(1) Pier foundations shall be installed
directly under the main frame of the home or building. The piers shall not be
further apart than six (6) feet on center when using a minimum pier foundation
of a 16" x 16" x 4" concrete pad or equivalent in the minimum soil bearing
capacity of 2000 lbs. PSF. Piers shall be no more than two feet from each end
of the frame.
(2) The minimum pier
foundation shall be a 16" X 16" X 4" concrete pad, precast or poured in place
concrete slab. All grass and organic material must be removed and the pier
foundation placed on stable soil. The minimum soil bearing capacity for the
minimum pier foundation is 2000 lbs. If the actual soil's bearing capacity is
greater than 2000 lbs., an assumed value of 2,000 lbs. must be used to
determine pier spacing. In a soil bearing capacity below these values, the pier
foundations must be increased in size according to the bearing load and the
soil bearing capacity of the soil. Two (2) 8" X 16" X 4" concrete pads are
considered minimum. All debris, grass, grass sod and other foreign material
that would be under the footers must be removed before footings or pier
foundations are installed. Pier footing must not be placed on a mound. If the
space under the home is to be enclosed with skirting or other material, the
skirting shall be vented, and a ground vapor retarder of 6 mil rated
polyethylene sheeting or equivalent should be installed. Venting shall be
provided for the crawl space at the minimum required by the latest publication
of NCSBCS/ANSI A225.1. The vapor barrier should cover the entire area under the
home and overlap at least 12 inches at all joints. All decayable material, such
as grass, roots, twigs, and wood scraps shall be removed from beneath the
home.
(3) Piers may be manufactured
load-bearing supports or devices and must be approved for the loads and use
intended, or piers shall be constructed of regular 8" X 8" X 16" concrete
blocks, with open cells in a vertical position when placed upon the pier
foundation. A 2" x 8" X 16" treated wood or hardwood plate or a concrete cap
shall be placed on top of the pier to serve as a pier cap. A true 1" thick
hardwood plate is optional. All piers must have a full size cap covering the
pier.
Additional full size plates not less than (1" X 8" X 16") may
be used; but, the additional plates shall not exceed 4" in total height. The
frame may be cushioned with treated wood, hardwood, or other Commission
approved shims (wedges) and the shims shall not occupy more than 1" of vertical
space between the top plate and main frame. One shim at least 4" x 6" nominal
is to be placed on each side of the main frame on single tiered piers. Two
shims are to be placed on each side of the main frame on double tiered piers.
Shims must be used in pairs and driven tight. Concrete block piers are to be
placed perpendicular to the main I beam or frame.
(4) All piers over 32" (over four 8" x 8" x
16" concrete blocks) in height shall be double tiered with the blocks
interlocked.
(5) A minimum of 12"
clearance shall be maintained from beneath the main frame or I beam to the top
of the soil's surface.
(6) The
maximum pier height shall be no more than 60 inches unless designed and
approved by a registered engineer or a higher height/different design is
required by the National Flood Insurance Program (NFIP) floodplain management
criteria.
(7) Exterior
sidewall/marriage wall blocking - In addition to providing piers for supporting
the frame, piers are also required to support the special roof loads. The
support piers are required at all marriage wall and sidewall openings 48" and
greater in width. These piers are to be placed at each side of each opening.
The most commonly occurring openings are sliding glass doors and full bay
windows. Typical marriage wall openings are cathedral openings and passageway
openings which are 48" and larger. Recessed walls are considered sidewall
openings. Each ridge beam column shall be supported by piers under the marriage
wall. Piers shall be placed under heavy loads such as masonry-faced fireplaces,
etc. Marriage walls shall have piers at each end of the home. Exterior door
openings shall have piers or an approved support device on each side.
(8) Marriage wall piers shall be constructed
to the same requirements as all other pier requirements.
(9) Perimeter pier foundations are required
to be 8" X 16" X 4" concrete pads. Perimeter piers shall be single tiered and
placed parallel to the sidewall.
(10) To assure that the manufacturer's
warranty remains valid, all new homes and buildings must be blocked according
to the manufacturer's installation manual.
(11) All new manufactured homes or
manufactured buildings shall be installed in accordance with the manufacturer's
installation instructions. Effective October 20, 2008, the Manufacturer's
Installation Instructions must meet or exceed the minimum requirements of the
HUD Model Manufactured Home Installation Standards. Manufacturers may provide
training to the installers of their homes to include lagging, sealing, and
complete trim out. Paragraphs 1-9 shall apply to all used homes and buildings
when the manufacturer's installation instructions are not available. It is the
installer's responsibility to ascertain for himself which homes may be
installed according to the State's minimum blocking standards.
Notes
Ala. Admin. Code r. 535-X-13-.06
New Rule: Filed June 24,
1993; effective July 29, 1993. Amended: Filed July 27, 2000; effective August
31, 2000; operative October 1, 2000. Amended: Filed February 4, 2002; effective
March 11, 2002. Amended: Filed July 9, 2003; effective August 13, 2003.
Amended: Filed November 5, 2003; effective December 10, 2003. Amended: Filed
November 8, 2004; effective December 13, 2004. Amended: Filed October 7, 2005;
effective November 11, 2005. Amended: Filed December 6, 2005; effective January
10, 2006. Amended: Filed January 5, 2007; effective February 9, 2007. Amended:
Filed October 7, 2008; effective November 11, 2008. Amended: Filed January 7,
2014; effective February 11, 2014.