Ill. Admin. Code tit. 77, § 890.1170 - Potable Water Supply Tanks and Auxiliary Pressure Tanks
a) Water Pressure. When the water pressure
from the public water supply main is insufficient during periods of peak flow
or due to the building height to supply all fixtures in accordance with Section
890.1210(c),
the rate of supply shall be supplemented by a gravity tank or auxiliary
pressure (booster) system. Auxiliary pressure systems shall not substitute for
adequate sizing of water distribution piping within the building.
b) Support. All water supply tanks shall be
supported in accordance with local building codes or authorities having
jurisdiction.
c) Tank Supply Inlet
and Outlet. The water supply inlet to the tank shall have a minimum air gap of
at least 6 inches. The supply outlet shall be a minimum of 4 inches above the
bottom of the tank.
d) Overflow For
Water Supply Tanks. Overflow pipes for gravity tanks shall be indirectly
connected to the drainage system with an air gap of at least 6 inches. Overflow
pipes shall be full sized, unrestricted and screened with 24-mesh per inch
stainless steel or bronze screen.
e) Size of Overflow. Overflow drains for
gravity water supply tanks shall have an area of at least twice the size of the
supply pipe.
f) Drains. Water
supply tanks shall be provided with valved drain lines located at their lowest
point and shall discharge through an indirect waste with an air gap of twice
the diameter of the drain line. The drain line and valve shall have no
restrictions and need not exceed 2 inches in diameter.
g) Gravity and Suction Tanks. Tanks used for
potable water supply or only to supply fire-fighting equipment shall be
equipped with tight, overlapping covers that are rodent and insect proof. The
tanks shall be vented with a return bend (turned down) pipe having an area at
least 1/2 the area of the tank outlet pipe, and the vent opening shall be
covered with a stainless steel or bronze screen of at least 24-mesh per
inch.
h) Pressure Tanks. Pressure
tanks used for supplying water to the water distribution system, or only to
supply standpipes for fire equipment, shall be equipped with a vacuum relief
valve located on top of the tank. An air inlet of this device shall be covered
with a stainless steel or bronze screen of at least 24-mesh per inch. (See
Section 890.1230(f).)