RELATES TO: KRS 224.01, 224.10, 224.40, 224.43, 224.99
NECESSITY, FUNCTION, AND CONFORMITY: KRS Chapter 224 requires
the cabinet to adopt rules and administrative regulations for the managing,
processing, or disposal of solid wastes.
KRS
224.40-305 requires that persons engaging in
the managing, processing, or disposal of waste obtain a permit. This chapter
establishes the minimum technical standards for solid waste sites or
facilities. This administrative regulation sets forth the liner and cap design
requirements for contained landfills.
Section
1. Liners for Contained Landfills. At a minimum all contained
landfills shall have:
(1) A primary composite
liner as specified in Sections 2 and 7 of this administrative regulation;
and
(2) A secondary composite
liner
that:
(a) Meets the secondary liner criteria
specified in Sections 2 and 7 of this administrative regulation; or
(b) Is a naturally occurring material
provided that such natural material:
1. Shall
be equivalent to material with a minimum thickness of twenty (20) feet with a
maximum permeability of 1 x 10-7 centimeters per
second;
2. Shall lie above the
uppermost aquifer; and
3. Shall
continuously underlie the landfill site or facility and be demonstrated to have
sufficient integrity to protect the uppermost aquifer from contamination in the
event of a breech of the primary composite liner.
Section 2. Components of
Contained Landfill Liner Systems. Once the subgrade is established, the primary
and secondary
liner systems shall consist of the layers, listed in subsections
(1) through (3) of this section.
(1) The
secondary
liner system shall consist of the following layers, listed from
bottom to top:
(a) A twelve (12) inch soil
layer with a permeability of 1 x 10-7 centimeters
per second as specified in Section 4 of this administrative
regulation;
(b) A secondary
synthetic liner as specified in Section 5 of this administrative
regulation;
(c) A twelve (12) inch
drainage layer with a permeability of 1 x 10-3
centimeters per second; and
(d) A
filter fabric or other material approved by the cabinet.
(2) The secondary liner layer specified in
subsection (1)(a) and (b) of this section may be substituted for by a naturally
occurring material as specified in Section 1(2) of this administrative
regulation.
(3) The primary
liner
shall consist of the following layers, listed from bottom to top:
(a) A thirty-six (36) inch clay layer with a
permeability of 1 x 10-7 centimeters per second as
specified in Sections 4, 6 and 7 of this administrative regulation;
(b) A primary synthetic liner as specified in
Section 5 of this administrative regulation;
(c) A twelve (12) inch drainage layer with
permeability of 1 x 10-2 centimeters per second or a
layer of equivalent performance as specified in Section 6 of this
administrative regulation; and
(d)
A filter fabric or other material approved by the cabinet to protect the
integrity of the drainage layer.
Section 3. Specific
Landfill Subgrade
Requirement. The
landfill subgrade is the uppermost in situ rock layer, in situ
soil layer or select fill that shall be graded and prepared for
landfill
construction. For lateral expansions adjacent to existing landfills, the
cabinet may approve encroachment upon the existing
landfill's side slope if a
leachate barrier system is designed and construction to intercept
leachate and
prevent its migration into the existing
landfill.
(1) Materials required. The landfill subgrade
material shall be free of organic material and consist of bedrock, on-site
soils, or any select fill with the structural ability to support the landfill
maximum load with a factor of safety of two (2.0).
(2) Construction requirements. The landfill
subgrade shall be graded in accordance with the requirements of the approved
engineering plans, report, and specifications. The material shall be
sufficiently dry and structurally sound to ensure that the first lift and all
succeeding lifts of soil placed over the landfill subgrade can be adequately
compacted to the design requirements.
(3) Certification requirements. At a minimum,
the subgrade surface shall be inspected in accordance with the following
requirements:
(a) Before placing any material
over the subgrade, the project engineer shall visually inspect the exposed
surface to evaluate the suitability of the subgrade and ensure that the surface
is properly compacted, smooth, uniform, and has positive surface
drainage;
(b) Soil subgrade shall
be proof-rolled using a minimum 100,000 pound loaded four (4) tire scraper
(twenty (20) cubic yard size) or equivalent procedure and equipment approved by
the cabinet;
(c) Soil subgrade
shall be tested for density and moisture content at a minimum frequency of nine
(9) tests per acre. The subgrade shall be compacted to a density of at least
ninety (90) percent of the standard proctor; and
(d) Sufficient cross sections shall be taken
showing the finished elevation of the completed sub-grade, referenced to
existing site control. These cross sections shall serve as documentation and
reference data for all future volume calculations.
