tank system is adequately designed and has sufficient structural strength and
compatibility with the waste(s) to be stored or treated to ensure that it will
not collapse, rupture, or fail. At a minimum, this assessment must consider the
following:
1. Design standard(s), if
available, according to which the tank and ancillary equipment were
constructed;
2. Hazardous
characteristics of the waste(s) that have been or will be handled;
3. Existing corrosion protection
measures;
4. Documented age of the
tank system, if available. (Otherwise, an estimate of age); and
5. Results of a leak test, internal
inspection, or other tank integrity examination such that:
(i) For nonenterable underground tanks, this
assessment must consist of a leak test that is capable of taking into account
the effects of temperature variations, tank end deflection, vapor pockets, and
high water table effects;
(ii) For
other than nonenterable underground tanks and for ancillary equipment, this
assessment must be either a leak test, as described above, or an internal
inspection and/or other tank integrity examination certified by a qualified
Professional Engineer in accordance with
335-14-8-.02(2)
(d) that addresses cracks, leaks, corrosion,
and erosion.
[Note: The practices described in the American Petroleum
Institute (API) Publication, Guide for Inspection of Refinery
Equipment, Chapter XIII, "Atmospheric and Low- Pressure Storage
Tanks", 4th Edition, 1981, may be used, where applicable, as guidelines in
conducting the integrity examination of an other than nonenterable underground
tank system.]
(c) Tank systems that store or treat
materials that become hazardous wastes subsequent to July 14, 1986 must conduct
this assessment within 12 months after the date that the waste becomes a
hazardous waste.
(d) If, as a
result of the assessment conducted in accordance with 335-14-6-.10(2)(a), a
tank system is found to be leaking or unfit for use, the owner or operator must
comply with the requirements of 335-14-6-.10(7).
(3)
Design and installation of
new tank systems or components.
(a) Owners or operators of new tank systems
or components must ensure that the foundation, structural support, seams,
connections, and pressure controls (if applicable) are adequately designed and
that the tank system has sufficient structural strength, compatibility with the
waste(s) to be stored or treated, and corrosion protection so that it will not
collapse, rupture, or fail. The owner or operator must obtain a written
assessment reviewed and certified by a qualified professional engineer in
accordance with
335-14-8-.02(2)(d),
attesting that the system has sufficient structural integrity and is acceptable
for the storing and treating of hazardous waste. This assessment must include
the following information:
1. Design
standard(s) according to which the tank(s) and the ancillary equipment is or
will be constructed;
2. Hazardous
characteristics of the waste(s) to be handled;
3. For new tank systems or components in
which the external shell of a metal tank or any external metal component of the
tank system is or will be in contact with the soil or with water, a
determination by a corrosion expert of:
(i)
Factors affecting the potential for corrosion, including but not limited to:
(I) Soil moisture content;
(II) Soil pH;
(III) Soil sulfides level;
(IV) Soil resistivity;
(V) Structure to soil potential;
(VI) Influence of nearby underground metal
structures (e.g., piping);
(VII)
Stray electric current; and
(VIII)
Existing corrosion-protection measures (e.g., coating, cathodic protection),
and
(ii) The type and
degree of external corrosion protection that are needed to ensure the integrity
of the tank system during the use of the tank system or component, consisting
of one or more of the following:
(I)
Corrosion-resistant materials of construction such as special alloys,
fiberglass-reinforced plastic;
(II)
Corrosion-resistant coating (such as epoxy or fiberglass) with cathodic
protection (e.g., impressed current or sacrificial anodes); and
(III) Electrical isolation devices such as
insulating joints and flanges.
[Note: The practices described in the National Association of
Corrosion Engineers (NACE) standard, "Recommended Practice (RP-02-85)-Control
of External Corrosion on Metallic Buried, Partially Buried, or Submerged Liquid
Storage Systems", and the American Petroleum Institute (API) Publication 1632,
"Cathodic Protection of Underground Petroleum Storage Tanks and Piping
Systems", may be used, where applicable, as guidelines in providing corrosion
protection for tank systems.]
4. For underground tank system components
that are likely to be affected by vehicular traffic, a determination of design
or operational measures that will protect the tank system against potential
damage; and
5. Design
considerations to ensure that:
(i) Tank
foundations will maintain the load of a full tank;
(ii) Tank systems will be anchored to prevent
flotation or dislodgment where the tank system is placed in a saturated zone,
or is located within a seismic fault zone; and
(iii) Tank systems will withstand the effects
of frost heave.
(b) The owner or operator of a new tank
system must ensure that proper handling procedures are adhered to in order to
prevent damage to the system during installation. Prior to covering, enclosing,
or placing a new tank system or component in use, an independent, qualified
installation inspector or a qualified professional engineer, either of whom is
trained and experienced in the proper installation of tank systems, must
inspect the system or component for the presence of any of the following items:
1. Weld breaks;
2. Punctures;
3. Scrapes of protective coatings;
4. Cracks;
5. Corrosion; or
6. Other structural damage or inadequate
construction or installation.
All discrepancies must be remedied before the tank system is
covered, enclosed, or placed in use.
