Current through Register Vol. 46, No. 15, April 8, 2022
a)
Measurement Location
1) Short-term or
long-term measurements shall be made, at the same time, in each lowest
structural area suitable for occupancy. For example, a split-level building
with a basement, a slab-on-grade room and a room over crawlspace shall have
measurements made in each of the foundation types: the basement, a
slab-on-grade room and a room over the crawlspace.
A) Measurements shall be made in rooms that
can be regularly occupied by individuals, such as family rooms, living rooms,
dens, playrooms and bedrooms.
B)
Charcoal canisters of any type shall not be placed in bathrooms, kitchens,
laundry rooms, spa rooms or other areas of high humidity.
C) When the area of the home being tested is
over 2000 square feet, an additional test location is required for each 2000
square feet of the area being tested.
D) Measurement devices shall be placed in the
general breathing zone and shall be:
i)
Undisturbed during the measurement period;
ii) At least 3 feet from exterior doors,
windows to the outside, or ventilation ducts;
iii) Out of the direct flow of air from the
ventilation duct;
iv) At least 1
foot from exterior walls;
v) 20
inches to 6 feet from the floor;
vi) At least 4 inches away from other objects
horizontally or vertically above the detector;
vii) At least 4 feet from heat, fireplaces
and furnaces, out of direct sunlight, etc.;
viii) At least 7 feet from sump
pits.
E) Measurement
devices may be suspended in the general breathing zone and, if suspended, shall
be 20 inches to 6 feet above the floor and at least 1 foot below the
ceiling.
F) Measurements made in
closets, cupboards, sumps, crawlspaces or nooks within the foundation shall not
be used as a representative measurement and shall not be the basis for a
decision to, or not to, mitigate the radon level within a building.
b) Measurements
1) A short-term measurement shall range in
duration from 48 hours to 90 days, depending upon the measurement device used.
Unoccupied homes shall be tested with the HVAC system set and operating
throughout the measurement interval in the normal range, such as 72 degrees F
plus or minus 5 degrees F.
A) Short-term
measurements shall be made under closed-building conditions. In measurements
lasting more than seven days and less than 90 days, closed-house conditions
shall be maintained as much as possible while the measurement is in
progress.
B) Closed building
conditions shall begin at least 12 hours prior to the beginning of the
measurement period for measurements lasting less than 96 hours.
C) The following conditions shall be complied
with during closed-building conditions:
i)
Operation of permanently installed HVAC systems shall continue during
closed-building conditions. Radon Measurement licensees shall inform the
resident in writing that operation of dryers, range hoods, bathroom fans and
other mechanical systems that draw air out of the building may adversely affect
the measurement results.
ii) In
buildings having permanently installed radon mitigation systems, the mitigation
system shall be functioning during the measurement interval.
iii) Air conditioning systems that recycle
interior air may be operated during closed-building conditions.
iv) All windows shall be kept closed.
Individuals licensed in accordance with the Home Inspector License Act [225
ILCS 441 ] may momentarily open and reclose windows when performing an
inspection, after informing the measurement licensee of the
inspection.
v) All external doors
shall be closed except for normal entry and exit. Structural openings due to
disrepair or structural defects shall be repaired to correct their condition
prior to initiation of closed-building conditions. All exterior windows and
doors shall be inspected by a Radon Measurement Professional licensee or Radon
Measurement Technician at the placement and retrieval of the detectors and the
result of the inspection documented for the measurement file.
vi) Whole-house fans shall not be operated.
Portable window fans shall be removed from the window or sealed in place.
Window air conditioning units shall only be operated in a recirculating mode.
If the building contains an air handling system, the air handling system shall
not be set for continuous operation unless the air handling equipment is
specifically used for radon control and is so labeled.
vii) Fireplaces or combustion appliances,
except water heaters and cooking appliances, shall not be operated unless they
are the primary sources of heat for the building.
viii) Ceiling fans, portable dehumidifiers,
portable humidifiers, portable air filters and window air conditioners shall
not be operated within 20 feet of the detector.
D) Short-term measurements of less than 96
hours shall not be conducted during severe storms or periods of sustained high
winds (30 miles per hour or more). Radon Measurement licensees shall check and
document local weather forecasts prior to placing short-term measurement
devices when the measurement period is less than 96 hours.
AGENCY NOTE: The National Weather Service defines a severe
storm as a storm that generates winds of 58 mph and/or 3/4-inch diameter hail
and that may produce tornadoes - not necessarily in that order.