Section 4. Specific Soil Component
Requirements of
Landfill Liner Systems. The soil component of the
landfill
liner system shall be a continuous layer of low permeability soil constructed
to control fluid migration.
(1) Low
permeability soil components shall have a maximum remolded coefficient of
permeability of 1 x 10-7 centimeters per second. The
soil shall be placed without damaging any collection and removal system
components. The soil material shall be substantially free of tree roots, wood
or other decayable materials and large rock. The soils shall be compacted to a
minimum of ninety-two (92) percent of the standard proctor density.
(2) Construction requirements. The project
engineer shall ensure that the soil component of the
liner system installation
conforms to the following minimum requirements:
(a) The soil component of the liner system
shall be placed on a slope of no less than three (3) percent toward the main
leachate collection line and one (1) percent along the main leachate collection
line to promote positive drainage across the liner surface and at a maximum
slope not greater than fifty (50) percent.
(b) Compaction shall be performed by properly
controlling the moisture content, lift thickness, and other necessary details
to obtain the density, moisture and permeability characteristics specified in
401 KAR Chapter 48. The maximum final compacted thickness of each lift of soil
material shall be six (6) inches or the thickness necessary to protect the
integrity of underlying components and achieve the required liner performance
standards.
(c) During construction
the moisture content of the soil component of the liner system shall be
maintained within the range identified in accordance with the certification
requirements to ensure that the remolded lift attains the required
permeability.
(3)
Certification requirements. The project
engineer shall include in the
construction
certification report a discussion of all required quality
assurance and quality control testing. The testing procedures and protocols
shall be submitted and approved by the cabinet. The results of all testing
shall be included in the construction
certification report including
documentation of any failed test results, descriptions of the procedures used
to correct the improperly installed material, and statements of all retesting
performed in accordance with the following requirements:
(a) The project
engineer shall certify the
results of the quality control testing of any soil
liner materials. The intent
of the quality control testing is to ensure that the specified material meets
the permeability requirements of subsection (1) of this section. Before and
during construction of the soil component of the
liner system, the following
minimum testing and classification shall be performed:
1. Determination of the classification of
soils for engineering purposes using test methods approved by the cabinet for
each 10,000 cubic yards of soil material placed and each time significant soil
material changes are noted:
2. One
(1) analysis of soil particle size for every 2,000 cubic yards of soil liner
material placed from the same source. Additional analyses shall be performed if
the source of material is changed or if a different soil type is encountered
from the same source.
3. One (1)
Atterberg limits analysis of plastic and liquid limit and plasticity index as
approved by the cabinet for every 2,000 cubic yards of soil liner material
placed;
4. One (1) moisture content
test for every 2,000 cubic yards of material placed; and
5. A minimum of one (1) comparison of the
moisture-density-permeability relation for every 20,000 cubic yards of material
placed and one (1) each time soil material changes are noted. A minimum of
three (3) laboratory permeability tests shall be performed using a triaxial
cell with backpressure. The specimen used for each permeability test shall be
remolded at the same moisture content which shall be equal to or not greater
than four (4) percent above the optimum moisture content. The comparison shall
be based on a semilog plot of percent maximum density versus permeability with
at least one (1) point below and one (1) point above the target permeability
value.
(b) Quality
assurance testing included in this paragraph shall be compared to and evaluated
against the quality control testing of paragraph (a) of this subsection where
applicable. Quality assurance testing shall include:
1. At least nine (9) density tests per acre
per lift of soil material placed;
2. A minimum of nine (9) moisture content
tests per acre per lift of soil material placed; and
3. All moisture-density testing performed
using nuclear methods.
Section 5. Specific Synthetic
Liner
Requirements. A synthetic
liner is a low permeability manmade material having a
maximum coefficient of permeability of 1 x 10
-12
centimeters per second and is used to control fluid migration from landfills.
(1) Materials required. The synthetic liner
material shall have a demonstrated hydraulic conductivity less than 1 x
10-12 centimeters per second and chemical and
physical resistance not adversely affected by waste placement or leachate
generated and a maximum water vapor transmission rate of 0.04 grams per square
meter per day for forty (40) mil nominal thickness material and 0.03 grams per
square meter per day for sixty (60) mil nominal thickness material.
Documentation shall be submitted to ensure chemical compatibility of the
synthetic liner material chosen or, in absence of the appropriate
documentation, chemical compatibility testing shall be performed using a test
method acceptable to the cabinet.