(c) New tank systems or components and piping
that are placed underground and that are backfilled must be provided with a
backfill material that is a noncorrosive, porous, homogeneous substance and
that is carefully installed so that the backfill is placed completely around
the tank and compacted to ensure that the tank and piping are fully and
uniformly supported.
(d) All new
tanks and ancillary equipment must be tested for tightness prior to being
covered, enclosed, or placed in use. If a tank system is found not to be tight,
all repairs necessary to remedy the leak(s) in the system must be performed
prior to the tank system being covered, enclosed, or placed into use.
(e) Ancillary equipment must be supported and
protected against physical damage and excessive stress due to settlement,
vibration, expansion, or contraction.
[Note: The piping system installation procedures
described in American Petroleum Institute (API) Publication 1615 (November
1979), "Installation of Underground Petroleum Storage Systems", or ANSI
Standard B31.3, "Petroleum Refinery Piping", and ANSI Standard B31.4 "Liquid
Petroleum Transportation Piping System", may be used, where applicable, as
guidelines for proper installation of piping systems.]
(f) The owner or operator must provide the
type and degree of corrosion protection necessary, based on the information
provided under 335-14-6-.10(3)(a)3. to ensure the integrity of the tank system
during use of the tank system. The installation of a corrosion protection
system that is field fabricated must be supervised by an independent corrosion
expert to ensure proper installation.
(g) The owner or operator must obtain and
keep on file at the facility written statements by those persons required to
certify the design of the tank system and supervise the installation of the
tank system in accordance with the requirements of 335-14-6-.10(3)(b) through
(f) to attest that the tank system was properly designed and installed and that
repairs, pursuant to 335-14-6-.10(3)(b) and (d) were performed. These written
statements must also include the certification statement as required in
335-14-8-.02(2)(d).
(4)
Containment and
detection of releases.
(a) In
order to prevent the release of hazardous waste or hazardous constituents to
the environment, secondary containment that meets the requirements of
335-14-6-.10(4) must be provided (except as provided in 335-14-6-.10(4)(f) and
(g) ):
1. For all new and existing tank
systems or components, prior to their being put into service;
2. For tank systems that store or treat
materials that become hazardous wastes, within two years of the hazardous waste
listing, or when the tank system has reached 15 years of age, whichever comes
later.
(b) Secondary
containment systems must be:
1. Designed,
installed, and operated to prevent any migration of wastes or accumulated
liquid out of the system to the soil, groundwater, or surface water at any time
during the use of the tank system; and
2. Capable of detecting and collecting
releases and accumulated liquids until the collected material is
removed.
(c) To meet the
requirements of 335-14-6-.10(4) (b), secondary containment systems must be at a
minimum:
1. Constructed of or lined with
materials that are compatible with the waste(s) to be placed in the tank system
and must have sufficient strength and thickness to prevent failure owing to
pressure gradients (including static head and external hydrological forces),
physical contact with the waste to which they are exposed, climatic conditions,
the stress of installation, and the stress of daily operation (including
stresses from nearby vehicular traffic);
2. Placed on a foundation or base capable of
providing support to the secondary containment system and resistance to
pressure gradients above and below the system and capable of preventing failure
due to settlement, compression, or uplift;
3. Provided with a leak-detection system that
is designed and operated so that it will detect the failure of either the
primary and secondary containment structure or any release of hazardous waste
or accumulated liquid in the secondary containment system within 24 hours, or
at the earliest practicable time if the existing detection technology or site
conditions will not allow detection of a release within 24 hours; and
4. Sloped or otherwise designed or operated
to drain and remove liquids resulting from leaks, spills, or precipitation.
Spilled or leaked waste and accumulated precipitation must be removed from the
secondary containment system within 24 hours, or in as timely a manner as is
possible to prevent harm to human health and the environment, if removal of the
released waste or accumulated precipitation cannot be accomplished within 24
hours.
[Note: If the collected material is a hazardous
waste under 335-14-2, it is subject to management as a hazardous waste in
accordance with all applicable requirements of 335-14-3 through 335-14-6. If
the collected material is discharged through a point source to waters of the
United States, it is subject to the requirements of Sections 301, 304, and 402
of the Clean Water Act, as amended. If discharged to a Publicly Owned Treatment
Works (POTWs), it is subject to the requirements of Section 307 of the Clean
Water Act, as amended. If the collected material is released to the
environment, it may be subject to the reporting requirements of 40 CFR Part
302.]
(d)
Secondary containment for tanks must include one or more of the following
devices:
1. A liner (external to the
tank);
2. A vault;
3. A double-walled tank; or
4. An equivalent device as approved by the
Department.
(e) In
addition to the requirements of 335-14-6-.10(4)(b), (c), and (d), secondary
containment systems must satisfy the following requirements:
1. External liner systems must be:
(i) Designed or operated to contain 100
percent of the capacity of the largest tank within its boundary;
(ii) Designed or operated to prevent run-on
or infiltration of precipitation into the secondary containment system unless
the collection system has sufficient excess capacity to contain run-on or
infiltration. Such additional capacity must be sufficient to contain
precipitation from a 25-year, 24-hour rainfall event.
