Ill. Admin. Code tit. 77, § 300.2910 - Structural
a) General Design
Requirements
1) The buildings and all parts
thereof shall be of sufficient strength to support all dead, live, and lateral
loads without exceeding the working stresses permitted for the materials of
their construction in generally accepted good engineering practice.
(B)
2) Special provision shall be
made for loads which have a greater load than the specified minimum live load,
including partitions which are subject to change of location. (B)
b) Construction shall be in
accordance with the requirements of National Fire Protection Association
Standard 101, Life Safety Code, and the minimum requirements contained herein.
(A, B)
1) Foundations shall rest on natural
solid ground and shall be carried to a depth of not less than one foot below
the estimated frost line or shall rest on leveled rock or load-bearing piles or
caissons when solid ground is not encountered. Footings, piers, and foundation
walls shall be adequately protected against deterioration from the action of
ground water. It is recommended that soil test borings be taken to establish
proper soil-bearing values for the soil at the building site.
2) Assumed live loads shall be in accordance
with the International Conference Building Officials Uniform Building
Code.
3) The fire resistance rating
of the structural members shall be as established by National Fire Protection
Association Standard 220 (Standard Types of Building Construction).
c) Provisions for Natural
Disasters (B)
1) Earthquakes: In regions where
local experience shows that earthquakes have caused loss of life or extensive
property damage, buildings and structures shall be designed to withstand the
force assumptions specified in the International Conference Building Officials
Uniform Building Code. Seismic zones are identified on the attached map.
(B)
2) Tornadoes and Floods:
Special provisions shall be made in the design of buildings, including
structural design, in regions where local experience shows loss of life or
damage to buildings resulting from hurricanes, tornadoes, or floods.
(B)
Notes
Amended at 13 Ill. Reg. 4684, effective March 24, 1989
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.