Md. Code Regs. 26.11.38.03 - 2015 NO[x] Emission Control Requirements
A. Daily NOx Reduction
Requirements During the Ozone Season.
(1) Not
later than 45 days after the effective date of this regulation, the owner or
operator of an affected electric generating unit (the unit) shall submit a plan
to the Department and EPA for approval that demonstrates how each affected
electric generating unit will operate installed pollution control technology
and combustion controls to meet the requirements of §A(2) of this regulation.
The plan shall summarize the data that will be collected to demonstrate
compliance with §A(2) of this regulation. The plan shall cover all modes of
operation, including but not limited to normal operations, start-up, shut-down,
and low load operations.
(2)
Beginning on May 1, 2015, for each operating day during the ozone season, the
owner or operator of an affected electric generating unit shall minimize
NOx emissions by operating and optimizing the use of all
installed pollution control technology and combustion controls consistent with
the technological limitations, manufacturers' specifications, good engineering
and maintenance practices, and good air pollution control practices for
minimizing emissions (as defined in
40 CFR §
60.11(d)) for such equipment
and the unit at all times the unit is in operation while burning any
coal.
B. Ozone Season
NOx Reduction Requirements.
(1) Except as provided in §B(3) of this
regulation, the owner or operator of an affected electric generating unit shall
not exceed a NOx 30-day systemwide rolling average
emission rate of 0.15 lbs/MMBtu during the ozone season.
(2) The owner or operator of an affected
electric generating unit subject to the provisions of this regulation shall
continue to meet the ozone season NOx reduction
requirements in COMAR 26.11.27.
(3)
Ownership of Single Electric Generating Facility.
(a) An affected electric generating unit is
not subject to §B(1) of this regulation if the unit is located at an electric
generating facility that is the only facility in Maryland directly or
indirectly owned, operated, or controlled by the owner, operator, or controller
of the facility.
(b) For the
purposes of this subsection, the owner includes parent companies, affiliates,
and subsidiaries of the owner.
C. Annual NOx
Reduction Requirements. The owner or operator of an affected electric
generating unit subject to the provisions of this regulation shall continue to
meet the annual NOx reduction requirements in COMAR
26.11.27.
D.
NOx Emission Requirements for Affected Electric
Generating Units Equipped with Fluidized Bed Combustors.
(1) The owner or operator of an affected
electric generating unit equipped with a fluidized bed combustor is not subject
to the requirements of §§A, B(1) and (2), and C of this regulation.
(2) The owner or operator of an affected
electric generating unit equipped with a fluidized bed combustor shall not
exceed a NOx 24-hour block average emission rate of 0.10
lbs/MMBtu.