(2) Construction requirements. Synthetic
liners shall be installed in accordance with the requirements of the approved
engineering plans, report, and specifications and manufacturer's
recommendations. The project
engineer shall ensure that the synthetic
liner
installation, at a minimum, shall conform with the following:
(a) The synthetic liner shall have a nominal
thickness of sixty (60) mils;
(b)
The synthetic liner shall be installed on a subgrade that has a minimum three
(3) percent slope to promote positive drainage;
(c) Synthetic liners installed on slopes
greater than twenty-five (25) percent shall be designed to withstand the
calculated tensile forces acting upon the synthetic material, and shall ensure
that overall slope stability is maintained;
(d) The surface of the supporting soil above
which the synthetic liner shall be installed shall be reasonably free of
stones, organic matter, irregularities, protrusions, loose soil, and any abrupt
changes in grade that may damage the synthetic liner. The supporting soil shall
conform to the requirements of Section 4 of this administrative
regulation;
(e) The anchor trench
shall be excavated to the length and width prescribed on the approved design
drawings;
(f) Field seams shall be
oriented parallel to the line of maximum slope, i.e., oriented along, not
across the slope. In corners and irregularly-shaped locations, the number of
field seams shall be minimized;
(g)
The materials shall be seamed using an appropriate method acceptable to the
cabinet. Seam testing shall be in accordance with the requirements of
subsection (3) of this section;
(h)
The seam area shall be free of moisture, dust, dirt, debris, and foreign
material of any kind before seaming; and
(i) Field seaming shall be prohibited when
the conditions including ambient air, temperature, precipitation, and wind do
not meet the engineers recommendations based upon the suppliers
specifications.
(3)
Certification requirements. The project
engineer shall include in the
construction
certification report a discussion of the approved data resulting
from the quality assurance and quality control testing required in this
paragraph. The results of all testing shall be included in the construction
certification report including documentation of any failed test results,
descriptions of the procedures used to correct the failed material, and
statements of all retesting performed.
(a) The
project
engineer shall certify the quality control testing of the synthetic
liner ensuring that the material and workmanship meet the requirements of the
approved engineering plans, reports, and specifications. Before installing a
synthetic
liner, the following information shall be available to the project
engineer for approval:
1. Origin and
identification of the raw materials used to manufacture the synthetic
liner;
2. Copies of quality control
certificates issued by the producer of the raw materials used to manufacture
the synthetic liner; and
3. Reports
of tests conducted to verify the quality of the raw materials used to
manufacture the synthetic liner. Tests for specific gravity, melt flow index,
and percent carbon black shall be performed using a method acceptable to the
cabinet.
(b) The project
engineer shall verify through appropriate documentation that the quality
control testing of any synthetic rolls fabricated into blankets at the factory
took place in accordance with the following requirements:
1. The synthetic liner was continuously
inspected for uniformity, damage, imperfections, holes, cracks, thin spots, and
foreign materials. Additionally, the synthetic liner shall be inspected for
tears, punctures, and blisters. Any imperfections shall be immediately repaired
and reinspected;
2. Nondestructive
seam testing was performed on all fabricated seams over their full length using
a test method acceptable to the cabinet; and
3. A destructive seam testing was performed
on a minimum of two (2) samples per blanket. The samples shall be taken from
extra material at the beginning or end of blanket seams such that the blanket
is not damaged and the blanket geometry is not altered. The size of the sample
taken shall be large enough to perform the required testing. An independent
laboratory acceptable to the cabinet shall perform the required testing on the
samples taken. If a sample fails a destructive test, the entire seam length
shall be reconstructed or repaired using a method acceptable to the cabinet and
retested using nondestructive seam testing over its full length using a test
method acceptable to the cabinet.
(c) Quality assurance testing performed in
the field under the supervision of the project
engineer shall assure conformity
of the synthetic
liner installation with the engineering plans, reports, and
specifications submitted in accordance with the following requirements:
1. During the construction phase, the
synthetic liner shall be inspected for uniformity, damage, and imperfections.
