675 IAC 15-2-28 - Alarm sounding devices

Authority: IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15

Sec. 28.

(a) Every smoke-detecting device shall cause the operation of an alarm signaling device or devices which shall be clearly audible in all bedrooms with all intervening doors closed.
(b) All alarm sounding devices shall be rated not less than eighty-five (85) decibels at ten feet (10').

Notes

675 IAC 15-2-28
Fire Prevention and Building Safety Commission; 675 IAC 15-2-28; filed Mar 25, 1986, 1:44 pm: 9 IR 1987, eff Jun 15, 1986; readopted filed Nov 29, 2001, 12:21 p.m.: 25 IR 1306; readopted filed Sep 21, 2007, 9:20 a.m.: 20071010-IR-675070388RFA; readopted filed Oct 10, 2007, 9:16 a.m: 20071031-IR-675070388RFA; readopted filed Aug 4, 2011, 8:35 a.m.: 20110831-IR-675110254RFA Readopted filed 3/10/2017, 9:37 a.m.: 20170405-IR-675170005RFA Readopted filed 5/11/2023, 2:22 p.m.: 20230607-IR-675230104RFA