Md. Code Regs. 20.50.09.07 - Certified and Approved Equipment
A. After January 1,
2024, any small generator facility inverter for which an interconnection
request is submitted shall be deemed certified and approved if it meets the
requirements of IEEE Standard 1547-2018 and UL Standard 1741-SB, except for
inverters purchased pursuant to Regulation .06N(2) of this chapter.
B. After January 1, 2024, any small generator
facility shall be deemed approved if the interconnection equipment including
interface components such as switchgear, multifunction relays, or other
interface devices are compatible with the interconnection equipment, pursuant
to witness test requirements pursuant to Regulation .06L of this
chapter.
C. An electric utility
shall approve a meter collar adapter model for installation in its Maryland
service area for specific compatible meter configurations and customer
applications, provided that the meter collar adapter model meets the following
criteria:
(1) The meter collar adapter model
is approved or listed by a nationally recognized testing laboratory;
(2) The meter collar adapter model is
approved for use in utility service areas, unless sufficient rational for
disapproval is provided by an electric utility;
(3) All meter collar model installations,
access, testing, inspections, servicing, and removals shall only be performed
by a qualified person as agreed between the utility and the meter collar
manufacturer;
(4) The meter collar
adapter model design does not impede access to the sealed meter socket
compartment, or to the meter itself by a qualified person;
(5) The meter collar adapter model is
compatible with the National Electric Code; and
(6) The meter collar adapter model is
compatible to the specific meter configurations and customer applications to
ensure that the meter collar adapter is capable of being safely and reliably
inserted into a meter socket to maintain a secure connection with both the
meter socket and the utility meter.
D. An electric utility shall approve or
disapprove a meter collar adapter model for installation in its service area no
later than 90 days after a meter collar manufacturer submits a request for
approval of the meter collar adapter, and a utility's procedures shall be
updated within 90 days of utility approval.
E. An electric utility shall provide an
explanation to the requesting meter collar manufacturer explaining the reasons
any meter collar adapter model application was denied.
F. A requesting meter collar adapter
manufacturer may appeal the utility decision to the Commission using the
dispute resolution process in Regulation .13 of this chapter.
G. An electric utility shall provide public
notice of all decisions approving a meter collar adapter model by posting the
information on the utility's website.
H. An electric utility shall authorize the
installation and operation of a utility-approved meter collar adapter for a
customer installation, provided the meter collar adapter meets the following
criteria:
(1) The meter collar adapter is
qualified to be connected to the supply side of the service disconnect,
pursuant to the applicable provisions of the National Electric Code;
(2) The meter collar adapter is rated for the
meter socket into which it is intended to be installed;
(3) The meter collar adapter does not exceed
the weight bearing limits of a meter socket;
(4) Multiple meter collar adapters are not
stacked in a meter socket; and
(5)
The meter collar adapter does not disable this excessive heating detection
capability of AMI meters.
I. A utility shall uninstall an approved
meter collar adapter in the aggregate if any deficiencies are found after
installation that result in safety or operational concerns, if these concerns
cannot be remediated by a customer for a specific installation or by a meter
collar adapter manufacturer, in the aggregate.
J. The determination of violations in this
regulation and the assessment of related civil penalties and corrective action
plans shall be delegated to the Engineering Division.