The liner shall be inspected for tears, punctures, or blisters. Any
imperfections shall be immediately repaired and reinspected;
2. All field seams shall be nondestructively
tested in accordance with the procedures listed in this clause using a test
method acceptable to the cabinet. The project engineer shall supervise all
nondestructive testing; record the location, date, test unit number, name of
tester, and results of all testing; inform the installer of any required
repairs; and overlay all seams which cannot be nondestruc-tively tested with
the same synthetic liner. The seaming and patching operation shall be inspected
by the project engineer for uniformity and completeness; and
3. Destructive testing shall be performed on
the synthetic liner seam sections in accordance with the following requirements
and using test methods acceptable to the cabinet. Seam samples for testing
shall be taken as follows: a minimum of one (1) test per every 500 feet of seam
length unless a more frequent testing protocol is agreed upon by the installer
and project engineer; additional test locations may be determined during
seaming at the project engineer's discretion; and all test locations shall be
appropriately documented. The project engineer shall approve the sample size to
be taken. The sample size shall be predetermined as being large enough to
perform the required testing. An independent laboratory acceptable to the
cabinet shall perform the required testing which shall include, as a minimum,
testing for seam strength and peel adhesion using testing procedures acceptable
to the cabinet. If a sample fails destructive testing the project engineer
shall ensure that the seam is reconstructed between the location of the sample
which failed and the location of the next acceptable sample; or the welding
path is retraced to an intermediate location at least ten (10) feet from the
location of the sample which failed the test, and a second sample is taken for
an additional field test. If this second test sample passes, the seam shall
then be reconstructed between the location of the second test and the original
sampled location. If the second sample fails, this process shall be repeated.
All acceptable seams shall lie between two (2) locations where samples passed
the required test procedures of this section and include one (1) test location
along the reconstructed seam.
Section 6. Primary
Liner System. The
liner
shall be designed using the following specifications:
(1) A thirty-six (36) inch thick low
permeability soil layer having a remolded coefficient of permeability of 1 x
10-7 centimeters per second and compacted to a
minimum of ninety-two (92) percent standard proctor density;
(2) A sixty (60) mil thick synthetic liner
having a maximum coefficient of permeability of 1 x
10-12centimeters per second and not adversely
affected by the leachate or loading from the operational landfill;
(3) A leachate collection and removal system
consisting of a twelve (12) inch thick granular material layer with a leachate
collection pipe network. This collection system shall be designed to achieve a
maximum hydraulic head on the primary composite liner no greater than twelve
(12) inches. The granular material shall have a minimum coefficient of
permeability of 1 x 10-2 centimeters per second. The
physical and chemical properties of the granular material and pipe shall not be
adversely affected by the loads or leachate generated by the operations of the
landfill. Alternate materials proposed to function as a substitute for the
granular soil layer shall be demonstrated to be equivalent in performance for
leachate drainage and load bearing properties; and
(4) The
leachate collection system shall
contain a perforated piping system capable of removing
leachate from the top
surface of the low permeability solid component, and conveying it to a
collection point. The drainage system shall meet the following requirements:
(a) Main leachate collection pipes shall have
a minimum diameter of eight (8) inches and shall be designed to withstand
static and dynamic loads that may be encountered;
(b) The sheet flow drainage distances to the
lateral drainage pipes shall not exceed fifty (50) feet;
(c) The lateral pipes shall be installed
primarily perpendicular to flow;
(d) The minimum diameter of lateral
perforated pipes shall be four (4) inches and shall be designed to withstand
static and dynamic loads that may be encountered. The materials used shall at a
minimum conform to the specifications for ASTM schedule eighty (80)
pipe;
(e) The minimum slope for the
piping system shall be one (1) percent;
(f) The leachate collection tank shall be a
minimum of 1,000 gallons. Additional capacity shall be provided to store
leachate for a minimum of fifteen (15) days production at peak production rates
during operation and closure;
(g)
The method of leachate disposal shall be described. When it is discharged to
the sediment structure, a treatment plant is proposed or other method of
discharge is proposed, the KPDES permit shall reflect this provision. When an
off-site wastewater treatment plant is used, the applicant shall provide
written documentation showing the acceptance of the waste. The criteria for
disposal at the wastewater treatment plant shall be stated. The leachate
collection system shall have a method to measure the quantity of leachate
managed at the site;
(h) The
leachate collection pipe system shall be designed to allow internal inspection,
cleaning and maintenance; and
(i)
The maximum design head of the leachate collection system shall be one (1)
foot.
(5) A geosynthetic
filter fabric or other suitable material shall be placed above the drainage
layer to prevent clogging.
Section
7. Slope Considerations.
(1) For
bottom slopes of less than or equal to ten (10) percent, the owner or operator
shall have a liner system meeting the requirements of Section 1 of this
administrative regulation.
(2) For
bottom slopes of ten (10) to twenty-five (25) percent, the owner or operator
shall have a liner system meeting the requirements of Section 2(3) of this
administrative regulation, except that the owner or operator may replace the
granular soil layers in the leachate collection and hydraulic relief systems
with synthetic drainage netting.
(3) For bottom slopes of more than
twenty-five (25) percent, the thickness of the soil required in Sections
2(3)(a) and (6)(1) of this administrative regulation shall be reduced by no
more than twelve (12) inches.
