(1)
General Rules.
(a) All products, systems, and equipment used
in the construction, installation, alteration, repair, replacement, or removal
of any plumbing or drainage system or part thereof, shall conform to the
material requirements in
248
CMR
10.06. For purposes of
248
CMR
10.06, all products, systems, and
equipment must meet the requirements for acceptance under
248
CMR
3.04:
Product, Design, and
Testing Standards, including, but not limited to, meeting the
requirements of generally accepted standards acceptable to the Board.
(b) Notwithstanding
248
CMR
10.06(1), the Inspector
may allow the extension, addition to, or relocation of existing water, soil,
waste and/or vent pipes with materials of like grade or quality in renovations
or in renovations or alterations where the original installation met all code
requirements then in effect.
(c)
The Board may accept products pursuant to
248
CMR
3.04(1) which do not
adhere to the requirements of
248
CMR
10.06(1) when the Board
has explicitly found that the material used in the product(s) are substantially
equivalent to materials normally acceptable by
248
CMR
10.06 and otherwise, would not be
detrimental to public health, safety, or welfare.
(d)
Alternate Materials, Methods,
and Systems. The provisions of
248
CMR
10.06 are not intended to prevent the use
of materials, methods or systems that are not specifically authorized or
prescribed by
248
CMR
10.06, provided such alternate materials,
methods and systems meet the standards, use and intent of
248
CMR
10.06 and the Board has granted
Product-Acceptance, a Variance, or a Test-site status pursuant to
248 CMR
3.00:
General Provisions Governing the Conduct
of Plumbing and Gas Fitting Work Performed in the
Commonwealth.
(e) All
pipe, valves and fittings used in a potable water system anticipated to be used
for human consumption shall comply with the Federal Safe Water Drinking Act
(SWDA) 42 USC Section
300 f.
(f) Notwithstanding the provisions of
248 CMR
10.00, all applicable products must meet the energy
efficiency standards outlined in M.G.L. c. 25B, §§ 5 through 10 and
225 CMR
9.00:
Appliance Energy-efficiency Standards,
Testing and Certification Program. To the extent these requirements
are mandated by law, no variance or other relief can be granted by the Board to
allow use of a non-compliant product.
(2)
Allowable
Materials.
(a)
Sheet
Copper. Sheet copper shall not be less than 12 ounces per square
foot when used in the following applications:
1. safe pan;
2. shower pan;
3. flush tank linings:
4. vent terminal flashing; or
5. general use.
(b)
Floor Flanges: A
floor flange used for a toilet or other similar fixture shall be product
accepted and made of copper, brass, cast iron, hubless cast iron or
plastic.
(c)
Storm
& Sanitary Above & Below Ground. Materials listed in
248
CMR
10.06:
Table
1.
(d)
Vent
Pipe & Fittings Above & Below Ground. Materials listed in
248
CMR
10.06:
Table 1.
10.06: Table 1
Storm and Sanitary Waste and Vent Piping
Click to
view image
Note: Always follow manufacturers installation
instructions wherever more stringent than 248 CMR.
A = Allowed: X = Not Allowed
* May be used only for storm water drainage For a list if
allowable materials for Special Waste, see
248
CMR 10.13(2)(a) and
(b).
(e)
Water Distribution Piping
Above and Below Ground. Materials listed in
248
CMR
10.06:
Table 2.
10.06 Table 2
Water Distribution Piping
Click to
view image
Note: Follow manufacturers installation
instructions wherever more stringent than 248 CMR. A = Allowed: X = Not
Allowed
(f)
CPVC
Pipe and PEX Tubing and Fittings. CPVC and PEX may be used for hot
and cold-water piping which is:
1. located in
residential dwellings, hotels, motels, inns, condominiums, and similar
buildings not exceeding six stories; or
2. located in a predominantly residential
building where there is a single, non-residential use on single floor and
meeting the following requirements:
a. the
non-residential use would be categorized exclusively as employee
(non-residential) per
248
CMR
10.10 (15):
Table 1 with no additional uses and,
b. the non-residential use shall be limited
to a maximum of four plumbing fixtures; and
c. the types of plumbing fixtures shall be
limited to toilets, sinks (lavatory, residential, and service sinks) and
drinking water stations.
3. used exclusively for dedicated cold-water
piping beginning at the outlet of the water meter or main control valve inside
any building directly to drinking water stations.
4. PEX tubing, and fittings may be used in
commercial buildings for the purpose of conveying reverse osmosis or other
similar processes that produce Purified Water from the point of treatment to
one or more points of use for drinking water.
Exception:
a. CPVC pipe and/or PEX domestic water tubing
and fittings shall not be installed within 24 inches of the final connection to
any domestic water heater.
b. CPVC
pipe and/or PEX tubing, and fittings shall not be used for steam flushing of
water purification systems. Only type 316 stainless steel tube and fittings
shall be used for this purpose.
(g)
PVC and ABS DWV Pipe and
Fittings.
1. PVC and ABS schedule
40 pipe and fittings may be used for drains, waste, or vents in residential
dwellings, hotels, motels, inns, condominiums and in residential areas of
assisted living facilities not exceeding ten stories; or
2. located in a predominantly residential
building where there is a single, non-residential use on a single floor and
meeting the following requirements:
a. the
non-residential use would be categorized exclusively as employee
(non-residential) per
248
CMR
10.10(15):
Table
1 with no additional uses and
b. the non-residential use shall be limited
to a maximum of four plumbing fixtures and.
c. the types of plumbing fixtures limited to
toilets, sinks (lavatory, residential, and service sinks) and drinking water
stations.