(iii) Free of cracks or gaps; and
(iv) Designed and installed to completely
surround the tank and to cover all surrounding earth likely to come into
contact with the waste if released from the tank(s) (i.e., capable of
preventing lateral as well as vertical migration of the waste).
(v) Provided with an impermeable interior
coating or lining if a concrete (or other porous or pervious material) liner is
used. The interior coating or lining must be compatible with the stored waste
and prevent migration of the waste into the concrete.
2. Vault systems must be:
(i) Designed or operated to contain 100
percent of the capacity of the largest tank within its boundary;
(ii) Designed or operated to prevent run-on
or infiltration of precipitation into the secondary containment system unless
the collection system has sufficient excess capacity to contain run-on or
infiltration. Such additional capacity must be sufficient to contain
precipitation from a 25-year, 24-hour rainfall event;
(iii) Constructed with chemical-resistant
water stops in place at all joints (if any);
(iv) Provided with an impermeable interior
coating or lining that is compatible with the stored waste and that will
prevent migration of waste into the concrete;
(v) Provided with a means to protect against
the formation of and ignition of vapors within the vault, if the waste being
stored or treated:
(I) Meets the definition
of ignitable waste under
335-14-2-.03(2);
or
(II) Meets the definition of
reactive waste under
335-14-2-.03(4)
and may form an ignitable or explosive vapor; and
(vi) Provided with an exterior moisture
barrier or be otherwise designed or operated to prevent migration of moisture
into the vault if the vault is subject to hydraulic pressure.
3. Double-walled tanks must be:
(i) Designed as an integral structure (i.e.,
an inner tank within an outer shell) so that any release from the inner tank is
contained by the outer shell;
(ii)
Protected, if constructed of metal, from both corrosion of the primary tank
interior and of the outer shell; and
(iii) Provided with a built-in continuous
leak detection system capable of detecting a release within 24 hours, or at the
earliest practicable time, if the owner or operator can demonstrate to the
Department, and the Department concurs, that the existing leak detection
technology or site conditions will not allow detection of a release within 24
hours.
[Note: The provisions outlined in the Steel Tank
Institute's (STI) "Standard for Dual Wall Underground Steel Storage Tank" may
be used as guidelines for aspects of the design of underground steel
double-walled tanks.]
(f) Ancillary equipment must be provided with
full secondary containment (e.g., trench, jacketing, double-walled piping) that
meets the requirements of 335-14-6-.10(4)(b) and (c) except for:
1. Aboveground piping (exclusive of flanges,
joints, valves, and connections) that is visually inspected for leaks on a
daily basis;
2. Welded flanges,
welded joints, and welded connections that are visually inspected for leaks on
a daily basis;
3. Sealless or
magnetic coupling pumps and sealless valves, that are visually inspected for
leaks on a daily basis; and
4.
Pressurized aboveground piping systems with automatic shut-off devices (e.g.,
excess flow check valves, flow metering shutdown devices, loss of pressure
actuated shut-off devices) that are visually inspected for leaks on a daily
basis.
(g) The owner or
operator may obtain a variance from the requirements of 335-14-6-.10(4) if the
Department finds, as a result of a demonstration by the owner or operator,
either: that alternative design and operating practices, together with location
characteristics, will prevent the migration of any hazardous waste or hazardous
constituents into the groundwater or surface water at least as effectively as
secondary containment during the active life of the tank system or that in the
event of a release that does migrate to groundwater or surface water, no
substantial present or potential hazard will be posed to human health or the
environment. New underground tank systems may not, per a demonstration in
accordance with 335-14-6-.10(4) (g)2., be exempted from the secondary
containment requirements of 335-14-6-.10(4). Application for a variance as
allowed in 335-14-6-.10(4)(g) does not waive compliance with the requirements
of Rule 335-14-6-.10 for new tank systems.
1.
In deciding whether to grant a variance based on a demonstration of equivalent
protection of groundwater and surface water, the Department will consider:
(i) The nature and quantity of the
waste;
(ii) The proposed alternate
design and operation;
(iii) The
hydrogeologic setting of the facility, including the thickness of soils between
the tank system and groundwater; and
(iv) All other factors that would influence
the quality and mobility of the hazardous constituents and the potential for
them to migrate to groundwater or surface water.