E) The Radon Measurement licensee
shall document that instructions describing closed-building conditions in
subsection (b)(1) were provided for the person who controls the building in
accordance with subsections (d)(1) and (2).
2) The Radon Measurement licensee shall
advise the resident in accordance with Appendix A.
3) Follow-up measurements shall be conducted
in the same location as the initial measurement, provided the initial
measurement was performed in accordance with acceptable measurement placement
protocol.
4) The results of both
initial and follow-up measurements and the average of duplicate measurements
shall be reported. The average shall be considered appropriate as the basis for
determining the need for mitigation.
c) Options for Real Estate Testing
1) Option 1: Simultaneous Testing
A) Simultaneous testing shall be comprised of
a minimum of 2 indoor radon measurements conducted simultaneously with similar
measurement devices (see Appendix C).
B) Simultaneous tests shall be:
i) Co-located and spaced 4 to 5 inches
apart;
ii) Exposed for the same
measurement period; and
iii)
Produce results in the same units (pCi/L or WL).
C) The results of both measurements and the
average of the simultaneous measurements shall be reported and shall be
considered appropriate as the basis for determining the need for
mitigation.
D) Simultaneous
measurement results that are both less than 4.0 pCi/L shall agree with a
Relative Percent Difference (RPD) of less than 67 percent. RPD is the
difference between the 2 results divided by the average of the 2 results times
100. If the RPD is greater than 67 percent, the Radon Measurement Professional
licensee shall investigate, document and correct the sources of the
error.
E) When one of the
measurements is equal to or greater than 4.0 pCi/L and one is less than 4.0
pCi/L, and the higher result is greater than twice the lower result, the client
shall be informed of the large discrepancy and the simultaneous measurements
repeated at no added cost to the client.
F) Simultaneous measurement results that are
both equal to or greater than 4.0 pCi/L shall agree with a RPD of less than 36
percent. If the RPD is greater than 36 percent, the Radon Measurement
Professional licensee shall investigate, document and correct the sources of
the error.
G) The precision of
simultaneous measurements shall be monitored and recorded in the quality
assurance records. The analysis of data from simultaneous measurements shall be
plotted on range control charts. If the precision estimated by the user is not
within the precision expected of the measurement method, the cause of the
problem shall be investigated and corrective action taken in accordance with
the licensee's Agency-approved quality program.
2) Option 2: Continuous Monitor Testing
A) This option requires an active continuous
monitor that has the capability to integrate and record a new result at least
hourly. Shorter integration periods and more frequent data logging afford
greater ability to detect unusual variations in radon or radon progeny
concentrations.
B) The minimum test
measurement period shall be 48 hours. The first 4 hours of data from a
continuous monitor may be discarded or incorporated into the result using
system correction factors. There shall be at least 44 contiguous hours of
usable data to produce a valid average.
i) The
"backing out" of data (i.e., removal of portions imbedded in the 44 contiguous
hours of monitoring) shall invalidate the measurement.
ii) The periodic results shall be averaged to
produce a result that is reported to the client.
3) Additional Requirement for Real
Estate Option Testing
A) Real Estate Option
tests shall be conducted in accordance with subsections (a)(1) and
(b)(1).
B) The measurement exposure
time shall be a minimum of 48 hours.
C) Measurement licensees shall establish
controls consistent with the devices used in their measurements to prevent
interference and document those controls in accordance with subsection
(l)(1).
d)
Non-Interference Agreement
1) The buyer,
seller, occupant, real estate professional or other individual in control of
the property shall sign a non-interference agreement indicating an
understanding of the testing conditions, the penalties for interference with an
in-progress radon measurement, and that any test interference that is detected
will be documented in the report and will invalidate the measurement
results.
2) If such an agreement
cannot be or will not be signed by the buyer, seller, occupant, real estate
professional or other individual in control of the property, the Radon
Measurement licensee shall document on the agreement why the signature was not
obtained. The agreement shall be retained for inspection by the
Agency.
e) Radon
Measurement In Progress Notification. The licensee shall post at every building
entry and in a conspicuous location a Radon Measurement In Progress
Notification. The Notice shall be posted upon initiation of a radon
measurement. A copy of a Radon Measurement In Progress Notice is provided in
Appendix D.
f) Multi-Family
Building Measurements. Professional licensees shall submit standard operating
procedures for the performance of multi-family building measurements.
AGENCY NOTE: This subsection does not apply to measurements in
an individual condominium unit.
