Ill. Admin. Code tit. 77, § 930.40 - Treatment Plant Maintenance
a) Slow
sand filtration treatment plants shall be maintained as follows:
1) Cleaning. Whenever the design flow can no
longer be achieved the filter must be cleaned. In order to clean the filter,
the water level must be lowered to 2 to 3 inches below the top of the sand. The
filter must not be drained. The accumulated mud and slime along with 1/2 inch
of the top of the sand surface must be removed.
2) Proper Filter Depth. After 6 inches of
sand has been removed due to repeated cleaning, additional sand which shall
comply with the design criteria specified in Section
930.20(c) must
be added so the filter is restored to the original depth of 3 feet.
b) Cartridge filtration treatment
plants shall be maintained as follows:
1)
Cartridge filters shall be cleaned or replaced according to the manufacturer's
recommendation.
2) Replacement
cartridges shall be equal to the original equipment.
c) Ultraviolet disinfection equipment shall
be maintained as follows:
1) The ultraviolet
equipment lamp shall be cleaned or replaced when the equipment has a lamp
intensity failure. The lamp shall be replaced when the equipment has a lamp
failure.
2) The ultraviolet lamp
shall be replaced at intervals specified by the manufacturer, but no less often
than annually.
3) Replacement
ultraviolet equipment lamps shall be equal to the original equipment.
Notes
Amended at 27 Ill. Reg. 15998, effective October 1, 2003
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.