Cal. Code Regs. Tit. 22, § 60306 - Use of Recycled Water for Cooling
(a) Recycled water used for industrial or
commercial cooling or air conditioning that involves the use of a cooling
tower, evaporative condenser, spraying or any mechanism that creates a mist
shall be a disinfected tertiary recycled water.
(b) Use of recycled water for industrial or
commercial cooling or air conditioning that does not involve the use of a
cooling tower, evaporative condenser, spraying, or any mechanism that creates a
mist shall be at least disinfected secondary-23 recycled water.
(c) Whenever a cooling system, using recycled
water in conjunction with an air conditioning facility, utilizes a cooling
tower or otherwise creates a mist that could come into contact with employees
or members of the public, the cooling system shall comply with the following:
(1) A drift eliminator shall be used whenever
the cooling system is in operation.
(2) A chlorine, or other, biocide shall be
used to treat the cooling system recirculating water to minimize the growth of
Legionella and other micro-organisms.
Notes
Note: Authority cited: Section 13521, Water Code. Reference: Sections 13520 and 13521, Water Code.