Ill. Admin. Code tit. 77, § 930.20 - Treatment Plant
A non-community water system, semi-private water system, or a private water system which obtains water from a surface source, shall treat water by utilizing a water treatment plant with either slow sand filtration or cartridge filtration, and disinfection.
a) General
1) Raw Water Quality. The turbidity of the
source water shall not exceed 50 nephelometric turbidity units. Cartridge
filtration shall not be used to treat water obtained from rivers.
2) Intake. A means must be provided to
withdraw raw water from the surface source. Intakes shall not incorporate a
submerged sand and gravel filter. The intake must be located at a point of
deepest water in the pond and must be capable of being raised or lowered for
cleaning. A coarse meshed screen with openings not greater than 1/4 inch shall
be placed over the end of the intake pipe to prevent entrance of fish, dead
leaves, and other debris. The intake pipe must be constructed such that it is
flexible, will not break when raised, and shall be approved for use as potable
water piping in accordance with the Illinois Plumbing Code (77 Ill. Adm. Code
890, Section 890.Appendix A Plumbing Materials, Equipment, Use Restrictions and
Applicable Standards) or Table A Approved Materials for Water Service Pipe of
this Part. The intake pipe must be kept below any ice, it must be buried in a
trench through shallow water, and it must be placed below the frost line at all
points.
b) Slow Sand
Filtration. The treatment plant shall include the following principal units.
1) Raw Water Pump. A pump shall be required
to deliver water from the intake to the filter at a rate which is greater than
the filtration rate. The pump must be self-priming or so installed that it will
not lose its prime.
A) The pump shall be
driven by an electric motor, controlled by a sensing system on top of the
filter, and set to start and stop the raw water pump automatically. The system
shall be set to allow 10 inch-12 inch fluctuation in the water level in the
filter to prevent frequent cycling of the pump.
B) The raw water pump will not be required
when the elevation of the filter is below the elevation of the intake pipe.
Elevation difference between the pond and the filter must be sufficient to
produce the flow rate needed at times of low pond water levels in accordance
with the rates set forth in Section
930.30 of this Part. There must
be no possibility of flooding the treatment plant by high water which may occur
below the pond.
2)
Filter Sand. The filter must be designed so that the raw water flows downward
by gravity through the filter media.
A)
Filter Sand. The filter media shall be a layer of sand at least three feet in
depth. The sand shall have an effective size of .25-.35 mm with an ideal size
of .30 mm and a uniformity coefficient of 1.4 -1.8 with an ideal uniformity
coefficient of 1.6. The sand shall be supported by a bed of gravel one foot in
depth. A perforated pipe must be installed at the bottom of the filter which
will allow water to flow to a water storage tank.
B) Filtration Rate. The maximum permissible
filtration rate shall be 2 gallons per minute for each 25 square feet of sand
surface area. The amount of water needed per day shall be calculated using
Table B.
C) Construction. The
filter must be constructed of concrete or a material which will not corrode or
deteriorate and the walls and bottom shall be watertight. Examples of materials
which will corrode or deteriorate include wood, tin, or steel. The minimum
height of the filter shall be 8 feet in order to provide for a 3 foot depth of
water above the sand, and a minimum of 1 foot from water level to the top of
the filter during operation.
D)
Underdrain Pipe. A perforated underdrain pipe, 11/4 inches inside diameter or
larger, shall be installed horizontally at 2 inches above the bottom of the
filter tank. One end of the pipe shall be capped within the filter to prevent
the entrance of gravel. The other end shall pass through the filter wall, and a
valve shall be installed to regulate the flow of water leaving the filter. See
Illustration A. Forty -50 holes in the underdrain pipe shall be drilled in 2
rows at a 90o angle to each other on the bottom side
of the pipe. The holes shall be 1/4 inch in diameter and shall be uniformly
spaced. One separate underdrain pipe shall be installed for each 75 square feet
of filter area.
