02-658 C.M.R. ch. 10, § 3 - Use of Existing Chimneys
10.3.1 Except as
provided in Section 10.3.1.1, the required 2" minimum clearance to combustible
material for existing interior chimneys and the required 1" minimum clearance
to combustible material for existing exterior chimneys is not required when
replacing oil- or gas-fired appliances.
10.3.1.1 The 2" clearance to combustible
material for existing interior chimneys and the 1" minimum clearance to
combustible material for existing exterior chimneys are required when a solid
fuel appliance or a wood stove is connected to the chimney flue.
10.3.2 When installing
any gas, oil or solid fuel appliance, the chimney must be lined with a clay
tile liner or listed lining system compatible with the intended fuel
source.