Cal. Code Regs. Tit. 22, § 64534.2 - Disinfection Byproducts Monitoring
Table 64534.2-A Routine and Increased Monitoring Frequency for TTHM and HAA5
| COLUMN A Type of System | COLUMN B Persons served | COLUMN C Minimum monitoring frequency | COLUMN D Sample location in the distribution system & increased monitoring frequencies |
| Systems using approved surface water | >=10,000 | Four samples per quarter per treatment plant | At least 25 percent of all samples collected each quarter at locations representing maximum residence time. Remaining samples taken at locations representative of at least average residence time in the distribution system and representing the entire distribution system, taking into account number of persons served, different sources of water, and different treatment methods1. |
| 500-9,999 | One sample per quarter per treatment plant | Locations representing maximum residence time1. | |
| <500 | One sample per year per treatment plant during month of warmest water temperature | Locations representing maximum residence time1. If the sample (or average of annual samples, if more than one sample is taken) exceeds MCL, system shall increase monitoring to one sample per treatment plant per quarter, taken at a point reflecting the maximum residence time in the distribution system, until system meets reduced monitoring criteria in paragraph (3) of this subsection. | |
| Systems using only ground water not under direct influence of surface water and using chemical disinfectant | >=10,000 | One sample per quarter per treatment plant | Locations representing maximum residence time1. |
| <10,000 | One sample per year per treatment plant during month of warmest water temperature | Locations representing maximum residence time1. If the sample (or average of annual samples, if more than one sample is taken) exceeds MCL, system shall increase monitoring to one sample per treatment plant per quarter, taken at a point reflecting the maximum residence time in the distribution system, until system meets reduced monitoring criteria in paragraph (3) of this subsection. | |
| 1 If a system elects to sample more frequently than the minimum required, at least 25 percent of all samples collected each quarter (including those taken in excess of the required frequency) shall be taken at locations that represent the maximum residence time of the water in the distribution system. The remaining samples shall be taken at locations representative of at least average residence time in the distribution system. | |||
Table 64534.2-B Reduced Monitoring Frequency for TTHM and HAA5
| the system may reduce monitoring if it has monitored at least one | |||
| If the system is a(n)... | serving... | year and... | to this level |
| Approved surface water system which has a source water TOC1 level, before any treatment, [LESS THAN EQUAL TO] 4.0 mg/L | >=10,000 | TTHM1 [LESS THAN EQUAL TO]0.040 mg/L and HAA51 [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per quarter at distribution system location reflecting maximum residence time. |
| 500-9,999 | TTHM1 [LESS THAN EQUAL TO]0.040 mg/L and HAA51 [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per year at distribution system location reflecting maximum residence time during month of warmest water temperature. | |
| System using only ground water not under direct influence of surface water and using chemical disinfectant | >=10,000 | TTHM1 [LESS THAN EQUAL TO]0.040 mg/L and HAA51 [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per year at distribution system location reflecting maximum residence time during month of warmest water temperature. |
| <10,000 | TTHM1 [LESS THAN EQUAL TO]0.040 mg/L and HAA51 [LESS THAN EQUAL TO]0.030 mg/L for the system may reduce monitoring if it has monitored at least one | One sample per treatment plant per three-year monitoring cycle at distribution system | |
| two consecutive years OR TTHM1 [LESS THAN EQUAL TO]0.020 mg/L and HAA51 [LESS THAN EQUAL TO]0.015 mg/L for one year | location reflecting maximum residence time during month of warmest water temperature, with the three-year cycle beginning on January 1 following the quarter in which system qualifies for reduced monitoring. | ||
| 1 TOC, TTHM, and HAA5 values based on annual averages. | |||
Table 64534.2-C Routine Monitoring Frequency for TTHM and HAA5
| Minimum monitoring frequency1 | |||
| Source water type | Persons served | Number of distribution system monitoring locations | Monitoring period2 |
| Systems using approved surface water | >=5,000,000 | 20 dual sample sets | per quarter |
| 1,000,000-4,999,999 | 16 dual sample sets | per quarter | |
| 250,000-999,999 | 12 dual sample sets | per quarter | |
| 50,000-249,999 | 8 dual sample sets | per quarter | |
| 10,000-49,999 | 4 dual sample sets | per quarter | |
| 3,301-9,999 | 2 dual sample sets | per quarter | |
