a) All water heaters shall comply with
Appendix A.Table A (Approved Standards for Plumbing
Appliances/Appurtenances/Devices) and ASHRAE 90 Standards. Hot water storage
tanks shall meet construction requirements of ASME, AGA or UL listed in
Appendix A.Table A (Approved Standards for Plumbing
Appliances/Appurtenances/Devices), as appropriate. Hot water supply boilers
with heat input in excess of 200,000 BTU per hour, water temperature in excess
of 200 degrees Fahrenheit, or capacity in excess of 120 gallons shall also
comply with the requirements of 41 Ill. Adm. Code
120(Boiler and Pressure
Vessel Safety). Smaller water storage tanks that are not subject to ASME
requirements shall be constructed of durable materials and constructed to
withstand 150 psi. (See Appendix I.Illustrations L and M, for examples of
typical water heater installations.)
1) All
equipment used for heating and storage of hot water shall bear the marking of
an approved testing agency certifying that it has been tested and approved and
listed as meeting the requirements of the applicable standard. Listing by UL,
the Canadian Standards Association (CSA), or National Board of Boiler and
Pressure Vessel Inspectors, or the ASME Standard shall constitute evidence of
conformance with these standards.
2) Solar Hot Water Heat Exchangers
A) A hot water heat exchanger used in a
solar-heated system may be of single wall construction if a non-toxic transfer
fluid with no conditioning chemicals in the system is used.
B) A hot water exchanger used in a
solar-heated system using a toxic transfer fluid or having conditioning
chemicals in the system shall be separated from the potable water by double
wall construction that has an air gap vented to the atmosphere between the
walls.
3) A hot water
heat exchanger may be of single wall construction if a non-toxic transfer fluid
with no conditioning chemicals in the system is used.
4) A hot water heat exchanger operating at or
below 65 psi using a toxic transfer fluid or having conditioning chemicals in
the system shall be separated from the potable water by double wall
construction, with an air gap open to the atmosphere between the two
walls.
5) A hot water heat
exchanger shall not be permitted on any hot water boiler system operating in
excess of 65 psi or 250 degrees Fahrenheit, unless:
A) the heat exchanger is
double-walled;
B) the heat
exchanger has an air gap open to the atmosphere between the two walls;
and
C) the heat exchanger has a
pressure gradient monitor system with a "fail-safe to off" switch installed to
isolate the heat exchanger from the potable cold or hot water system. If
pressure on the potable water side reaches a pressure less than 20 psi above
the pressure of the transfer fluid or steam and a pressure-reducing valve is
installed on the inlet to the heat exchanger with a setting 20 psi lower than
the potable water pressure at the heat exchanger, an audible alarm shall be
activated and the heat exchanger shall be automatically shut off until the
alarm and heat exchanger can be reset manually.
6) Any boiler using toxic chemicals shall
have a label with a minimum size of 5 inches by 5 inches attached to the boiler
in a conspicuous place. The label shall read as follows:
WARNING
Chemicals and additives used to treat the boiler feed water
in this boiler are not approved for potable water. The steam or hot water
produced by this boiler is not potable. If the steam or hot water produced by
this boiler is used to heat water, the water will not be considered potable if
the steam and potable water are mixed.
7) Indirect, External, Submerged Coils.
Indirect, external, tankless or submerged coils used in heating water shall be
equipped with a thermostatic mixing valve or valves when not connected to a
storage tank. A pressure relief valve shall be installed on the cold water
inlet of the tank. A properly sized temperature and pressure relief valve,
based upon the energy input rating of the coils, shall be installed on the
tempered line with the temperature sensing element immersed in the tempered
water line as close as possible to the mixing valve.
8) Water Heaters Used for Space Heating. Any
water heater to be used for space heating, in addition to hot water supply,
shall conform to ANSI Z21.10.1, Z21.10.1a and Z21.10.1b and shall be
constructed for continuous use, and the piping for space heating shall be
conducted to a proper terminal heating device.
A) A thermostatic mixing valve, conforming to
ASSE 1017, shall be installed on the hot water line to the plumbing fixtures.
(The mixing valve shall be set to prevent temperatures exceeding 120 degrees
Fahrenheit from reaching the plumbing fixtures.)
B) A single check valve shall be installed in
the cold water line supplying the water heater. This will prevent hot water
backing up from the heating unit to the plumbing fixtures.
C) A properly sized and approved expansion
tank shall be located on the outlet side of the check valve in the water
heater's cold water supply, with no shut-off valve between the heater and
expansion tank.