1)
Initial measurements shall be short-term measurements of at least 48 hours to
90 days, depending on the device used, and shall be made in regularly occupied
rooms in contact with the soil, whether the contact is slab-on-grade, a
basement, a berm, a room above a crawlspace or any combination.
A) Regularly occupied rooms include bedrooms,
offices, dens, family rooms, work areas and play rooms.
B) A minimum of one detector shall be placed
per every 2000 square feet of open floor area.
2) Regularly occupied rooms shall be tested
simultaneously.
A) The licensee shall ensure
that each occupant/resident is provided information regarding necessary test
conditions.
B) The licensee shall
perform and document a surveillance of the building to determine the rooms
needing testing prior to placement.
3) Follow-up Measurements
A) Follow-up measurements shall be performed
in every room with a short-term, initial measurement result of 4.0 pCi/L or
greater, unless measurements are during a real estate transaction. Refer to
Appendix A.
B) If performing
measurements in accordance with subsection (c), Options for Real Estate
Testing, follow-up measurements are not required. Refer to Appendix
B.
4) During both
initial and follow-up measurements, the HVAC system shall be operated normally.
An understanding of the design, operation and maintenance of a building's HVAC
system and how it influences indoor air conditions is essential for
understanding, managing and developing a measurement strategy in multi-family
buildings. If the units of a building have a common HVAC system, the building
shall be tested by a licensee licensed to perform measurements in commercial
buildings.
5) The Radon Measurement
Professional licensee shall recommend in writing to the multi-family building
management, owners or representatives that a decision to mitigate be based on
Appendix A or Appendix B, as applicable.
6) Multi-family building measurements shall
be performed in accordance with subsections (a) through (e) and (h) through
(n).
A) A Device Placement Log and Floor Plan
shall be finalized for each multi-family building in which radon or radon
progeny measurements are made.
B)
All measurements devices, including duplicate measures and blanks, shall be
noted on the Device Placement Log and by serial number.
7) Requirements for Specific Multi-Family
Building Designs
A) Slab-on-Grade Design.
Measure a regularly-occupied room in each unit in contact with the
ground.
B) Crawlspace Design.
Measure a regularly-occupied room directly in each unit above an enclosed
crawlspace.
C) Basement Design. In
addition to measuring a regularly-occupied basement room in each unit, measure
a regularly-occupied room in each unit above the basement that has at least one
wall with substantial contact with the ground.
g) School and Commercial Building
Measurements. Professional licensees shall submit standard operating procedures
for the performance of school and commercial building measurements.
1) Initial measurements shall be short-term
measurements of at least 48 hours to 90 days, depending on the device used, and
shall be made in all frequently occupied rooms in contact with the soil,
whether the contact is slab-on-grade, a basement, berm, a room above a
crawlspace or any combination.
A) Frequently
occupied rooms include classrooms, offices, conference rooms, gymnasiums,
auditoriums, cafeterias and break rooms.
B) Testing need not be conducted in
infrequently used areas such as storage rooms, stairwells, restrooms, utility
closets, elevator shafts or hallways.
C) A minimum of one detector shall be placed
per every 2000 square feet of open floor area.
D) Schools and commercial buildings shall
only be tested for radon during periods when the HVAC system is operating as it
does normally when the buildings are occupied, even if the testing occurs when
school is not in session or during long holidays.
2) All frequently occupied rooms shall be
tested simultaneously.
A) The licensee shall
ensure that the teacher or frequent adult user of the room being tested is
aware of the detector.
B) The
licensee shall perform and document a surveillance of the building to determine
the rooms needing testing prior to placement.
C) The measurement professional shall review
any School Screening Measurements available and may accept those measurements
as valid in determining any additional appropriate testing
strategies.
3) Follow-up
measurements shall be performed in every room with a short-term, initial
measurement result of 4.0 pCi/L or greater. Refer to Appendix A.
4) During both initial and follow-up
measurements, the HVAC system shall be operated normally.
5) The Radon Measurement Professional
licensee shall recommend in writing to the school or commercial building
management, owners or representatives that a decision to mitigate not be based
on initial measurement results.
6)
School and commercial building measurements shall be performed in accordance
with subsections (a) and (b).
A) School and
commercial building measurements of less than 96 hours duration shall be
performed under closed-building conditions as described in subsection
(b)(1).
B) Duplicate measurements
shall be performed and shall represent 10 percent of all the detectors
deployed, or a maximum of 50 detectors, whichever is less, within the
building.
