Ill. Admin. Code tit. 77, § 890.1210 - Design of a Building Water Distribution System
a) Design and Installation. The design and
installation of the hot and cold water building distribution systems shall
provide a volume of water at the required rates and pressures to ensure the
safe, efficient and satisfactory operation of fixtures, fittings, appliances
and other connected devices during periods of peak use. No distribution pipe or
pipes shall be installed or permitted outside of a building or in an exterior
wall or attic unless the pipe is protected from freezing.
b) Size of Water Distribution Pipes. The
fixture supply for each fixture shall be at least the minimum size provided in
Appendix A.Table D. The size of all other water distribution pipes shall be
determined by calculating the water supply demand (in water supply fixture
units) for that portion of the water distribution system served by the pipe.
Using Appendix A.Tables M, N, O, P and Q, the cumulative water supply demand or
load shall be calculated for all fixtures, piping, valves and fittings served
by the water distribution pipe, and the pipe shall meet the minimum size
provided in Appendix A.Table N or O, as applicable. Exception: As an
alternative to using Tables M, N, O, P and Q to design and size the piping in
the water distribution system, the system may be designed and sized employing
current engineering practices, provided that the design/plans are approved in
writing by an Illinois licensed professional engineer, an Illinois licensed
architect or an individual Certified in Plumbing Design (CPD) by the American
Society of Plumbing Engineers and approved in writing by the
Department.
c) Minimum Water
Pressure. The minimum constant water service pressure on the discharge side of
the water meter shall be (at least) 20 psi, and the minimum constant water
pressure at each fixture shall be at least 8 psi or the minimum recommended by
the fixture manufacturer.
d)
Auxiliary Pressure. Supplementary Tank. If the pressure in the system is below
the minimum 8 psi at the highest water outlet when the flow in the system is at
peak demand, an automatically controlled pressure tank or gravity tank of a
capacity to supply sections of the building installation that are too high to
be supplied directly from the public water main shall be installed.
e) Low Pressure Cut-Off. When a booster pump,
except those used for fire protection, is used on an auxiliary pressure system,
a low-pressure cut-off switch shall be installed on the booster pump to prevent
the creation of pressures less than 5 psi on the suction side of the pump. A
shut-off valve shall be installed on the suction side of the water system and
within 5 feet from the pump suction inlet, and a pressure gauge shall be
installed between the shut-off valve and pump.
f) Water Hammer. All building water supply
systems shall be provided with air chambers or approved mechanical devices or
water hammer arrestors to absorb pressure surges. Water pressure absorbers
shall be installed at the ends of long pipe runs or near batteries of fixtures.
1) Air Chambers - An air chamber that is
installed in a fixture supply shall be at least 12 inches in length and the
same diameter as the fixture supply, or an air chamber with an equivalent
volume may be used. An air chamber that is installed in a riser shall be at
least 24 inches in length and at least the same size as the riser.
2) Mechanical Devices - If a mechanical
device or water hammer arrestor is used, the manufacturer's specifications for
location and installation shall be followed.
g) Excessive Static Water Pressure
1) If water main pressure exceeds 80 psi, a
pressure reducing valve and a strainer with a by-pass relief valve shall be
installed in the water service pipe near the entrance to the building to reduce
the water pressure to 80 psi or lower, except where the water service pipe
supplies water directly to a water pressure booster system, an elevated water
tank, or to pumps provided in connection with a hydropneumatic or elevated
water supply tank system. Sill cocks and outside hydrants may be left on full
water main pressure.
2) When the
water pressure exceeds 80 psi at any plumbing fixture, a pressure reducing
valve, pressure gauge and a strainer with a by-pass relief valve shall be
installed in a water supply pipe serving the fixture to reduce the water
pressure at the fixture to 80 psi or lower.
h) Approval of Auxiliary Pressure Systems.
Whenever, in any building, structure or premises receiving its potable water
supply from the public water system, a pump or any other device for increasing
the water pressure is to be installed, installation plans shall be approved by
the Department prior to installation in accordance with Section
890.1940.
i) Variable Street Pressures. If the water
main has a wide fluctuation in pressure, the water distribution system shall be
designed for minimum pressure available at the main.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.