Section
8. Final Cap System. At a minimum the final cap shall consist of a
layered system. Each layer shall have the same slope of between five (5) and
twenty-five (25) percent. The components, listed from bottom to top, are:
(1) A filter fabric or other material
approved by the cabinet;
(2) A
twelve (12) inch sand gas venting system with a minimum hydraulic permeability
of 1 x 10-3;
(3) A filter fabric or other material
approved by the cabinet;
(4) An
eighteen (18) inch clay layer with a maximum permeability of 1 x
10-7 centimeters per second;
(5) For areas of the final cap with a slope
of less than fifteen (15) percent, a twelve (12) inch drainage layer with a
minimum permeability of 1 x 10-3 centimeters per
second; and
(6) A thirty-six (36)
inch vegetative soil layer.
Section
9. Final Cap System Specifications. The specifications for final
cap component layers are:
(1) A low
permeability clay layer listed in Section 8(4) of this administrative
regulation shall be compacted to a minimum of ninety-two (92) percent of the
standard proctor density;
(2) A
drainage layer specified in Section 8(5) of this administrative regulation
shall be compacted to a minimum of eighty-five (85) percent of the standard
proctor density. Field tile drainage shall be specified as necessary to relieve
water captured by this drainage layer;
(3) A vegetative soil layer as specified in
Section 8(6) of this administrative regulation shall be sufficient to sustain
vegetative growth and prevent root penetration of the underlying layers. A
thicker layer may be required by the cabinet to properly retain moisture or
meet closure care requirements.
(4)
Drainage berms of at least one (1) foot in height or two (2) feet in width
shall be placed at the following intervals for the following slopes:
(a) 150 feet at greater than ten (10) percent
slope;
(b) 200 feet at slope
between five (5) and ten (10) percent. In lieu of drainage berms, the owner or
operator may substitute a design with a horizontal terrace of at least fifteen
(15) feet width on the slope for every twenty-five (25) feet maximum rise in
elevations on the slope. The slope of the terrace shall be five (5) percent
into the fill and drainage ditches shall be designed for each terrace to convey
precipitation flows. The maximum slope between terraces shall not exceed
twenty-five (25) percent; or
(c)
The applicant shall may adjust the drainage berm specifications with design
calculations based upon characteristics of soils and cover.
(5) A synthetic liner with a
minimum thickness of forty (40) mils and a maximum coefficient of permeability
of 1 x 10-12 centimeters per second may be
substituted for the low-permeability soil cover in Section 8(4) of this
section.
(6)
(a) The final cover shall be
revegetated.
(b) The soil-water pH
shall be adjusted and the soil fertilized based upon current soil test
results.
(c) The seed bed shall be
prepared and temporary nurse crops and permanent grasses planted in accordance
with the approved closure plan within thirty (30) days of completion of final
cover grading.
(d) The owner or
operator shall repeat the above as necessary to achieve permanent
vegetation.
(e) Erosion controls
shall be addressed in the closure plan and constructed as required. All slopes
over three (3) percent shall have controls applied at the time of
seeding.
(f) The
owner or
operator
shall inspect all areas and perform maintenance and revegetation. At a minimum,
the
site shall be initially inspected according to this table:
Seeding Date
|
Follow-up Inspection Date
|
Complete Revegetation By
|
Aug. 16-Oct. 15
|
April 1
|
June 15
|
Oct. 16-Mar. 15
|
June 1
|
June 30
|
Mar. 16-Jun. 15
|
September 1
|
October 15
|
Jun. 16-Aug. 15
|
October 1
|
October 30
|
After the initial inspection, follow-up inspections shall be
made on April 1, and September 1, with revegetation completed by June 15 and
October 15.
(g) After one
(1) year, all areas larger than 100 square feet with less than forty (40)
percent vegetation shall be tested to determine required revegetation, which
shall be completed by September 30.
Section 10. Structural Integrity of Cap and
Liner. The design engineer shall analyze the structural integrity of the site,
the subbase, each component of the composite liner, each component of the final
cover, the composite liner system and the final cap as a system. Modifications
to the design shall be provided where necessary, to achieve a minimum factor of
safety of two (2) for the subbase, one and one-fourth (1.25) for the structural
design of the facility liner components, and one and one-half (1.5) for the
final cover system. Synthetic liner material and structural synthetic materials
shall be designed for a maximum elongation of ten (10) percent.
Section 11. Alternative Specifications.
Alternative specifications may be used only after approval by the cabinet upon
a demonstration by a qualified registered professional engineer that they shall
result in performance with regard to safety, stability and environmental
protection equal to or better than that resulting from designs complying with
the specifications of this administrative regulation.