Ill. Admin. Code tit. 77, § 300.2830 - Preparation of Drawings and Specifications
a) The preparation of drawings and
specifications shall be executed by or be under the immediate supervision of an
architect registered in the State of Illinois:
b) The first submission shall be the design
development drawings indicating in detail the assignment of all spaces, size or
areas and rooms, and indicating in outline, the fixed and movable equipment and
furniture, and the outline specifications.
c) The plans shall be drawn at a scale
sufficiently large to clearly present the proposed design.
d) The drawings shall include:
1) a plan of each floor including the
basement or ground floor,
2) roof
plan,
3) plot plan showing roads,
parking areas, and sidewalks,
4)
elevations of all facades,
5)
sections through the building,
6)
identification of all fire and smoke compartmentation.
e) Outline specifications shall provide a
general description of the construction including finishes; acoustical
material, floor covering; heating and ventilating systems; description of the
electrical system including the emergency electrical system and the type of
elevators.
f) The total gross floor
area and bed count shall be shown on the drawings.
g) A brief narrative of the proposed program
shall be submitted with the preliminary drawings and outline
specifications.
h) Following
approval of the design development drawings and the outline specifications,
working drawings and specifications shall be submitted. All working drawings
shall be well prepared and clean and distinct prints shall be submitted.
Drawings shall be accurately dimensioned and include all necessary explanatory
notes, schedules and legends. Working drawings shall be complete and adequate
for contract purposes. Drawings shall be prepared for each of the following
branches of work: Architectural, Structural, Mechanical, Electrical and
Plumbing.
1) The architectural drawings shall
show:
A) Site plan showing all topography,
newly established levels and grades, existing structures on the site (if any),
new buildings and structures, roadways, walks, and the extent of the areas to
be landscaped. All structures which are to be removed under the construction
contract shall be shown.
B) Plan of
each floor and roof.
C) Elevation
of each facade.
D) Sections through
building.
E) Elevators and
dumbwaiters drawings delineating shaft details and dimensions, sizes of cab
platforms and doors, travel distances including elevation height of landings,
pit sizes, and machine rooms.
F)
Kitchen, laundry, clean and soiled utility room, special care areas, and
similar areas detailed at a scale to show the locations, type, size and
connection of all fixed and movable equipment.
G) Scale details as necessary at a scale
sufficiently large to properly indicate details of the work.
H) Schedule of finishes.
2) The structural drawings shall show:
A) Plans of foundations, floors, roofs and
all intermediate levels shall show the complete design with sizes, sections,
and the relative location of the various members including:
B) Schedule of beams, girders and
columns.
C) Notes on design data
including the name of the governing building code, values of allowable unit
stresses, assumed live loads, wind loads, earthquake load, and soil bearing
pressures.
D) Details of special
connections, openings, pipe sleeves and expansion joints.
E) Special structures shall include
calculations defining load assumption, shear and moment diagrams and horizontal
and vertical reactions.
3) Mechanical drawings with specifications
shall show the complete heating, cooling and ventilation systems; plumbing,
drainage, stand pipe, and sprinkler systems.
A) Heating, Cooling and Ventilation.
i) Pumps, tanks, boilers and piping and
boiler room accessories.
ii) Air
conditioning systems with required equipment, water and refrigerant piping, and
ducts.
iii) Supply and exhaust
ventilating systems with connections and piping.
iv) Air quantities for all rooms including
supply and exhaust ventilating duct openings.
B) Plumbing, Drainage and Stand Pipe Systems.
i) Size and elevation of: street sewer, house
sewer, house drains, street water main and water service into the
building.
ii) Location and size of
soil, waste, and vent stacks with connections to house drains, cleanouts,
fixtures and equipment.
iii) Size
and location of hot, cold and circulating mains, branches, and risers from the
service entrance, and tanks.
iv)
Riser diagram of all plumbing stacks with vents, water risers and fixture
connections.
v) Gas, oxygen and
similar piped systems.
vi) Stand
pipe and sprinkler systems.
vii)
All fixtures and equipment that require water and drain connections.
4) Electrical drawings
shall show all electrical wiring, outlets, and equipment which require
electrical connections.
A) Electrical service
entrance with switches and feeders to the public service feeders,
characteristics of the light and power current, transformers and their
connections.
B) Location of main
switchboard, power panels, light panels and equipment. Feeder and conduit sizes
shall be shown with schedule of feeder breakers or switches.
C) Light outlets, receptacles, switches,
power outlets, and circuits.
D)
Telephone layout showing service entrance, telephone switchboard, strip boxes,
telephone outlets and branch conduits as approved by the telephone company.
Where public telephones are used for inter-communication, provide separate room
and conduits for racks and automatic switching equipment as required by the
telephone company.
E) Nurses' call
systems with outlets for beds, duty stations, corridor signal lights,
annunciators and wiring diagrams.
F) Fire alarm system with stations, signal
devices, control board and wiring diagrams.
G) Emergency electrical system with outlets,
transfer switch, source of supply, feeders, and circuits.
H) All other electrically operated systems
and equipment.
5) When
the project is an addition, details and information on the existing building
shall be provided as follows:
A) Type of
activities within the existing building and distribution of existing
beds.
B) Type of construction of
existing building and number of stories in height.
C) Plans and details showing attachment of
new construction to the existing structure.
D) Mechanical and Electrical systems showing
connections to the existing system.
E) The Department may require submission of
drawings of all or any part of the existing structure, depending upon the
extent of the modification.
6) Specifications shall supplement the
drawings and shall: Describe, except where fully indicated and described on the
drawings, the materials, workmanship, kind, sizes, capacities, finishes, and
other characteristics of all materials, products, articles and
devices.
Notes
Amended at 13 Ill. Reg. 4684, effective March 24, 1989
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.