2. In deciding whether to grant a variance
based on a demonstration of no substantial present or potential hazard, the
Department will consider:
(i) The potential
adverse effects on groundwater, surface water, and land quality taking into
account:
(I) The physical and chemical
characteristics of the waste in the tank system, including its potential for
migration,
(II) The hydrogeological
characteristics of the facility and surrounding land,
(III) The potential for health risks caused
by human exposure to waste constituents,
(IV) The potential for damage to wildlife,
crops, vegetation, and physical structures caused by exposure to waste
constituents, and
(V) The
persistence and permanence of the potential adverse effects;
(ii) The potential adverse effects
of a release on groundwater quality, taking into account:
(I) The quantity and quality of groundwater
and the direction of groundwater flow,
(II) The proximity and withdrawal rates of
water in the area,
(III) The
current and future uses of groundwater in the area, and
(IV) The existing quality of groundwater,
including other sources of contamination and their cumulative impact on the
groundwater quality;
(iii) The potential adverse effects of a
release on surface water quality, taking into account:
(I) The quantity and quality of groundwater
and the direction of groundwater flow,
(II) The patterns of rainfall in the
region,
(III) The proximity of the
tank system to surface waters,
(IV)
The current and future uses of surface waters in the area and any water quality
standards established for those surface waters, and
(V) The existing quality of surface water,
including other sources of contamination and the cumulative impact on
surface-water quality;
(iv) The potential adverse effects of a
release on the land surrounding the tank system, taking into account:
(I) The patterns of rainfall in the region,
and
(II) The current and future
uses of the surrounding land.
3. The owner or operator of a tank system for
which a variance from secondary containment had been granted in accordance with
the requirements of 335-14-6-.10(4) (g) l., at which a release of hazardous
waste has occurred from the primary tank system but has not migrated beyond the
zone of engineering control (as established in the variance), must:
(i) Comply with the requirements of
335-14-6-.10(7), except 335-14-6-.10(7)(d); and
(ii) Decontaminate or remove contaminated
soil to the extent necessary to:
(I) Enable
the tank system, for which the variance was granted, to resume operation with
the capability for the detection of releases at least equivalent to the
capability it had prior to the release, and
(II) Prevent the migration of hazardous waste
or hazardous constituents to groundwater or surface water; and
(iii) If contaminated soil cannot
be removed or decontaminated in accordance with 335-14-6-.10(4)(g)3.(ii),
comply with the requirements of 335-14-6-.10(8)(b).
4. The owner or operator of a tank system,
for which a variance from secondary containment had been granted in accordance
with the requirements of 335-14-6-.10(4) (g) l., at which a release of
hazardous waste has occurred from the primary tank system and has migrated
beyond the zone of engineering control (as established in the variance), must:
(i) Comply with the requirements of
335-14-6-.10(7) (a), (b), (c), and (d);
(ii) Prevent the migration of hazardous waste
or hazardous constituents to groundwater or surface water, if possible, and
decontaminate or remove contaminated soil. If contaminated soil cannot be
decontaminated or removed or if groundwater has been contaminated, the owner or
operator must comply with the requirements of 335-14-6-.10(8)(b); and
(iii) If repairing, replacing, or
reinstalling the tank system, provide secondary containment in accordance with
the requirements of 335-14-6-.10(4)(a) through (f) or reapply for a variance
from secondary containment and meet the requirements for new tank systems in
335-14-6-.10(3) if the tank system is replaced. The owner or operator must
comply with these requirements even if contaminated soil can be decontaminated
or removed and groundwater or surface water has not been
contaminated.
(h) The following procedures must be followed
in order to request a variance from secondary containment:
1. The Department must be notified in writing
by the owner or operator that he intends to conduct and submit a demonstration
for a variance from secondary containment as allowed in 335-14-6-.10(4)(g)
according to the following schedule:
(i) For
existing tank systems, at least 24 months prior to the date that secondary
containment must be provided in accordance with 335-14-6-.10(4) (a);
and
(ii) For new tank systems, at
least 30 days prior to entering into a contract for installation of the tank
system.
2. As part of
the notification, the owner or operator must also submit to the Department a
description of the steps necessary to conduct the demonstration and a timetable
for completing each of the steps. The demonstration must address each of the
factors listed in 335-14-6-.10(4)(g) l. or (g)2.;
3. The demonstration for a variance must be
completed and submitted to the Department within 180 days after notifying the
Department of intent to conduct the demonstration; and
4. The Department will inform the public,
through a newspaper notice, of the availability of the demonstration for a
variance. The notice shall be placed in a daily or weekly major local newspaper
of general circulation and shall provide at least 30 days from the date of the
notice for the public to review and comment on the demonstration for a
variance. The Department also will hold a public hearing, in response to a
request or at its own discretion, whenever such a hearing might clarify one or
more issues concerning the demonstration for a variance. Public notice of the
hearing will be given at least 30 days prior to the date of the hearing and may
be given at the same time as notice of the opportunity for the public to review
and comment on the demonstration. These two notices may be combined.
5. The Department will approve or disapprove
the request for a variance within 90 days of receipt of the demonstration from
the owner or operator and will notify in writing the owner or operator and each
person who submitted written comments or requested notice of the variance
decision. If the demonstration for a variance is incomplete or does not include
sufficient information, the 90-day time period will begin when the Department
receives a complete demonstration, including all information necessary to make
a final determination. If the public comment period in 335-14-6-.10(4)(h)4. is
extended, the 90-day time period will be similarly extended.
(i) All tank systems, until such
time as secondary containment that meets the requirements of 335-14-6-.10(4) is
provided, must comply with the following:
1.