| 500-3,300 | 1 TTHM and 1 HAA5 sample: one at the location with the highest TTHM measurement, one at the location with the highest HAA5 measurement | per quarter | |
| <500 | 1 TTHM and 1 HAA5 sample: one at the location with the highest TTHM measurement, one at the location with the highest HAA5 measurement3 | per year | |
| Systems using ground water not under direct influence of surface water | >=500,000 | 8 dual sample sets | per quarter |
| 100,000-499,999 | 6 dual sample sets | per quarter | |
| 10,000-99,999 | 4 dual sample sets | per quarter | |
| 500-9,999 | 2 dual sample sets | per year | |
| <500 | 1 TTHM and 1 HAA5 sample: one at the location with the highest TTHM measurement, one at the location with the highest HAA5 measurement3 | per year | |
| 1 All systems shall monitor during the month of highest disinfection byproduct concentrations. | |||
| 2 Systems on quarterly monitoring shall take dual sample sets every 90 days at each monitoring location, except for systems using approved surface water and serving 500-3,300 persons. | |||
| 3 Only one location with a dual sample set per monitoring period is needed if highest TTHM and HAA5 concentrations occur at the same location and month. | |||
Table 64534.2-D Reduced Monitoring Frequency for TTHM and HAA5
| Minimum monitoring frequency | |||
| Source water type | Persons served | Number of distribution system monitoring locations | Monitoring period1 |
| Systems using approved surface water | >=5,000,000 | 10 dual sample sets: at the locations with the five highest TTHM and five highest HAA5 LRAAs | per quarter |
| 1,000,000-4,999,999 | 8 dual sample sets: at the locations with the four highest TTHM and four highest HAA5 LRAAs | per quarter | |
| 250,000-999,999 | 6 dual sample sets: at the locations with the three highest TTHM and three highest HAA5 LRAAs | per quarter | |
| 50,000-249,999 | 4 dual sample sets: at the locations with the two highest TTHM and two highest HAA5 LRAAs | per quarter | |
| 10,000-49,999 | 2 dual sample sets: at the locations with the highest TTHM and highest HAA5 LRAAs | per quarter | |
| 3,301-9,999 | 2 dual sample sets: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement | per year | |
| 500-3,300 | 1 TTHM and 1 HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter | per year | |
| Systems using only ground water not under direct influence of surface water | >=500,000 | 4 dual sample sets: at the locations with the two highest TTHM and two highest HAA5 LRAAs | per quarter |
| 100,000-499,999 | 2 dual sample sets: at the locations with the highest TTHM and highest HAA5 LRAAs | per quarter | |
| 10,000-99,999 | 2 dual sample sets: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement | per year | |
| 500-9,999 | 1 TTHM and 1 HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set per year if the highest TTHM and HAA5 measurements occurred at the same location and quarter | per year | |
| <500 | 1 TTHM and 1 HAA5 sample: one at the location and during the quarter with the highest TTHM single measurement, one at the location and during the quarter with the highest HAA5 single measurement; 1 dual sample set every third year if the highest TTHM and HAA5 measurements occurred at the same location and quarter | every third year | |
| 1 Systems on quarterly monitoring shall take dual sample sets every 90 days. | |||
Notes
2. Editorial correction of Table 64534.2-B (Register 2007, No. 30).
3. Amendment of subsections (a)(2) and (b)(1)-(3), new subsection (b)(4), amendment of subsections (c)(1)-(2), new subsections (c)(3)-(d)(8) and amendment of NOTE filed 5-22-2012; operative 6-21-2012 (Register 2012, No. 21).
4. Amendment of subsections (a)(2). (c)(2) and (c)(3), repealer of subsections (c)(3)(A)-(B) and amendment of subsection (d)(2) filed 5-28-2014; operative 7-1-2014 (Register 2014, No. 22).
5. Change without regulatory effect amending subsections (a)(1), (b)(3), (c)(2)-(3), (d)(2)-(3) and (d)(6) and amending NOTE filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
6. Editorial correction of Table 64534.2-D within subsection (d)(3) (Register 2021, No. 33).
Note: Authority cited: Sections 116271, 116350 and 116375, Health and Safety Code. Reference: Sections 116350, 116385 and 116555, Health and Safety Code.
2. Editorial correction of Table 64534.2-B (Register 2007, No. 30).
3. Amendment of subsections (a)(2) and (b)(1)-(3), new subsection (b)(4), amendment of subsections (c)(1)-(2), new subsections (c)(3)-(d)(8) and amendment of Note filed 5-22-2012; operative 6-21-2012 (Register 2012, No. 21).
4. Amendment of subsections (a)(2). (c)(2) and (c)(3), repealer of subsections (c)(3)(A)-(B) and amendment of subsection (d)(2) filed 5-28-2014; operative
5. Change without regulatory effect amending subsections (a)(1), (b)(3), (c)(2)-(3), (d)(2)-(3) and (d)(6) and amending Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.