8 AAC 61.1160 - Additional power transmission and distribution standards
(a) Notwithstanding
29 C.F.R.
1926.950(c)(1), as amended,
an employer may not allow an employee to perform rubber glove work on energized
lines of 5,000 volts or greater from phase-to-phase or
phase-to-ground.
(b)
Notwithstanding 29 C.F.R.
1926.950(c)(1), as amended,
an employer may not allow an employee to approach or take any conductive
object, without an insulating handle that meets the requirements of
29 C.F.R.
1910.269(j)(1), closer to
exposed energized parts of 5,000 volts or greater than shown in Tables R-6 -
R-10 contained in 29 C.F.R.
1910.269, as amended, or Table V-1 contained
in 29 C.F.R.
1926.950, as amended.
Notes
Authority:AS 18.60.020
AS 18.60.030
AS 18.60.075
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.