02-658 C.M.R. ch. 110, § 16 - LOW WATER CONTROL FOR SOLID FUEL FIRED BOILERS
Current through 2022-14, April 6, 2022
Low water protection shall be accomplished in one of two ways:
1. If the opening of an electric
circuit will arrest the combustion process, a low water cut-off will be
satisfactory if it conforms to the following:
A. All solid fuel fired boilers shall be
provided with a properly installed and operating low water cut-off.The low
water cut-off may be installed in, or attached to, the boiler at the level
recommended by the boiler manufacturer, but in no case shall the low water
cut-off be installed below the crown sheet. The low water cut-off, when not
installed directly in the boiler, may be installed either in the main supply
line (vertical riser) as close to the boiler as possible or in a water column
of continuous piping attached directly to the boiler.
B. The low water cut-off shall be designed
and approved for the media in which it is used, either steam or
water.
C. No valves or other
obstructive devices may be installed between the boiler and any safety controls
or devices; or
2. If the
opening of an electric circuit will not arrest the combustion process, low
water protection shall be accomplished in accordance with the appliance
manufacturer's instructions.