3. PVC and ABS
schedule 40 pipe and fittings shall not be used for drains, waste, or vents in
commercial kitchens, laundry rooms, public toilet facilities or other
commercial areas located in assisted living facilities, hotels, motels, inns,
or similar establishments. See 10.06: Example
1.
4. For the purposes of
248
CMR
10.06, ten stories shall be determined by
the building permit. If no building permit is required, ten stories shall be
determined by the authority having jurisdiction.
Exception:
a. PVC and ABS schedule 40 pipe and fittings
may be used for the drains, waste, and vent piping serving fixtures in
commercial establishments which are specifically used only for that type of
business in:
i. sinks used for washing of hair
and/or coloring in barber shops and beauty salons;
ii. fixtures used in salons for manicures and
pedicures;
iii. equipment used for
processing in photo-labs; or
iv.
plumbing fixtures which incorporate alcohol, soda, or other similar carbonated
type beverages in commercial buildings. These fixtures may discharge indirectly
into the sanitary drainage system. Transition to commercially accepted
materials shall be made immediately after the point of dilution. Refer to
248
CMR
10.12(1)(a)2.
Note: All piping for the
above-mentioned fixtures shall be connected to the main or branch drain serving
other fixtures to provide a point of waste dilution. Vent piping from the
fixture discharging the waste shall extend to a point six inches above the
flood rim of the fixture and then shall re-transition to cast iron or copper
piping material as used throughout the rest of the commercial
building.
v. Type 1 PVC pipe
and fittings may be used as indirect waste piping for dialysis equipment in
medical buildings.
vi. PVC Schedule
40 perforated pipe may be used for subsoil drainage in commercial
buildings.
vii. For thermal
expansion of PVC DWV please
see
248
CMR
10.05(7)(e).
10.06: Example 1
PVC Limited Allowances in Mixed-Use Building Ten Stories
and Under
Click to
view image
(h)
Other Plastics.
1. Pipe and fittings from purified water
systems installed from the point of purification to the final point of use as
defined in
248
CMR
10.03 shall be of a size and material
specified by the equipment manufacturer.
2. Product-accepted multilayer polypropylene
pipe with intermediate fiberglass layer and related fittings. Single wall
Polypropylene pipe and fittings for cold water installations
only.
(i)
Urinal Wastes. Urinal waste branches and urinal
fixture wastes shall be installed using the following:
1. Extra heavy or service weight cast iron
soil pipe and fittings with caulked joints
2. Extra heavy, service weight or no-hub cast
iron soil pipe and fittings with resilient gaskets or no hub clamps with
elastomeric sealing sleeves.
3.
Threaded cast iron pipe with cast iron drainage fittings.
4. Iron size copper or brass pipe with cast
brass drainage fittings.
5. PVC and
ABS schedule 40 plastic pipe and fittings may be used only in residential type
buildings.
6. Schedule 80 PVC and
CPVC threaded nipples may be used as a final point of connection for toilets
and urinals to carriers and fittings.
(j)
Sumps and Tanks for
Sewage. All sumps and tanks for receiving sewage removed by
mechanical or ejector methods shall be watertight and designed and constructed
as follows:
1.
Concrete. Three-inch minimum wall.
2.
Cast Iron.
Minimum A-inch thickness.
3.
Metal.
a. Minimum C
inch thickness for above ground and treated to resist corrosion.
b. For below ground installation sumps and
tanks shall be designed and accepted for that type of installation and treated
inside and outside to resist corrosion,
4.
Fiberglass.
Reinforced polyester resin glass fibers that comply with ANSI listed
standards.
(k)
Single Stack Sanitary Drainage System - (So-vent).
1. A Massachusetts professional engineer
shall be responsible for the design of the so-vent plumbing system.
2. As part of the design process, the
Massachusetts professional engineer shall be responsible for assuring that the
piping installation, including pipe sizing, dimension, and other aspects meet
the requirements for proper functioning as designed.
3. The Local or State plumbing Inspector
shall be responsible for all other aspects of the installation, as required by
248 CMR but is under no obligation to approve or otherwise involve themselves
in the design process or ensuring the system meets the design specifications.
An affidavit shall be provided by the designing engineer to the local plumbing
inspector prior to final inspection.
(l)
Vacuum Drainage
System. An engineered vacuum system that employs specifically
designed fixtures, piping arrangements and vacuum pumps that are designed and
installed in compliance with the manufacturer's recommendations may be used in
a building or structure provided that in addition to being in conformance with
248 CMR
3.00 through
10.00 the following
requirements are satisfied:
1. Each system
shall be designed or engineered by a Massachusetts professional
engineer.
2. Piping material shall
be type K, L, M or DWV hard drawn copper or cast iron.
3. All fittings shall be made of cast brass
or hard drawn wrought or cast iron and must be of DWV design.
4. The plumbing Inspector shall be
responsible for all other aspects of the installation, as required by 248 CMR
but is under no obligation to approve or otherwise involve themselves in the
design process or ensuring the System meets the design specifications. An
affidavit shall be provided by the designing engineer to the local plumbing
inspector prior to final inspection.
5. Any change or redesign in the vacuum
drainage system shall be subject to the requirements of
248
CMR
10.06(2)(m) and
248
CMR
10.23.
(m)
Relief Valve
Discharge. The use of any non-ferrous pipe and fittings rated at a
maximum service temperature of 200 °F on the outlet of a relief valve with
a discharge not exceeding 105,000 BTU per hour shall be
allowed.