For nonenterable underground tanks, a leak test that meets the requirements of
335-14-6-.10(2)(b)5. must be conducted at least annually;
2. For other than non-enterable underground
tanks, and for all ancillary equipment, the owner or operator must either
conduct a leak test, as described in 335-14-6-.10(4) (i) l., or an internal
inspection or other tank integrity examination by a qualified professional
engineer that addresses cracks, leaks, and corrosion or erosion at least
annually. The owner or operator must remove the stored waste from the tank, if
necessary, to allow the condition of all internal tank surfaces to be assessed.
[Note: The practices described in the American
Petroleum Institute (API) Publication, Guide for Inspection of
Refining Equipment, Chapter XIII, "Atmospheric and Low- Pressure
Storage Tanks", 4th Edition, 1981, may be used, when applicable, as guidelines
for assessing the overall condition of the tank system.]
3. The owner or operator must maintain on
file at the facility a record of the results of the assessments conducted in
accordance with 335-14-6-.10(4)(i) l. through (i)3.
4. If a tank system or component is found to
be leaking or unfit for use as a result of the leak test or assessment in
335-14-6-.10(4)(i) l. through (i)3., the owner or operator must comply with the
requirements of 335-14-6-.10(7).
(5)
General operating
requirements.
(a) Hazardous
wastes or treatment reagents must not be placed in a tank system if they could
cause the tank, its ancillary equipment, or the secondary containment system to
rupture, leak, corrode, or otherwise fail.
(b) The owner or operator must use
appropriate controls and practices to prevent spills and overflows from tank or
secondary containment systems. These include at a minimum:
1. Spill prevention controls (e.g., check
valves, dry disconnect couplings);
2. Overfill prevention controls (e.g., level
sensing devices, high level alarms, automatic feed cutoff, or bypass to a
standby tank); and
3. Maintenance
of sufficient freeboard in uncovered tanks to prevent overtopping by wave or
wind action or by precipitation.
(c) The owner or operator must comply with
the requirements of 335-14-6-.10(7) if a leak or spill occurs in the tank
system.
(6)
Inspections.
(a) The
owner or operator must inspect, where present, at least once each operating
day, data gathered from monitoring and leak detection equipment (e.g., pressure
or temperature gauges, monitoring wells) to ensure that the tank system is
being operated according to its design.
[Note:
335-14-6-.02(6)(c)
requires the owner or operator to remedy any deterioration or malfunction he
finds. 335-14-6-.10(7) requires the owner or operator to notify the Department
and the Regional Administrator within 24 hours of confirming a release. Also,
40 CFR Part 302 may require the owner or operator to notify the National
Response Center of a release.]
(b) Except as noted under 335-14-6-.10(6)
(c), the owner or operator must inspect at least once each operating day:
1. Overfill/spill control equipment (e.g.,
waste-feed cutoff systems, bypass systems, and drainage systems) to ensure that
it is in good working order;
2.
Aboveground portions of the tank system, if any, to detect corrosion or
releases of waste; and
3. The
construction materials and the area immediately surrounding the externally
accessible portion of the tank system, including the secondary containment
system (e.g., dikes) to detect erosion or signs of releases of hazardous waste
(e.g., wet spots, dead vegetation).
(c) Owners or operators of tank systems that
either use leak detection equipment to alert facility personnel to leaks, or
implement established workplace practices to ensure leaks are promptly
identified, must inspect at least weekly those areas described in
335-14-6-.10(6)(b)(1) through (3). Use of the alternate inspection schedule
must be documented in the facility's operating record. This documentation must
include a description of the established workplace practices at the
facility.
(d) Ancillary equipment
that is not provided with secondary containment, as described in
335-14-6-.10(4)(f) l. through 4., must be inspected at least once each
operating day.
(e) The owner or
operator must inspect cathodic protection systems, if present, according to, at
a minimum, the following schedule to ensure that they are functioning properly:
1. The proper operation of the cathodic
protection system must be confirmed within six months after initial
installation and annually thereafter; and
2. All sources of impressed current must be
inspected and/or tested, as appropriate, at least bimonthly (i.e., every other
month).
[Note: The practices described in the National Association of
Corrosion Engineers (NACE) standard, "Recommended Practice (RP-02-85)-Control
of External Corrosion on Metallic Buried, Partially Buried, or Submerged Liquid
Storage Systems", and the American Petroleum Institute (API) Publication 1632,
"Cathodic Protection of Underground Petroleum Storage Tanks and Piping
Systems", may be used, where applicable, as guidelines in maintaining and
inspecting cathodic protection systems.]
(f) The owner or operator must document in
the operating record of the facility an inspection of those items in
335-14-6-.10(6)(a) through (e).
(7)
Response to leaks or spills
and disposition of leaking or unfit-for-use tank systems. A tank
system or secondary containment system from which there has been a leak or
spill, or which is unfit for use, must be removed from service immediately, and
the owner or operator must satisfy the following requirements:
(a) Cessation of Use; prevent flow or
addition of wastes. The owner or operator must immediately stop the flow of
hazardous waste into the tank system or secondary containment system and
inspect the system to determine the cause of the release.
(b) Removal of waste from tank system or
secondary containment system.