D) Valves (manual,
automatic) supplying hot water to the heat transfer unit for space heating
shall have a minimum of a 1/8-inch orifice. This will prohibit potable water
from standing in the heat transfer unit when not in use. This does not prohibit
full shut off/isolation valves on either side of the pump within a heat
transfer unit, as needed, to permit the servicing of the pump.
E) The water heater instructions shall have a
statement specifying that piping and components connected to the water heater
for the space heating application shall be suitable for use with potable water,
and the water heater shall not exceed a developed length of more than 25 feet
from the heating coil.
F) A
statement specifying that toxic chemicals, such as those used for boiler
treatment, shall not be introduced into the potable water used for space
heating shall be included in the instructions. A label with the following words
shall be firmly attached to any water heater used for space heating: "DO NOT
INJECT TOXIC MATERIALS INTO THIS TANK."
G) A statement specifying that a water heater
that will be used to supply potable water shall not be connected to any heating
system or components previously used with a non-potable water heating appliance
shall be included in the installation instructions.
H) Each water heater shall bear a statement
on the rating plate as follows: "SUITABLE FOR POTABLE WATER HEATING AND SPACE
HEATING."
9)
Point-of-Use Water Heaters. Point-of-use water heaters shall meet the following
requirements:
A) Non-storage and
non-pressurized units intended to deliver water temperatures exceeding 110
degrees Fahrenheit, or with no mechanical or electrical temperature limiting
device, shall have the faucet located at least 3 inches from the 110 degrees
Fahrenheit hot water or cold water faucet. Faucet outlets shall have labels
clearly and conspicuously indicating extremely hot water. These units are
exempt from the requirement that a relief valve or valves be used to protect
against excessive or unsafe temperature or pressure.
B) Units intended to deliver water
temperatures 110 degrees Fahrenheit or less shall have an internal burnout
element. These units are exempt from the requirement that a relief valve or
valves to be used to protect against excessive or unsafe temperature and/or
pressure.
C) All pressurized
point-of-use water heaters, other than those in subsection (a)(9)(A) or (B),
shall be provided with proper temperature and pressure relief.
10) Steam Heat. All water heaters,
including storage heaters, instantaneous shell and tube heat exchangers, steam
injection heaters and any other device using steam to heat water for potable
use, shall meet the following requirements:
A) All chemicals and additives used to treat
the boiler feed water in a boiler supplying steam to heat potable water shall
be approved for use with potable water. If approved chemicals and additives are
used with steam boilers generating at 15 psi or less, or are used with pressure
reducing stations with pressure relief valves set at 15 psi or less downstream
from the pressure reducing valves, single wall heat exchangers may be
used.
B) All steam heat exchangers
operating in excess of 15 psi but less than 50 psi shall be separated by double
wall construction, with an air gap open to the atmosphere between the two
walls.
C) All steam heat exchangers
operating in excess of 50 psi shall meet the following requirements:
i) The heat exchanger shall be
double-walled;
ii) The heat
exchanger shall have an air gap open to the atmosphere between the 2 walls;
and
iii) The heat exchanger shall
have a pressure gradient monitoring system with a "fail-safe to off" switch
installed to isolate the heat exchanger from the potable cold or hot water
system. If the pressure on the potable water side reaches a pressure less than
20 psi above the pressure of the transfer fluid or steam and a pressure
reducing valve is installed on the inlet to the heat exchanger with a setting
20 psi lower than the potable water pressure at the heat exchanger, an audible
alarm shall be activated and the heat exchanger shall automatically shut off
until the conditions resulting in an alarm are corrected and the heat exchanger
pressure gradient monitoring system can be manually reset.
D) The steam pressure to all the steam heat
injectors shall be 15 psi lower than the water pressure at the ejector. Steam
injection heaters shall be supplied with steam from a generator or boiler that
uses only United States Food and Drug Administration (FDA) approved additives
or chemicals.
E) The following
warning label with a minimum size of 5 inches by 5 inches shall be permanently
attached on the front of any boiler providing steam to direct-injection steam
hot water heaters:
"If the chemicals used to treat the boiler feed water in this
boiler are not approved for potable water, the steam produced by this boiler
cannot be considered potable. Therefore, if steam from this boiler is used to
heat water, the water shall not be considered potable and any cross-connections
between the hot water produced and a potable water supply must be provided with
a device to prevent the backflow of the non-potable hot water into the potable
water supply."