Md. Code Regs. 20.50.09.02 - Definitions
A. In this chapter,
the following terms have the meanings indicated.
B. Terms Defined.
(1) "Adverse system impact" means a negative
effect, due to technical or operational limits on conductors or equipment being
exceeded, that may compromise the safety or reliability of the electric
distribution system.
(2) "Affected
system" means a utility electric system that is affected by the interconnection
of a small generator facility to another utility's electric distribution
system.
(3) 'Aggregate generation"
means the aggregated net system capacities of all small generator facilities
across multiple points of common coupling.
(4) "Applicant" means a person who has
submitted an interconnection request to interconnect a small generator facility
to a utility's electric distribution system.
(5) "Area network" means a type of electric
distribution system served by multiple transformers interconnected in an
electrical network circuit, often used in large, densely populated metropolitan
areas.
(6) "Certificate of
completion" means a certificate provided by a utility to an applicant
containing information about the interconnection equipment used, its
installation, and local inspections.
(7) "Closed circuit" means an electric
distribution system circuit with no available hosting capacity.
(8) "Commissioning test" means one of several
tests applied to a small generator facility by the applicant after construction
is completed to verify that the small generator facility does not create
adverse system impacts, including the test specified in Section 5.4 of IEEE
Standard 1547.
(9) "Default utility
required inverter settings profile" means a utility set of default smart
inverter settings optimized for use across a utility's service
territory.
(10) "Distributed energy
resource" means any geographically dispersed energy resource located on an
electric distribution system that produces electricity or offsets electrical
demand including small generator facilities, energy storage devices, energy
efficiency devices, and demand response devices.
(11) "Distribution upgrade" means a required
addition or modification to the utility electric distribution system, excluding
the interconnection facilities, necessary to accommodate the interconnection of
a small generator facility.
(12)
"Draw-out type circuit breaker" means a molded case switching device that:
(a) Can be inserted into or removed from its
enclosure during no-load conditions; and
(b) Is capable of making, carrying, and
breaking currents under normal and abnormal circuit conditions.
(13) Electric Distribution System.
(a) "Electric distribution system" means the
facilities and equipment used to transmit electricity generally at less than 69
kV to ultimate usage points such as homes and industries from interchanges with
higher voltage transmission networks that transport bulk power over longer
distances.
(b) "Electric
distribution system" has the same meaning as the term Area EPS as defined in
Section 3.1.6.1C of IEEE Standard 1547.
(14) "Energy Storage Device" means apiece of
equipment that captures energy produced at one time, stores that energy for a
period of time, and delivers that energy as electricity at a future time.
(15) "Fault current" means the
electrical current that flows through a circuit during an electrical fault
condition, such as when one or more electrical conductors contact ground or
each other.
(16) "Grid support
services" means compensated or uncompensated services unrelated to wholesale
markets provided by a small generator facility that support the safety,
stability, reliability, or economics of the electric grid.
(17) "Hosting capacity" means the amount of
aggregate generation that can be accommodated on an electric distribution
system or area, or a system component, without requiring infrastructure
upgrades.
(18) "Hosting capacity
reporting system" means the information available on a utility website
providing reports, tabular data, or maps of hosting capacity available on the
electric distribution system.
(19)
"Hosting capacity upgrade plan" means a utility plan to promote clean energy
interconnection for a particular area or a proposal to open multiple restricted
and closed circuits or areas on an electric system in the aggregate through
proactive distribution system investments that includes a cost allocation and
recovery proposal, under conditions that are approved by the
Commission.
(20) "IEEE Standard
1547" means the standard incorporated by reference in COMAR
20.50.02.02C.
(21) "IEEE Standard 1547.1" means the
standard incorporated by reference in COMAR
20.50.02.02C.
(22) "Inadvertent export" means the
unscheduled export of power from a small generator facility, beyond a specified
magnitude and for a limited duration, generally due to fluctuations in
load-following behavior.
(23)
"Interconnection agreement" means an agreement that contains details regarding
the proposed interconnection equipment and its operation to ensure the
reliability and safety of the grid, including schedules, rights, obligations,
and terms and conditions that become effective on the date the agreement is
executed by the utility and the interconnection customer.
