105 CMR, § 675.011 - Required Evacuation
(A) If air levels
of carbon monoxide or nitrogen dioxide exceed the evacuation air levels of
105 CMR
675.008(C), the operator
shall:
(1) immediately evacuate all people
from the interior of the indoor skating rink;
(2) contact the local fire department as soon
as possible to assist in the evacuation of the facility and to assess the
hazard;
(3) contact the local board
of health upon completion of the evacuation;
(4) contact the Bureau within two hours of
the evacuation.
(B)
Re-occupancy of the indoor skating rink after evacuation under 105 CMR 675.011
can only occur if:
(1) three consecutive air
samples taken by the operator within no greater than a three hour period and
taken in accordance with the air sampling procedures set forth in
105 CMR 675.006(A)(2)
and (4) indicate that the air levels of
carbon monoxide or nitrogen dioxide have been reduced below the correction air
levels;
(2) appropriate long-term
corrective measures have been taken to prevent further future exceedances of
the correction air levels; and
(3)
the air levels of carbon monoxide and nitrogen dioxide are found to be below
the correction air levels through one or more independent measurements taken by
the local fire department, local health department or the Bureau.