Cal. Code Regs. Tit. 22, § 66264.1052 - Standards: Pumps in Light Liquid Service
(a)
(1)
Each pump in light liquid service shall be monitored monthly to detect leaks by
the methods specified in Section
66264.1063(b),
except as provided in subsections (d), (e), and (f) of this section.
(2) Each pump in light liquid service shall
be checked by visual inspection each calendar week for indications of liquids
dripping from the pump seal.
(b)
(1) If
an instrument reading of 10,000 ppm or greater is measured, a leak is
detected.
(2) If there are
indications of liquids dripping from the pump seal, a leak is
detected.
(c)
(1) When a leak is detected, it shall be
repaired as soon as practicable, but not later than 15 calendar days after it
is detected, except as provided in Section
66264.1059.
(2) A first attempt at repair (e.g.,
tightening the packing gland) shall be made no later than one day (24 hours)
after each leak is detected.
(d) Each pump equipped with a dual mechanical
seal system that includes a barrier fluid system is exempt from the
requirements of subsection (a) of this section, provided the following
requirements are met:
(1) each dual
mechanical seal system shall be:
(A) operated
with the barrier fluid at a pressure that is at all times greater than the pump
stuffing box pressure;
(B) equipped
with a barrier fluid degassing reservoir that is connected by a closed-vent
system to a control device that complies with the requirements of Section
66264.1060; or
(C) equipped with a system that purges the
barrier fluid into a hazardous waste stream with no detectable emissions to the
atmosphere.
(2) The
barrier fluid system shall not be a hazardous waste with organic concentrations
10 percent or greater by weight.
(3) Each barrier fluid system shall be
equipped with a sensor that will detect failure of the seal system, the barrier
fluid system, or both.
(4) Each
pump shall be checked by visual inspection, each calendar week, for indications
of liquids dripping from the pump seals.
(5)
(A)
Each sensor as described in subsections (d)(3) of this section shall be checked
daily or be equipped with an audible alarm that shall be checked monthly to
ensure that it is functioning properly.
(B) The owner or operator shall determine,
based on design considerations and operating experience, a criterion that
indicates failure of the seal system, the barrier fluid system, or
both.
(6)
(A) If there are indications of liquids
dripping from the pump seal or the sensor indicates failure of the seal system,
the barrier fluid system, or both based on the criterion determined in
subsection (d)(5)(B) of this section, a leak is detected.
(B) When a leak is detected, it shall be
repaired as soon as practicable, but not later than 15 calendar days after it
is detected, except as provided in Section
66264.1059.
(C) A first attempt at repair (e.g.,
relapping the seal) shall be as soon as possible, to minimize escape of
hazardous constituents to the environment, but not later than 24 hours after
each leak is detected.
(e) Any pump that is designated, as described
in Section
66264.1064(g)(2),
for no detectable emissions, as indicated by an instrument reading of less than
500 ppm above background, is exempt from the requirements of subsections (a),
(c), and (d) of this section if the pump meets the following requirements:
(1) the pump shall have no externally
actuated shaft that shall penetrate the pump housing;
(2) the pump shall operate with no detectable
emissions as indicated by an instrument reading of less than 500 ppm above
background as measured by the methods specified in Section
66264.1063(c);
and
(3) the pump must be tested for
compliance with subsection (e)(2) of this section initially upon designation,
annually, and at other times as required by the Department.
(f) If any pump is equipped with a
closed-vent system capable of capturing and transporting any leakage from the
seal or seals to a control device that complies with the requirements of
Section 66264.1060, it is exempt from the
requirements of subsections (a) through (e) of this section.
Notes
2. Change without regulatory effect amending subsection (f) filed 12-28-95 pursuant to section 100, title 1, California Code of Regulations (Register 95, No. 52).
Note: Authority cited: Sections 25150 and 25159, Health and Safety Code. Reference: Sections 25159 and 25159.5, Health and Safety Code; 40 CFR section 264.1052.
2. Change without regulatory effect amending subsection (f) filed 12-28-95 pursuant to section 100, title 1, California Code of Regulations (Register 95, No. 52).
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.