(24) "Interconnection customer" means an entity that
proposes to interconnect or has interconnected a small generator facility to an
electric distribution system.
(25)
Interconnection Equipment.
(a)
"Interconnection equipment" means a group of components or an integrated system
connecting an electric generator with a local electric power system, or an
electric distribution system.
(b)
"Interconnection equipment" means all interface equipment including switchgear,
protective devices, inverters, or other interface devices.
(c) "Interconnection equipment" includes
equipment installed as part of an integrated equipment package that includes a
generator or other electric source.
(26) Interconnection Facilities.
(a) "Interconnection facilities" means
facilities and equipment required by the utility to accommodate the
interconnection of a small generator facility.
(b) "Interconnection facilities" includes all
facilities and equipment between the small generator facility and the point of
interconnection, and modifications, additions, or upgrades that are necessary
to physically and electrically interconnect the small generator facility to the
electric distribution system.
(c)
"Interconnection facilities" includes any distribution upgrade.
(27) "Interconnection facility
cost sharing" means the allocation of distribution interconnection facility
upgrade costs among multiple small generator facility projects that utilize the
hosting capacity created by an interconnection facility upgrade.
(28) "Interconnection request" means an
applicant's request for the interconnection of a small generator facility, or
to increase the capacity or operating characteristics of a small generator
facility that is already interconnected with the utility's electric
distribution system.
(29)
"Interconnection study" means an interconnection feasibility study,
interconnection system impact study, or interconnection facilities study as
described in Regulation .12 of this chapter.
(30) "Limited export agreement" means an
agreement for energy supplied to the grid by an interconnection customer that
may be managed to specified ramp rates and generation levels for operating
conditions, as specified in the interconnection agreement or in a separate
limited export agreement.
(31)
"Line section" means that portion of a utility electric distribution system
connected to an interconnection customer, bounded by automatic sectionalizing
devices, or the end of the distribution line.
(32) Local Electric Power System.
(a) "Local electric power system" means those
facilities that deliver electric power to a load that are contained entirely
within a single premises or group of premises.
(b) "Local electric power system" has the
same meaning as the term local electric power system as defined in Section
3.1.6.2C of IEEE Standard 1547.
(33) "Meter collar adapter" means an
electronic device that is installed between a residential electric meter and
the meter socket, for the purpose of facilitating the deployment of
customer-owned or customer-leased technology.
(34) "Minor equipment modification" means a
change to the proposed small generator facility that does not have a
significant impact on safety or reliability of the electric distribution
system.
(35) "Minor system
modification" means a change to the distribution system:
(a) Located between the service tap on the
distribution circuit and the meter serving the applicant; or
(b) That the utility estimates will entail
less than 4 hours of work and less than $1,500 in materials.
(36) "Nameplate capacity" means
the maximum rated output of a generator, electric power production equipment or
energy storage under specific conditions designated by the manufacturer is
usually listed on a nameplate physically attached to the equipment.
(37) "Nationally recognized testing
laboratory (NRTL)" means a qualified private organization recognized by the
Occupational Safety and Health Administration to perform independent safety
testing and product certification.
(38) "Net system capacity" means the total
export capacity at a point of common coupling of a small generator facility as
measured by the nameplate capacities of all power production units and energy
storage devices minus their consumption of electrical power, if applicable, as
limited through the use of a control system, power relays, or other similar
device settings or adjustments.
(39) "Parallel operation" means the sustained
state of operation over 100 milliseconds which occurs when a small generator
facility is connected electrically to the electric distribution system, and
thus has the ability for electricity to flow from the small generator facility
to the electric distribution system.
(40) "Permission to operate notice" means the
written permission provided by a utility in the form of an email or letter
authorizing an interconnection customer to interconnect and operate its small
generator interconnection facility.
(41) "Point of common coupling" means the point of
interconnection where the small generator facility is electrically connected to
the electric distribution system.
(42) "Point of interconnection " has the same
meaning as the term "point of common coupling".
(43) "Primary line" means a distribution line
rated at greater than 600 volts.
(44) "Primary voltage hosting capacity
upgrade cost" means the equipment upgrade costs of all interconnection
equipment, interconnection facilities, protective devices and associated
communications systems, and other upgrades that directly increase hosting
capacity for multiple primary voltage and secondary voltage interconnection
customers while excluding equipment upgrade costs that solely benefit a single
interconnection customer, to the extent practicable and material.