C) Blank measurements
shall be performed and shall represent 5 percent of all the detectors deployed,
or a maximum of 25 detectors, whichever is less, within the building.
D) Licensees using passive monitors shall
conduct spiked measurements at the rate required in Section
422.140(a)(2)(B)(ii).
E) A Device Placement Log and Floor Plan
shall be finalized for each school or commercial building in which radon or
radon progeny measurements are made. All measurement devices, including
duplicate measures and blanks, shall be noted on the Device Placement Log and
Floor Plan by serial number.
7) Requirements for Specific School and
Commercial Building Designs
A) Slab-on-Grade
Design. Measure all frequently-occupied rooms in contact with the
ground.
B) Open-Plan or Pod Design.
If sections of a pod have moveable walls that can physically separate them from
other sections, measure each section separately. If moveable walls are absent
or inoperable, measure the pod as one room placing detectors every 2000 square
feet.
C) Crawlspace Design. Measure
all rooms directly above an enclosed crawlspace.
D) Basement Design. In addition to measuring
all frequently-occupied basement rooms, measure all frequently occupied rooms
above the basement that have at least one wall with substantial contact with
the ground.
8) The
on-site presence of the Licensed Radon Measurement Professional providing
supervision is required for all radon measurement activities at schools and
commercial buildings.
h)
New Construction Testing Conditions
1) Newly
constructed buildings shall not be tested for radon or radon progeny unless the
installation of the following items is completed:
A) All insulation;
B) All exterior doors with associated
hardware shall be installed prior to testing;
C) All windows;
D) All fireplaces and fireplace
dampers;
E) All heating, air
conditioning, and plumbing appliances;
F) All ceiling covers;
G) All interior trim and coverings for the
exterior walls;
H) All exterior
siding, weatherproofing and caulking;
I) All interior and exterior structural
components; and
J) Any interior or
exterior work that may adversely affect the measurement validity.
2) Unoccupied homes shall be
tested with the HVAC system set and operating in the normal range, such as 72
degrees F plus or minus 5 degrees F.
i) Post-Mitigation Testing
1) Post-mitigation measurements shall not be
conducted if temporary radon reduction measures are in use.
2) Post-mitigation measurements shall be
conducted to determine a system's effectiveness after a permanent radon
reduction system has been fully operational for at least 24 hours but not later
than 30 days following completion and activation of a mitigation system. The
mitigation system shall be operated normally and continuously during the entire
measurement period.
3)
Post-mitigation measurements shall be conducted in accordance with subsections
(a), (b) and (c).
j)
Temporary Radon Reduction Measures
1)
Temporary radon reduction measures include:
A)
The introduction of unconditioned air into the building; or
B) Closure of normally accessible areas of
the building; or
C) Lowering the
thermostat below its normal use range, such as 72 degrees F plus or minus 5
degrees F.
2) Any of the
conditions listed in subsection (k) of this Section shall invalidate
measurement results. The Radon Measurement licensee shall not conduct a
measurement until the conditions have been corrected. The Radon Measurement
licensee shall inform the client and other parties involved in a real estate
transaction that these conditions invalidate the measurement results.
3) Any improper radon reduction efforts that
may affect the measurement results identified prior to, during, or after
initial, follow-up, real estate option or post-mitigation measurements shall
invalidate the measurement results. The Radon Measurement licensee shall not
conduct a measurement until the improper conditions have been
corrected.
4) Post-mitigation
measurements shall not be conducted if any improper radon reduction efforts
that may affect the measurement results are identified.
k) When Radon Measurements Shall Not Be Made
1) Short-term radon measurements of less than
96 hours shall not be conducted during severe storms or periods of sustained
high winds (30 miles per hour or more). Radon Measurement licensees shall check
and document local weather forecasts prior to placing short-term measurement
devices when the measurement period is less than 96 hours.
AGENCY NOTE: The National Weather Service defines a severe
storm as a storm that generates winds of 58 mph, and/or ¾-inch diameter
hail and that may produce tornadoes - not necessarily in that order.
2) Radon measurements of any
duration shall not be made during renovation of a building, especially
renovations involving structural changes, or during renovations of the HVAC
systems or any change that disturbs the normal airflow of the building.
AGENCY NOTE: When renovations are planned, radon measurements
should be made prior to renovations and immediately upon the completion of
renovations.
l)
Quality Assurance for Radon Measurements.
