(a)
No irrigation with disinfected tertiary recycled water shall take place within
50 feet of any domestic water supply well unless all of the following
conditions have been met:
(1) A geological
investigation demonstrates that an aquitard exists at the well between the
uppermost aquifer being drawn from and the ground surface.
(2) The well contains an annular seal that
extends from the surface into the aquitard.
(3) The well is housed to prevent any
recycled water spray from coming into contact with the wellhead
facilities.
(4) The ground surface
immediately around the wellhead is contoured to allow surface water to drain
away from the well.
(5) The owner
of the well approves of the elimination of the buffer zone
requirement.
(b) No
impoundment of disinfected tertiary recycled water shall occur within 100 feet
of any domestic water supply well.
(c) No irrigation with, or impoundment of,
disinfected secondary-2.2 or disinfected secondary-23 recycled water shall take
place within 100 feet of any domestic water supply well.
(d) No irrigation with, or impoundment of,
undisinfected secondary recycled water shall take place within 150 feet of any
domestic water supply well.
(e) Any
use of recycled water shall comply with the following:
(1) Any irrigation runoff shall be confined
to the recycled water use area, unless the runoff does not pose a public health
threat and is authorized by the regulatory agency.
(2) Spray, mist, or runoff shall not enter
dwellings, designated outdoor eating areas, or food handling
facilities.
(3) Drinking water
fountains shall be protected against contact with recycled water spray, mist,
or runoff.
(f) No spray
irrigation of any recycled water, other than disinfected tertiary recycled
water, shall take place within 100 feet of a residence or a place where public
exposure could be similar to that of a park, playground, or school
yard.
(g) All use areas where
recycled water is used that are accessible to the public shall be posted with
signs that are visible to the public, in a size no less than 4 inches high by 8
inches wide, that include the following wording: "RECYCLED WATER -- DO NOT
DRINK". Each sign shall display an international symbol similar to that shown
in figure 60310-A. The Department may accept alternative signage and wording,
or an educational program, provided the applicant demonstrates to the
Department that the alternative approach will assure an equivalent degree of
public notification.
(h) Except as
allowed under the Cross-Connection Control Policy Handbook, no physical
connection shall be made or allowed to exist between any recycled water system
and any separate system conveying potable water.
(i) Except for use in a cemetery that
complies with the requirements of section 8118 of the Health and Safety Code,
the portions of the recycled water piping system that are in areas subject to
access by the general public shall not include any hose bibs. Only quick
couplers that differ from those used on the potable water system shall be used
on the portions of the recycled water piping system in areas subject to public
access.