Cal. Code Regs. Tit. 22, § 66264.1054 - Standards: Pressure Relief Devices in Gas/Vapor Service
(a) Except during pressure releases, each
pressure relief device in gas/vapor service shall be operated with no
detectable emissions, as indicated by an instrument reading of less than 500
ppm above background, as measured by the method specified in Section
66264.1063(c).
(b)
(1)
After each pressure release, the pressure relief device shall be returned to a
condition of no detectable emissions, as indicated by an instrument reading of
less than 500 ppm above background, as soon as practicable, but no later than
24 hours after each pressure release, except as provided in Section
66264.1059.
(2) No later than 24 hours after the pressure
release, the pressure relief device shall be monitored to confirm the condition
of no detectable emissions, as indicated by an instrument reading of less than
500 ppm above background, as measured by the method specified in Section
66264.1063(c).
(c) Any pressure relief device that is
equipped with a closed-vent system capable of capturing and transporting
leakage from the pressure relief device to a control device as described in
Section 66264.1060 is exempt from the
requirements of subsections (a) and (b) of this section.