E) Gravel. Clean,
washed gravel shall be placed in three graded layers in the filter, the
coarsest gravel being on the bottom. The bottom layer shall be placed to a
depth of 6 inches, and shall consist of stones 1/2-3/4 inches in diameter. The
top of the pipe shall be 2 inches below the top of this layer. The second or
middle layer shall be 3 inches in depth and shall consist of stones 1/4-1/2
inches in diameter. The third or top layer shall be 3 inches in depth and
consist of stones 1/8-1/4 inches in diameter.
F) Filter Valves. The piping which carries
the water from the filter is to be valved as shown in Illustration B. The
filter to waste pipe shall discharge at least 6 inches above the floor drain to
permit checking the clarity of the filtered water and to measure the flow rate
of filtered water. The floor drain shall not be located over the filtered water
storage tank nor shall any portion of the waste drain piping pass through any
part of the water storage tank. The filtered water shall be stored in the
storage tank and a float valve shall be installed at the end of the filtered
water pipe within the storage tank to shut off the flow when the tank is filled
to approximately 6 inches from the top. (See Illustration A for exact
location.) Solenoid valves controlled by a float switch may also be used. A
manhole shall be installed in the top of the storage tank. The manhole shall
have a raised curb and be provided with a cover of the overhanging type. The
float valve is to be located to one side of the manhole so that it may be
reached for any adjustment, without entering the storage tank. The floor drain
which receives filtered water and discharges to waste shall discharge at ground
level, at least 15 feet horizontally and downgrade from the plant and above any
floodwater level. This drain shall not be connected to any other drain or
sewer.
G) Filtered Water Storage
Tank. A watertight and pollution-proof reservoir must be provided to receive
the filtered water. Its capacity shall be at least equal to the amount of water
which will be used in one day. This amount is obtained by using Table B. The
top of the storage tank shall not be higher than the bottom of the filter, and
shall not be located where it can be subject to flooding. Sources of pollution
shall not be located closer to buried water storage tanks than indicated in
Section 920.50 of the Illinois Water
Well Construction Code (77 Ill. Adm. Code
920.50).
H) Filtered Water Pump and Pressure Tank. An
electrically driven pump shall be provided to remove water from the storage
tank. The water distribution system shall be designed to maintain a minimum
positive pressure of 20 pounds per square inch (p.s.i.) in all parts of the
system at all times. Water pipe shall conform to applicable specifications and
standards of the Illinois Plumbing Code (77 Ill. Adm. Code 890, Section
890.1150) for the type of pipe
to be used.
I) Filter Building. A
building or structure shall be provided to enclose the filter and pumps. If the
system is to be operated through the winter months, heating must be provided to
prevent freezing.
c) Cartridge Filtration. The treatment plant
shall include the following principal units.
1) Raw Water Pump. The pump shall be driven
by an electric motor and be controlled by a pressure switch set to turn on the
pump at a pressure of no less than 20 pounds per square inch. The pump shall be
protected against excessive cycling by the installation of a hydropneumatic
tank. The volume of water that can be drawn from the hydropneumatic tank
between pump cycles shall be at least equal to the volume of water pumped in 30
seconds. The hydropneumatic tank shall be installed upstream of the filters and
disinfection system.
2) Particulate
Reduction Filter. Particulate reduction shall be accomplished using a filter
certified to comply with ANSI/NSF Standard 42 - Drinking Water Treatment units
- Aesthetic Effects, for particulate reduction, class I or II and be listed as
such by an approved certification agency. The design flow rate in the
particular application in which the filter is utilized shall not exceed the
rated service flow rate for which the filter was certified. An official
certification label from the certifying agency shall be permanently affixed to
the filter. When treating turbid waters, an additional filter may be needed
prior to the particulate reduction filter.
3) Turbidity Reduction and Cyst Reduction.
Turbidity reduction and cyst reduction shall be accomplished utilizing either
separate filters for each process or one filter for both processes. The
turbidity and cyst reduction filters shall be located downstream of the
particulate reduction filter.
A) Turbidity
Reduction Filter. Turbidity reduction shall be accomplished using a filter
certified to comply with ANSI/NSF Standard 53 - Drinking Water Treatment units
- Health Effects, for turbidity reduction and be listed as such by an approved
certification agency. The design flow rate in the particular application in
which the filter is utilized shall not exceed the rated service flow rate for
which the filter was certified. An official certification label from the
certifying agency shall be permanently affixed to the filter.
