La. Admin. Code tit. 33, § XV-1747 - Pool Water Purity

Current through Register Vol. 48, No. 3, March 20, 2022

A. Pool water purification systems shall be run sufficiently to maintain the conductivity of the pool water below 20 microsiemens per centimeter under normal circumstances. If pool water conductivity rises above 20 microsiemens per centimeter, the licensee shall take prompt actions to lower the pool water conductivity and shall take corrective actions to prevent future recurrences.
B. The licensee shall measure the pool water conductivity frequently, but no less than weekly, to assure that the conductivity remains below 20 microsiemens per centimeter. Conductivity meters shall be calibrated at least annually.

Notes

La. Admin. Code tit. 33, § XV-1747
Promulgated by the Department of Environmental Quality, Office of Air Quality and Radiation Protection, Radiation Protection Division, LR 24:2120 (November 1998).
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:2001 et seq.