Ill. Admin. Code tit. 35, § 611.1058 - Repeat Monitoring and E. coli Requirements
a) Repeat Monitoring
1) If a sample taken under Sections
611.1054 through
611.1057 is total
coliform-positive, the supplier must collect a set of repeat samples within 24
hours after being notified of the positive result. The supplier must collect no
fewer than three repeat samples for each total coliform-positive sample found.
The Agency may, by a SEP, extend the 24-hour limit on a case-by-case basis if
the supplier has a logistical problem in collecting the repeat samples within
24 hours that is beyond its control. Alternatively, the Agency may implement
criteria for the supplier to use in lieu of case-by-case extensions. In the
case of an extension, the Agency must specify how much time the supplier has to
collect the repeat samples. The Agency cannot waive the requirement for a
supplier to collect repeat samples in subsections (a)(1) through
(a)(3).
2) The supplier must
collect all repeat samples on the same day, except that the Agency may, by a
SEP, allow a supplier with a single service connection to collect the required
set of repeat samples over a three-day period or to collect a larger volume
repeat samples in one or more sample containers of any size, as long as the
total volume collected is at least 300 ml.
3) The supplier must collect an additional
set of repeat samples in the manner specified in subsections (a)(1) through
(a)(3) if one or more repeat samples in the current set of repeat samples is
total coliform-positive. The supplier must collect the additional set of repeat
samples within 24 hours after being notified of the positive result, unless the
Agency extends the limit as provided in subsection (a)(1). The supplier must
continue to collect additional sets of repeat samples until either total
coliforms are not detected in one complete set of repeat samples or the
supplier determines that a coliform treatment technique trigger specified in
Section 611.1059(a) has
been exceeded as a result of a repeat sample being total coliform-positive and
notifies the Agency. If a trigger identified in Section
611.1059 is exceeded as a result
of a routine sample being total coliform-positive, the supplier is required to
conduct only one round of repeat monitoring for each total coliform-positive
routine sample.
4) After a supplier
collects a routine sample and before it learns the results of the analysis of
that sample, if the supplier collects another routine sample from within five
adjacent service connections of the initial sample, and the initial sample,
after analysis, is found to contain total coliforms, then the system may count
the subsequent sample as a repeat sample instead of as a routine
sample.
b) Escherichia
coli (E. coli) Testing
1) If any routine or
repeat sample is total coliform-positive, the supplier must analyze that total
coliform-positive culture medium to determine if E. coli are present. If E.
coli are present, the supplier must notify the Agency by the end of the day
when the supplier is notified of the test result, unless the supplier is
notified of the result after the Agency office is closed and the Agency does
not have either an after-hours phone line or an alternative notification
procedure, in which case the supplier must notify the Agency before the end of
the next business day.
2) The
Agency has the discretion to allow a supplier, on a case-by-case basis, to
forego E. coli testing on a total coliform-positive sample if that supplier
assumes that the total coliform-positive sample is E. coli-positive.
Accordingly, the supplier must notify the Agency as specified in subsection
(b)(1) and the provisions of Section 141.63(c) apply.