Ill. Admin. Code tit. 77, § 890.1230 - Safety Devices
a) All
equipment used for heating water or storing hot water shall be provided, at the
time of installation of the equipment, with the required relief valve or valves
to protect against excessive or unsafe temperature and pressure. This shall be
achieved by installing either a pressure relief valve and a temperature relief
valve or by installing a combination pressure-temperature relief
valve.
b) Pressure and Temperature
Relief Valves
1) Pressure Relief Valves.
Pressure relief valves shall have an ASME relief rating to meet the pressure
conditions specified on the equipment served. They shall be installed in the
cold water supply line to the heating equipment served, except where scale
formation from hard water may be encountered, in which case they shall be
installed in the hot water supply line from the heating equipment served. There
shall not be a shut-off valve between the pressure relief valve and the tank.
Except when an alternate design is approved by the Department in writing
pursuant to Section 890.140(a)(2)
or 890.1940, the pressure relief
valve shall be set to open at a maximum of the working pressure rating of the
water heater, but shall not exceed 150 psi. Each pressure relief valve shall
have a test lever.
2) Temperature
Relief Valves. Temperature relief valves shall bear the Canadian Standard
Association (CSA) relief rating, expressed in British Thermal Units (BTU) of
heat input per hour, for the equipment served. They shall be installed so that
the temperature-sensing element is immersed in the hottest water within the top
6 inches of the tank. The valve shall be set to open full when the stored water
temperature is 210 degrees Fahrenheit.
c) Combination Pressure-Temperature Relief
Valves
1) Combination pressure-temperature
relief valves shall comply with the applicable requirements listed in Appendix
A.Table A (Approved Standards for Plumbing Appliances/Appurtenances/Devices)
for individual pressure and individual temperature relief valves, shall be
installed so that the temperature sensing element is immersed in the hottest
water within the top 6 inches of the tank, and shall have a test
lever.
2) A check valve or shut-off
valve shall not be installed between any safety device and the hot water
equipment, nor shall there be any shut-off valve in the discharge pipe from the
relief valve. (See Appendix I.Illustrations N and O.)
3) Energy cut-off devices shall not be used
in lieu of subsections (c)(1) and (2) and shall be of a design to properly
serve the intended use of the plumbing appliance, appurtenance or device.
Exception: Instantaneous cut-off devices are exempted or may be used.
d) Relief Discharge Outlet
1) A relief discharge outlet shall be
installed and be indirectly connected to waste. The discharge pipe from the
relief valve shall not be located so as to create a safety hazard or to
discharge so as to cause damage to the building or its contents. The relief
valve shall not discharge through a wall into the outside atmosphere or where
there is a possibility of freezing.
2) No reduced coupling, valve or any other
restriction that would impede the flow of discharge shall be installed in the
discharge line of any relief valve. The discharge line shall be installed from
the relief valve to within 6 inches of the floor or receptor and the end of the
line shall not be threaded.
3) Any
piping used for discharge from the relief valve shall be of metallic material,
shall comply with Appendix A. Table A (Approved Materials for Water
Distribution Pipe) for potable water piping, and shall drain continuously
downward to the outlet.
4) The
discharge piping shall discharge indirectly into a floor drain, hub drain,
service sink, sump or a trapped and vented P-trap that is located in the same
room as the water heater. (See Sections
890.1010 and
890.1050(a), (b) and
(c).) The trap shall have a deep seal to
protect against evaporation or shall be fed by means of a priming device
designed and installed for that purpose. The use of a light grade oil in the
trap will retard evaporation.
e) Pressure Marking - Hot Water Storage Tank.
Hot water storage tanks shall be permanently marked in an accessible place with
the maximum allowable working pressure.
f) Vacuum Relief Valve. If a hot water
storage tank or water heater is located at an elevation above the fixture
outlets in the hot water system, or if the storage tank or water heater is
bottom fed, a vacuum relief valve as listed in Appendix A.Table A (Approved
Standards for Plumbing Appliances/Appurtenances/Devices) shall be installed on
the storage tank or heater.
g)
Multiple Temperature Hot Water Systems. These systems shall be provided with
thermostatic mixing valves to control the desired temperatures.