(45) "Primary voltage interconnection
customer" means an interconnection customer with a point of interconnection at
greater than 600 nominal volts.
(46) Proposed Use.
(a) "Proposed use" means the operational
control modes of a small generator facility upon which the applicant's
technical review is based and under which the small generator facility is bound
to operate upon the execution of the interconnection agreement.
(b) "Proposed use" for a small generator
facility includes a combination of electric generators and energy storage
devices operating in specified operational control modes during specified time
periods.
(47) "Queue
position" means the order of a completed interconnection request, relative to
all other pending completed interconnection requests, that is established based
upon the date and time of receipt of the completed interconnection request by
the utility.
(48) "Radial
distribution circuit" means a circuit configuration in which independent
feeders branch out radially from a common source of supply.
(49) "Reserve hosting capacity" means the
amount of hosting capacity reserved for small generator facilities on an
electric distribution system circuit.
(50) "Restricted circuit" means an electric
system distribution circuit with reserve hosting capacity.
(51) "Rightsizing" means to increase the
size, scope, and cost of an electric utility hosting capacity upgrade project,
following a distributed energy resource interconnection request, to account for
both the immediate interconnection customer's needs and future hosting capacity
needs that are identified by the electric utility through a distributed energy
resource forecast.
(52) "Scoping
meeting" means a meeting between the applicant and utility conducted for the
purpose of discussing alternative interconnection options, exchanging
information, including any electric distribution system data and earlier study
evaluations that would be reasonably expected to impact interconnection
options, analyzing information, and determining the potential feasible points
of interconnection.
(53) "Secondary
line" means a service line subsequent to the primary line that is rated for 600
volts or less, also referred to as the customer's service line.
(54) "Secondary voltage hosting capacity
upgrade cost" means the costs of all primary voltage and secondary voltage
interconnection equipment upgrades that directly increase secondary voltage
hosting capacity available to multiple secondary voltage interconnection
customers while excluding all primary voltage and secondary voltage
interconnection equipment upgrade costs that solely benefit a single
interconnection customer, to the extent practicable and material.
(55) "Secondary voltage interconnection
customer" means an interconnection customer with a point of interconnection at
less than or equal to 600 nominal volts.
(56) "Shared transformer" means a transformer
that supplies secondary source voltage to more than one customer.
(57) "Site-specific utility required inverter
settings profile" means a set of smart inverter settings optimized for use at a
specific site on a utility's electric system.
(58) Small Generator Facility.
(a) "Small generator facility" means the
equipment used to generate or store electricity that operates in parallel with
the electric distribution system.
(b) "Small generator facility" includes an
electric generator, a prime mover, energy storage device, and the
interconnection equipment required to safely interconnect with the electric
distribution system or local electric power system.
(59) "Smart Inverter" means any inverter
hardware system certified to be compliant with IEEE 1547-2018 or subsequent
revisions to these standards.
(60)
Spot Network.
(a) "Spot network" means a type
of electric distribution system that uses two or more inter-tied transformers
to supply an electrical network circuit.
(b) "Spot network" is generally used to
supply power to a single customer or a small group of customers.
(c) "Spot network" has the same meaning as
the term is defined in 4.1.4 of IEEE Standard 1547.
(61) "Statewide utility required inverter
settings profile" or "grid code" means a set of smart inverter settings
optimized for use Statewide that can be used by utilities and manufacturers in
establishing defaults.
(62)
"Utility monitoring and control plan" means a plan to monitor and control, in
the aggregate, a set of small generator facilities in multiple locations that
includes a cost recovery method, under conditions that are approved by the
Commission.
(63) "Utility required
inverter settings profile" means smart inverter settings for a small generator
facility that are established by a utility.
(64) "Witness test" means, for lab-certified
or field-approved equipment, verification either by an on-site observation or
review of documents by the utility that the interconnection installation
evaluation required by Section 5.3 of IEEE Standard 1547 and the commissioning
test required by Section 5.4 of IEEE Standard 1547 have been adequately
performed.
Notes
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.