Ill. Admin. Code tit. 77, § 890.1190 - Water Supply Control Valves and Meter
a) A full-port shut-off valve shall be
located near the curb or property line and immediately inside the building, on
the inlet and outlet side of the water meter. When located underground, this
valve shall be in a stop box or meter vault. (See Appendix I.Illustration
H.)
b) The utility meter may be
installed outside in an accessible meter vault or within the building. The
meter shall have unions on the inlet and outlet openings. A full-port valve
with an open area at least that of the water service shall be provided for all
meters and shall be provided with a drain valve installed on the discharge side
of the meter valve when located inside of a building. (See Appendix
I.Illustrations H and I.)
c) Tank
Controls. Supply lines taken from pressure or gravity tanks shall be valved at
or near their source.
d) Water
Heating Equipment. A shut-off valve shall be provided in the cold water branch
within 5 developed feet of each water storage tank or each water heater and
located in the same room.
e)
Separate Controls for Each Family Unit. In multiple family dwellings, the water
service or water distribution pipe to each family unit shall be controlled by
an arrangement of line valves that permits each group of fixtures and each
individual fixture to be shut off without interference with the water supply to
any other family unit or portion of the building. The location of these valves
shall be uniform in each family unit of a multiple family dwelling. (See
Appendix I.Illustration J.)
f)
Buildings Other Than Dwellings. In all buildings other than dwellings and
health care facilities as specified in subsection (g), line valves shall be
installed to permit the water supply to all equipment or fixtures in each
separate room to be shut off without interfering with the water supply to any
other room or portion of the building. For plumbing equipment or fixtures that
are installed back-to-back in adjacent rooms, e.g., in adjacent restrooms, a
common line valve may be used to shut off the water supply to the back-to-back
fixtures in no more than two adjacent rooms. (See Appendix I.Illustration
K.)
g) Health Care Facilities. In
the residence rooms of health care facilities, the water distribution pipe to
each resident unit shall be controlled by an arrangement of line valves that
permits each group of fixtures, and each individual fixture, to be shut off
without interference with the water supply to any other unit or portion of the
building.