1)
Radon Measurement licensees shall abide by the Quality Assurance Program
described in Section
422.60(a)(5)(I).
2) Measurements not performed in accordance
with subsections (a), (b) and (c) shall be considered inappropriate for the
purpose of determining the need for mitigation or the effectiveness of a
mitigation service.
m)
Measurement Documentation
1) Radon Measurement
Professional licensees shall ensure that sufficient information on each
measurement is recorded in a permanent record to allow for future data
comparisons, interpretations and reporting to clients.
2) Radon Measurement Professional licensees
shall keep the following information in a measurement record that shall be
maintained for inspection for a minimum of 5 years. Additional method-specific
documentation is outlined in Section 422.140.
A) A complete copy of the measurement
report.
B) A description of any
non-interference controls used and copies of non-interference agreements
completed in accordance with subsection (d); and
C) A record of any quality control measures
associated with the test, such as the results of simultaneous measurements,
diagnostic measurements, duplicate measurements, and calculations associated
with the measurement.
n) Measurement Results
1) Measurement results shall be reported in
the units that the device measures.
2) Any measurement results based on radon gas
shall be reported to no more than one decimal place, e.g.,
4.3 pCi/L.
3) All valid individual measurement results
shall be reported.
4) When using
continuous radon monitors, hourly readings shall be included.
5) Measurements made in separate locations
shall not be averaged.
6) The
average of collocated measurement devices shall be reported, as well as the
individual results. Standard mathematical rules shall be followed; i.e., if the
average of two measurements produces a result of 3.95 pCi/L, the result shall
be reported as 4.0 pCi/L.
7) Any
quality control measurements shall be reported as such.
o) Measurement Reports
1) Radon Measurement Professional licensees
shall return radon measurement results to the occupant, the owner of the
building, his/her representatives or the client within 45 days after retrieving
exposed devices. As a minimum, the measurement report shall contain:
A) Measurement results reported in accordance
with subsection (n).
B) The exact
start and stop dates and times of the measurement period.
C) The address of the building measured,
including the zip code.
D) A
description of the measurement device used, its manufacturer, model or type,
and serial numbers or other unique device identification numbers.
E) The names and Illinois radon license
numbers of the licensees placing and retrieving the devices.
F) The name and Illinois license number of
the laboratory analyzing the device, if applicable.
G) A statement describing recommendations
concerning retesting or mitigation provided to the occupant, the owner of the
building, his/her representatives or the client in accordance with Appendix A
or B, as appropriate.
H) A
statement of whether a mitigation system was observed in the building during
placement or retrieval. The statement shall indicate whether the system is PNC
or ASD. If the system is ASD, the statement shall indicate whether the
mitigation system is operating and the mitigation tag number for systems
installed after November 1, 2009.
I) A statement describing any observed
tampering, interference or deviations from the required measurement
conditions.
J) A description of the
condition of any permanent vents that allow outdoor air into the building, such
as crawlspace vents or combustion air supply to combustive
appliances.
K) A description of any
severe weather conditions.
L) The
exact locations of all measurement devices deployed and any information that
would allow for future data comparisons and interpretations. Licensees shall
provide the exact locations by one of the following methods:
i) A scale diagram of the footprint of the
building identifying the windows and doors, finished and unfinished areas, room
use, furnaces, hot water heaters, dryers, combustion appliances, crawlspace
vents, fireplaces, mitigation systems, floor drains and foundation types,
indicating the front of the home and any other pertinent information that may
affect the measurement.
ii) A copy
of Appendix E for each foundation type measured.
2) Laboratories receiving an
exposed device that has been delivered for analysis shall return results to the
client within 45 days. At a minimum, the measurement report shall contain:
A) Measurement results reported in accordance
with subsection (n).
B) The exact
start and stop dates of the measurement period.
C) The address of the building measured,
including the zip code.
D) A
description of the measurement device used, its manufacturer, model or type,
and serial numbers or other unique device identification numbers.
E) The name and Illinois license number of
the laboratory analyzing the device.
p) Devices Placed by Clients. Radon licensees
shall provide the client with the following:
1) For licensees providing measurement
devices to clients, sufficient detectors to ensure that testing is performed
consistent with this Part.
2) The
Agency's address and telephone number.
3) Devices that will be placed by the client
shall be accompanied by instructions on how to use the device. These
instructions shall be consistent with this Section and include specific
information on the minimum and maximum length of time that the device shall be
exposed.