B) Cyst Reduction Filter. Cyst reduction
shall be accomplished using a filter certified to comply with ANSI/NSF Standard
53 - Drinking Water Treatment units - Health Effects, for cyst reduction and be
listed as such by an approved certification agency. The design flow rate in the
particular application in which the filter is utilized shall not exceed the
rated service flow rate for which the filter was certified. An official
certification label from the certifying agency shall be permanently affixed to
the filter.
4) Flow
Control. A flow control valve and a flow rate meter shall be installed
downstream of the filters. The flow rate meter shall have a range which will
permit the measurement of the rated service flow rate for the filters, and
shall have an accuracy of ± 10% over the full scale.
d) Disinfection.
1) A disinfection system shall be installed
with calcium or sodium hypochlorites or gas chlorine or other disinfecting
agents approved by the Department. Proposals for the use of disinfecting agents
other than those specifically listed in this Section must be approved by the
Department prior to preparation of final plans and specifications. The
Department will grant approval when all available information establishes that
the chemical to be used as a disinfecting agent meets the following conditions:
the residual levels created by the use of the chemical will not jeopardize the
health of the user of the water, testing procedures for residual elements are
recognized in "Standard Methods for the Examination of Water and Wastewater"
(1995 Edition - American Public Health Association) (see Section
930.15) and the chemical will
destroy bacteria in the water supply. Ultraviolet disinfection may only be used
in water treatment plants utilizing cartridge filtration.
2) Chlorination. Disinfection using chlorine
shall include feeding equipment, a retention tank and testing equipment.
A) Chlorination Equipment. The chlorinator
shall be designed to provide a free chlorine residual of at least two
milligrams per liter (mg/l) in the water. The equipment shall be designed so
that it will operate accurately over the desired feeding range. Where flow is
uniform, actuation of a constant volume feeder by the pump circuit is required.
Where flow is variable, automatic flow proportioning is required.
i) Hypochlorinator. Positive displacement
pumps shall be provided to inject hypochlorite solution. The pump shall be of
variable flow type and shall be of sufficient capacity to feed the required
amount of disinfectant. If calcium hypochlorite is used, the concentration of
calcium hypochlorite in the solution shall not exceed 5 percent. The solution
container shall have a minimum capacity equal to the volume of solution
required per day. The chlorine pump shall be controlled by a float switch
located in the filtered water storage tank. Chlorine shall be pumped whenever
water is flowing into the storage tank.
ii) Gas Chlorinators. Any gas chlorination
system shall meet the requirements of Section
900.40(n)(5) of
the Drinking Water Systems Code (77 Ill. Adm. Code
900.40(n)(5)).
B) Contact Time and Point of
Application. Chlorine shall be applied after the filter and prior to the
filtered water storage tank, and in a manner that will provide a free chlorine
residual of at least 2 milligrams per liter in the water after thorough mixing
and a contact time of at least 30 minutes at maximum flow rates. The pipe
carrying water from the filter shall terminate at or above the water surface of
the storage tank. Water shall be withdrawn from a solid pipe at a point not
more than 3 inches above the bottom of the water storage tank.
C) Testing Equipment. Chlorine residual test
equipment capable of measuring free chlorine residual shall be provided and
shall be capable of measuring residuals to the nearest 0.1 mg/L in the range
below 0.5 mg/L, to the nearest 0.3 mg/L between 0.5 and 1.0 mg/L, and to the
nearest 0.5 mg/L between 1.0 mg/L and 2.0 mg/L.
3) Ultraviolet Disinfection. Where
ultraviolet disinfection is used, it shall be accomplished using an ultraviolet
disinfection system certified to comply with ANSI/NSF Standard 55 - Ultraviolet
Microbiological Water Treatment Systems - Class A Systems. The design flow rate
for the ultraviolet disinfection equipment shall be at least equal to the rated
service flow rate for any of the filters. The ultraviolet disinfection
equipment shall be installed downstream of the filters.