1. If the
release was from the tank system, the owner or operator must, within 24 hours
after detection of the leak or, if the owner or operator demonstrates that it
is not possible, at the earliest practicable time remove as much of the waste
as is necessary to prevent further release of hazardous waste to the
environment and to allow inspection and repair of the tank system to be
performed.
2. If the release was to
a secondary containment system, all released materials must be removed within
24 hours or in as timely a manner as is possible to prevent harm to human
health and the environment.
(c) Containment of visible releases to the
environment. The owner or operator must immediately conduct a visual inspection
of the release and, based upon that inspection:
1. Prevent further migration of the leak or
spill to soils or surface water; and
2. Remove, and properly dispose of, any
visible contamination of the soil or surface water.
(d) Notifications, reports.
1. Any release to the environment, except as
provided in 335-14-6-.10(7)(d)2., must be reported to the Department within 24
hours of detection.
Report of a release pursuant to 40 CFR Part 302 does not
satisfy this requirement.
2. A leak or spill of hazardous waste that
is:
(i) Less than or equal to a quantity of
one (1) pound, and
(ii) Immediately
contained and cleaned up is exempted from the requirements of 335-14-6-.10(7)
(d).
3. Within 30 days
of detection of a release to the environment, a report containing the following
information must be submitted to the Department:
(i) Likely route of migration of the
release;
(ii) Characteristics of
the surrounding soil (soil composition, geology, hydrogeology,
climate);
(iii) Results of any
monitoring or sampling conducted in connection with the release (if available).
If sampling or monitoring data relating to the release are not available within
30 days, these data must be submitted to the Department as soon as they become
available;
(iv) Proximity to
downgradient drinking water, surface water, and populated areas; and
(v) Description of response actions taken or
planned.
(e)
Provision of secondary containment, repair, or closure.
1. Unless the owner or operator satisfies the
requirements of 335-14-6-.10(7)(e)2. through 4., the tank system must be closed
in accordance with 335-14-6-.10(8).
2. If the cause of the release was a spill
that has not damaged the integrity of the system, the owner/operator may return
the system to service as soon as the released waste is removed and repairs, if
necessary, are made.
3. If the
cause of the release was a leak from the primary tank system into the secondary
containment system, the system must be repaired prior to returning the tank
system to service.
4. If the source
of the release was a leak to the environment from a component of a tank system
without secondary containment, the owner or operator must provide the component
of the system from which the leak occurred with secondary containment that
satisfies the requirements of 335-14-6-.10(4) before it can be returned to
service, unless the source of the leak is an aboveground portion of a tank
system. If the source is an aboveground component that can be inspected
visually, the component must be repaired and may be returned to service without
secondary containment as long as the requirements of 335-14-6-.10(7)(f) are
satisfied. If a component is replaced to comply with the requirements of
335-14-6-.10(7)(e), that component must satisfy the requirements for new tank
systems or components in 335-14-6-.10(3) and 335-14-6-.10(4). Additionally, if
a leak has occurred in any portion of a tank system component that is not
readily accessible for visual inspection (e.g., the bottom of an inground or
onground tank), the entire component must be provided with secondary
containment in accordance with 335-14-6-.10(4) prior to being returned to
use.
(f) Certification
of major repairs. If the owner or operator has repaired a tank system in
accordance with 335-14-6-.10(7)(e), and the repair has been extensive (e.g.,
installation of an internal liner; repair of a ruptured primary containment or
secondary containment vessel), the tank system must not be returned to service
unless the owner or operator has obtained a certification by a qualified
professional engineer in accordance with
335-14-8-.02(2)(d)
that the repaired system is capable of handling hazardous wastes without
release for the intended life of the system. This certification is to be placed
in the operating record and maintained until closure of the facility.
[Note: The Department may, on the basis of any information
received that there is or has been a release of hazardous waste or hazardous
constituents into the environment, issue an order under RCRA Section 3004(v),
3008(h), or 7003(a), or the AHWMMA, respectively, requiring corrective action
or such other response as deemed necessary to protect human health or the
environment.]
[Note: See
335-14-6-.02(6)(c)
for the requirements necessary to remedy a failure. Also, 40 CFR Part 302
requires the owner or operator to notify the National Response Center of a
release of any "reportable quantity".]
(8)
Closure and post-closure
care.
(a) At closure of a tank
system, the owner or operator must remove or decontaminate all waste residues,
contaminated containment system components (liners, etc.), contaminated soils,
and structures and equipment contaminated with waste, and manage them as
hazardous waste, unless
335-14-2-.01(3)(d)
applies. The closure plan, closure activities, cost estimates for closure, and
financial responsibility for tank systems must meet all of the requirements
specified in Rules
335-14-6-.07
and
335-14-6-.08.
[Generators accumulating hazardous waste in tanks for 90 days or less are not
required to provide a closure plan, cost estimate, or financial
assurance.]
(b) If the owner or
operator demonstrates that not all contaminated soils can be practicably
removed or decontaminated as required in 335-14-6-.10(8) (a), then the owner or
operator must close the tank system and perform post-closure care in accordance
with the closure and post-closure care requirements that apply to landfills
[
335-14-6-.14(11)
]. In addition, for the purposes of closure, post-closure, and financial
responsibility, such a tank system is then considered to be a landfill, and the
owner or operator must meet all of the requirements for landfills specified in
Rules
335-14-6-.07
and
335-14-6-.08.
