Ill. Admin. Code tit. 77, § 890.1200 - Water Service Sizing
a) Water
Service Pipe Sizing. The water service pipe from the street main (including the
tap) to the water distribution system for the building shall be sized in
accordance with Appendix A, Tables M, N, O, P and Q. Water service pipe and
fittings shall be at least 3/4 inch diameter. Plastic water pipe shall be rated
at a minimum of 160 psi at 73.4 °F. If flushometers or other devices
requiring a high rate of water flow are used, the water service pipe shall be
designed and installed to provide this additional flow.
b) Demand Load. The calculation of the water
service demand load for a building shall be based on the total number and types
of fixtures installed in the building, assuming the simultaneous use of such
fixtures.
c) Unused sections of
water service or water distribution piping ("dead ends"), where the water in
the piping may become stagnant, are prohibited. A developed length of more than
2 feet shall be considered a dead end.
Notes
Amended at 28 Ill. Reg. 4215, effective February 18, 2004