16-219 C.M.R. ch. 27, § 02 - Structural Requirements
A. All supporting
members shall be of sufficient size and strength to support the
structure.
B. Tents shall be
adequately guyed, supported and braced to withstand a wind pressure or suction
of ten (10) pounds per square foot. The poles and their supporting guys, stays,
stakes, fastenings, etc., shall be of sufficient strength and attached so as to
resist wind pressure of twenty (20) pounds per square foot of projected area of
the tent.
C. Grandstands shall be
designed to support, in addition to their own weight, a uniformly distributed
live load of not less than one hundred (100) pounds per square foot of gross
horizontal projection of the grandstand. All seats and foot-board members shall
be designed for live loads of not less than one hundred twenty (120) pounds per
linear foot.
D. Grandstands shall
be designed to resist, without live load, a horizontal wind load of thirty (30)
pounds per square foot of all vertical projections of the stand, and with full
live load, one-half of such wind load.
E. Grandstands shall be designed to resist a
horizontal swaying force applied to the seats in a direction parallel to the
length of the seats, of twenty-four (24) pounds per linear foot of seats, and
in a direction perpendicular to the length of the seats of ten (10) pounds per
linear foot of seats.
F. Portable
grandstands shall be provided with base plates, sills, floor runners, or
sleepers, of such area that the total live and dead load shall not exceed
fifty-five (55) pounds per square inch on base plates, sills, floor runners, or
sleepers. When portable grandstands rest directly on earth of such character as
to be incapable of supporting the load without appreciable settlement, mud
sills of suitable material, having sufficient area to prevent undue or
dangerous settlement, shall be installed under base plates, runners, or
sleepers. All bearing surfaces shall be in contact.
G. A-frames, or other supports, and seat
stringers for portable grandstands shall be secured to prevent accidental
displacement during occupancy.
H.
Field connections to wood members shall be by means of rivets, bolts, approved
connectors, friction or other devices, or lag screws, except that lag screws
shall not be permitted for direct tension. The use of nails and wood screws is
permissible for holding wood parts together, except that these shall not be
used for demountable joinings, nor shall these be used where their loosening or
splitting of surrounding wood would jeopardize the structure or its occupants.
Wood members in tension shall be connected at each end by means of not less
than two bolts, rivets, or lag screws, or by approved connectors, or approved
devices. Adequate provision shall be made to prevent the splitting or shearing
of wood at such connections.