(c) [Reserved]
(d) [Reserved]
(e) If an owner or operator has a tank system
which does not have secondary containment that meets the requirements of
335-14-6-.10(4)(b) through (f) and which is not exempt from the secondary
containment requirements in accordance with 335-14-6-.10(4)(g), then,
1. The closure plan for the tank system must
include both a plan for complying with 335-14-6-.10(8)(a) and a contingent plan
for complying with 335-14-6-.10(8) (b).
2. A contingent post-closure plan for
complying with 335-14-6-.10(8)(b) must be prepared and submitted as part of the
permit application.
3. The cost
estimates calculated for closure and post-closure care must reflect the costs
of complying with the contingent closure plan and the contingent post-closure
plan, if these costs are greater than the costs of complying with the closure
plan prepared for the expected closure under 335-14-6-.10(8) (a).
4. Financial assurance must be based on the
cost estimates in 335-14-6-.10 ( 8) (e)3 .
5. For the purposes of the contingent closure
and post-closure plans, such a tank system is considered to be a landfill, and
the contingent plans must meet all of the closure, post-closure, and financial
responsibility requirements for landfills under Rules
335-14-6-.07
and
335-14-6-.08.
(9)
Special
requirements for ignitable or reactive wastes.
(a) Ignitable or reactive waste must not be
placed in a tank system, unless:
1. The waste
is treated, rendered, or mixed before or immediately after placement in the
tank system so that:
(i) The resulting waste,
mixture or dissolved material no longer meets the definition of ignitable or
reactive waste under
335-14-2-.03(2)
or
335-14-2-.03(4);
and
2. The waste is stored or treated in such a
way that it is protected from any material or conditions which may cause the
waste to ignite or react; or
3. The
tank system is used solely for emergencies.
(b) The owner or operator of a facility where
ignitable or reactive waste is stored or treated in tanks must comply with the
requirements for the maintenance of protective distances between the waste
management area and any public ways, streets, alleys, or an adjoining property
line that can be built upon as required in Tables 2-1 through 2-6 of the
National Fire Protection Association's "Flammable and Combustible Liquids
Code", (1977 or 1981) [incorporated by reference in Rule
335-14-1-.02
(297) ] .
(10)
Special requirements for incompatible wastes.
(a) Incompatible wastes, or incompatible
wastes and materials, must not be placed in the same tank system, unless
335-14-6-.02(8)(b)
is complied with.
(b) Hazardous
waste must not be placed in a tank system that has not been decontaminated and
that previously held an incompatible waste or material, unless
335-14-6-.02(8)(b)
is complied with.
(11)
Waste analysis and trial tests. In addition to
performing the waste analysis required by
335-14-6-.02(4),
the owner or operator must, whenever a tank system is to be used to treat
chemically or to store a hazardous waste that is substantially different from
waste previously treated or stored in that tank system; or treat chemically a
hazardous waste with a substantially different process than any previously used
in that tank system:
(a) Conduct waste
analyses and trial treatment or storage tests (e.g., bench-scale or pilot-plant
scale tests); or
(b) Obtain
written, documented information on similar waste under similar operating
conditions to show that the proposed treatment or storage will meet the
requirements of 335-14-6-.10(5) (a).
[Note:
335-14-6-.02(4)
requires the waste analysis plan to include analyses needed to comply with
335-14-6-.10(9) and 335-14-6-.10(10).
335-14-6-.05(4)
requires the owner or operator to place the results from each waste analysis
and trial test, or the documented information, in the operating record of the
facility. ]
(12)
Special requirements for Small Quantity Generators that accumulate
hazardous waste in tanks.
(a) The
requirements of 335-14-6-.10(12) apply to Small Quantity Generators that
accumulate hazardous waste in tanks for less than 180 days (or 270 days if the
generator must ship the waste greater than 200 miles), and do not accumulate
over 6,000 kg on-site at any time.
(b) Small Quantity Generators must comply
with the following general operating requirements:
1. Treatment or storage of hazardous waste in
tanks must comply with
335-14-6-.02(8)(b).
2. Hazardous wastes or treatment reagents
must not be placed in a tank if they could cause the tank or its inner liner to
rupture, leak, corrode, or otherwise fail before the end of its intended
life.
3. Uncovered tanks must be
operated to ensure at least 60 centimeters (2 feet) of freeboard, unless the
tank is equipped with a containment structure (e.g., dike or trench), a
drainage control system, or a diversion structure (e.g., standby tank) with a
capacity that equals or exceeds the volume of the top 60 centimeters (2 feet)
of the tank.
4. Where hazardous
waste is continuously fed into a tank, the tank must be equipped with a means
to stop this inflow (e.g., waste feed cutoff system or by-pass system to a
stand-by tank).
