310 CMR, § 80.30 - Requirements for Compatibility
(1) The Owner
and Operator shall not introduce, or allow to be introduced, any regulated
substance into a UST system that is not compatible with the UST
system.
(2) The Owner or Operator
shall ensure that all UST systems are compatible with the environment in which
they are installed including, but not limited to, soil and
groundwater.
(3) The Owner or
Operator storing regulated substance containing greater than 10% ethanol or
greater than 20% biofuel shall demonstrate compatibility of the tank, piping,
sumps, pumping equipment, leak detection equipment, spill buckets and overfill
prevention equipment with the regulated substance by complying with one of the
following options:
(a) Certification or
listing of UST system and UST components listed in 310 CMR 80.30(3) by a
nationally recognized, independent testing laboratory for use with the
regulated substance stored; or
(b)
Manufacturer's approval, in writing, indicating an affirmative statement of
compatibility, specifying the range of biofuel blends are compatible with the
UST system and UST components.