Ill. Admin. Code tit. 77, § 300.2920 - Mechanical Systems
a) General
Requirements
1) Mechanical systems shall be
tested, balanced, and operated to demonstrate that the installation and
performance of these systems conform to the requirements of this
Section.
2) Upon the completion of
the contract, the owner shall be furnished with a complete set of
manufacturer's operating and preventative maintenance instructions, a parts
list with numbers and descriptions for each piece of equipment, and a copy of
the air-balance report. A complete set of these documents shall be kept on the
premises.
3) The owner shall be
provided with instructions in the operational use of the systems and
equipment.
b) Thermal and
acoustical insulation shall be provided as set forth in the ASHRAE Handbook of
Fundamentals and the Handbook of Applications and NFPA 90A. Commercial kitchen
grease hoods shall be insulated according to NFPA 96 and in accordance with the
insulation manufacturer's installation instructions. Domestic water piping that
is accessible to residents shall be insulated as required by the Illinois
Accessibility Code. Insulation shall be provided for the following:
1) Boilers, smoke breeching, and
stacks;
2) Steam supply and
condensate return piping;
3) Hot
water piping above 180 degrees Fahrenheit and all water heaters, generators,
and convertors;
4) Hot water piping
above 125 degrees Fahrenheit that is exposed to contact by residents;
5) Chilled water, refrigerant, and other
process piping and equipment operating with fluid temperatures below the
ambient dew point;
6) Water supply
and drainage piping on which condensate may occur;
7) Air ducts and casings with outside surface
temperatures below the ambient dew point; and
8) Other piping, ducts, and equipment as
necessary to maintain the efficiency of the system.
c) Insulation may be omitted from hot water
and steam condensate piping that is not subject to contact by residents when
the insulation is not necessary for preventing excessive system heat loss or
excessive heat gain.
d) Insulation,
including finishes and adhesives on exterior surfaces of ducts, pipes, and
equipment, shall have a flame spread rating of 25 or less and a smoke-developed
rating of 50 or less as determined by an independent testing laboratory in
accordance with the American Society for Testing and Materials Standard E84.
Exception: Duct, pipe, and equipment coverings shall not be required to meet
these requirements if they are located entirely outside of a building, do not
penetrate a wall or roof, or do not create an exposure hazard.
e) Steam and Hot Water Systems. Supply and
return mains and risers for cooling, heating, and process steam systems shall
be valved to isolate the various sections of each system. Each piece of
equipment shall be valved at the supply and return ends.
f) Thermal Hazards. Any surface that is
accessible to residents and exceeds a temperature of 140 degrees Fahrenheit
(such as radiators, hot water or steam pipes, baseboard heaters, or therapy
equipment) shall be provided with partitions, screens, shields, or other means
to protect residents from injury. Any protective device shall be designed and
installed so that it does not present a fire or safety hazard or adversely
affect the safe operation of the equipment.
g) Heating, Ventilating, and Air Conditioning
Systems
1)
Areas of a nursing home
used by residents of the nursing home shall be air conditioned
and heated by means of operable air-conditioning and heating equipment. The
areas subject to this air-conditioning and heating requirement include, without
limitation, bedrooms or common areas such as sitting rooms, activity rooms,
living rooms, community rooms, and dining rooms. (Section 3-202(8) of
the Act)
A) The mechanical system shall be
capable of maintaining a temperature of at least 75 degrees Fahrenheit,
pursuant to the requirements of Section
300.670(j).
B) The air-conditioning system shall be
capable of maintaining an ambient air temperature of between 75 degrees
Fahrenheit and 80 degrees Fahrenheit, pursuant to the requirements of Section
300.670(j).
2) All ventilation supply, return, and
exhaust systems shall be mechanically operated.
3) Outdoor air intakes shall be located as
far as practical, but not less than 15 feet, from the exhaust outlets of
ventilation systems, combustion equipment stacks, plumbing vent stacks, or
areas that may collect vehicular exhaust and other noxious fumes, including the
exhaust stream from fuel-fired heating, ventilating and air conditioning (HVAC)
sections. The bottom of outdoor air intakes serving central systems shall be
located as high as practical, but not less than six feet above ground level,
or, if installed above the roof, three feet above roof level. For fuel-fired
heating sections of rooftop HVAC units, the exhaust vent may discharge not less
than 36 inches above the highest point of the fresh air intake hood in lieu of
the 15-foot separation.
4) The
ventilation systems shall be designed and balanced to provide the pressure
relationships and ventilation rates as shown in Table B.
5) A differential pressure measuring device
shall be installed across each filter bed serving a central air system. The
device may be a remote readout instrument if the remote readout is readily
visible in a location accessible to the maintenance staff, or if the readout is
displayed on an interactive screen.
6) Air conditioning and ventilating systems
shall be designed, installed, and maintained as required by NFPA 90A. For areas
within the footprint of the facility that are heated by fuel-fired appliances
using an air-to-air heat exchanger, no fewer than two carbon monoxide (CO)
detectors shall be installed in the area served by each heat exchanger. One CO
detector shall be installed within five feet of a supply duct and one within
five feet of a return or exhaust duct. CO detectors shall be line or system
powered and shall signal the building fire alarm system when activated. If
detectors are line powered, a battery back-up or connection to the emergency
power system is required.
7) The
hood and duct system for cooking equipment used in processes that produce smoke
or grease-laden vapors shall comply with NFPA 96. The hood's extinguishment
system shall be connected to the building fire alarm system and shall initiate
a general alarm when activated. Duct insulation that is used in lieu of spacing
from combustible construction members shall terminate at the top of the hood on
the lower end, covering the duct collar, and shall pass through any combustible
nailer opening in the roof/ceiling assembly and into the roof jack assembly.
The material used shall be installed exactly as the manufacturer's
installations require.
8) The
ventilation of the medical gas storage and manifold rooms shall comply with the
requirements of NFPA 99, as applicable, including the gravity option system. If
a concentrator is used to simultaneously fill a portable container and as a
patient breathing device, the standards in NFPA 99 governing the use of medical
gases in resident rooms shall be observed.
9) Boiler rooms and other rooms having
combustion equipment shall be provided with sufficient outdoor air to maintain
combustion rates of equipment and limit temperatures to 20 degrees Fahrenheit
over ambient inside air in adjacent interior spaces. If sealed combustion units
are in use, the discharge line shall remain clear of any adjacent walk paths
and shall be not less than 15 feet from any operable fenestration or air
intakes. NFPA 54 shall apply, including the calculations for combustion air
openings. Effective temperature shall be as defined by the American Society of
Heating, Refrigerating, and Air Conditioning Engineers Handbook of
Fundamentals.
10) Rooms containing
heat-producing equipment, such as boiler rooms, heater rooms, food preparation
centers, laundries, and sterilizer rooms, shall be insulated and ventilated to
prevent any floor surface above from exceeding a temperature of 10 degrees
Fahrenheit above the ambient room temperature. The ventilation rates shown in
Table B shall be considered as minimum acceptable rates and shall not be
construed as precluding the use of higher ventilation rates.
11) Access for filter changing shall be
provided within equipment rooms.
Notes
Amended at 35 Ill. Reg. 3378, effective February 14, 2011
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.