[Note: These systems are intended to be used in
the event of a leak or overflow from the tank due to a system failure (e.g., a
malfunction in the treatment process, a crack in the tank, etc. ) . ]
(c) Except as noted in
335-14-6-.10(12) (d), Small Quantity Generators accumulating hazardous waste in
tanks must inspect, and document in accordance with Rule
335-14-6-.02(6)(d),
where present:
1. Discharge control equipment
(e.g., waste feed cutoff systems, by-pass systems, and drainage systems) at
least once each operating day, to ensure that it is in good working
order;
2. Data gathered from
monitoring equipment (e.g., pressure and temperature gauges) at least once each
operating day to ensure that the tank is being operated according to its
design;
3. The level of waste in
the tank at least once each operating day to ensure compliance with
335-14-6-.10(12)(b)3.;
4. The
construction materials of the tank at least weekly to detect corrosion or
leaking of fixtures or seams; and
5. The construction materials of, and the
area immediately surrounding discharge confinement structures (e.g., dikes) at
least weekly to detect erosion or obvious signs of leakage (e.g., wet spots or
dead vegetation).
[Note: As required by
335-14-6-.02(6)(c),
the owner or operator must remedy any deterioration or malfunction he
finds.
(d) Small
Quantity Generators accumulating hazardous waste in tanks or tank systems that
have full secondary containment and that either use leak detection equipment to
alert facility personnel to leaks, or implement established workplace practices
to ensure leaks are promptly identified, must inspect at least weekly, where
applicable, the areas identified in 335-14-6-.10(12) (c) l. through 5. Use of
the alternate inspection schedule must be documented in the facility's
operating record. This documentation must include a description of the
established workplace practices at the facility.
(e) Small Quantity Generators accumulating
hazardous waste in tanks must, upon closure of the facility, remove all
hazardous waste from tanks, discharge control equipment, and discharge
confinement structures.
[Note: At closure, as throughout the operating
period, unless the owner or operator can demonstrate, in accordance with
335-14-2-.01(3)(c) or
(d), that any solid waste removed from his
tank is not a hazardous waste, the owner or operator becomes a generator of
hazardous waste and must manage it in accordance with all applicable
requirements of 335-14-3, 335-14-4, and 335-14-6.]
(e) Small Quantity Generators must comply
with the following special requirements for ignitable or reactive waste:
1. Ignitable or reactive waste must not be
placed in a tank, unless:
(i) The waste is
treated, rendered, or mixed before or immediately after placement in a tank so
that:
(I) The resulting waste, mixture, or
dissolution of material no longer meets the definition of ignitable or reactive
waste under
335-14-2-.03(2)
or
335-14-2-.03(4);
and
(ii) The waste is stored or treated in such a
way that it is protected from any material or conditions that may cause the
waste to ignite or react; or
(iii)
The tank is used solely for emergencies.
2. The owner or operator of a facility which
treats or stores ignitable or reactive waste in covered tanks must comply with
the buffer zone requirements for tanks contained in Tables 2-1 through 2-6 of
the National Fire Protection Association's "Flammable and Combustible Liquids
Code", (1977 or 1981) [incorporated by reference in Rule
335-14-1-.02(2)
].
(f) Small Quantity
Generators must comply with the following special requirements for incompatible
wastes:
1. Incompatible wastes, or
incompatible wastes and materials (see 335-14-6 -Appendix V for examples) must
not be placed in the same tank, unless
335-14-6-.02(8)(b)
is complied with.
2. Hazardous
waste must not be placed in an unwashed tank which previously held an
incompatible waste or material, unless
335-14-6-.02(8)(b)
is complied with.
(13)
Air emission
standards. The owner or operator shall manage all hazardous waste
placed in a tanks in accordance with the applicable requirements of
335-14-6-.27,
335-14-6-.28,
and
335-14-6-.29.
Notes
Ala. Admin. Code r.
335-14-6-.10
November 19, 1980.
Amended: July 19, 1982; February 15, 1988; August 24, 1989; December 6, 1990;
January 25, 1992, Amended: Filed November 30, 1994; effective January 5, 1995.
Amended: Filed February 21, 1997; effective March 28, 1997. Amended: Filed
February 20, 1998; effective March 27, 1998. Amended: Filed February 26, 1999;
effective April 2, 1999. Amended: Filed March 9, 2001; effective April 13,
2001. Amended: Filed February 8, 2002; effective March 15, 2002. Amended: Filed
March 13, 2003; effective April 17, 2003. Amended: Filed February 24, 2005;
effective March 31, 2005. Amended: February 28, 2006; effective April 4, 2006.
Amended: February 27, 2007; effective April 3, 2007. Amended: Filed April 22,
2008; effective May 27, 2008. Amended: February 24, 2009; effective March 31,
2009.
Amended by
Alabama
Administrative Monthly Volume XXXV, Issue No. 05, February 28,
2017, eff. 3/31/2017.
Authors: Stephen C. Maurer; Michael Champion;
Amy P. Zachry; C. Edwin Johnston; Michael B. Champion; Ronald T. Shell; Bradley
N. Curvin; Theresa A. Maines; Vernon H. Crockett
Statutory Authority:
Code of Ala.
1975, ยงยง 22-30 -11,
22-30-16.