522 CMR, § 1.04 - Department Jurisdiction
(1)
Enforcement. Pursuant to M.G.L. c. 146, § 5, the
Division shall enforce M.G.L. 146, and 522 CMR, except when otherwise
provided.
(2) District Engineering
Inspectors may enter any premises pursuant to M.G.L. c. 146, §
5.
(3)
Inspection. A District Engineering Inspector shall
perform the First Inspection of a Boiler or Pressure Vessel as required by
M.G.L. c. 146, § 6.
(a)
Boilers. All Boilers and their Appurtenances shall be
thoroughly inspected externally and internally under the specifications of 522
CMR 2.00: Power Boilers and 4.00: Heating Boilers and
Other Heat Storage Sources, except those specified in M.G.L. c. 146,
§ 7, which includes:
1. Boilers of
railroad locomotives, motor vehicles or steam fire engines brought into the
Commonwealth for temporary use in times of emergency;
2. Boilers used in private
residences;
3. Boilers used for
heating purposes which carry pressures not exceeding 15 pounds to the square
inch and have less than four square feet of grate surface;
4. Boilers of not more than three
horsepower;
5. Boilers under the
jurisdiction of the United States; and
6. Boilers used exclusively for horticultural
or agricultural purposes.
(b)
Air Tanks. All
Air Tanks and their Appurtenances, except those specified in M.G.L. c. 146,
§ 34, shall be thoroughly inspected externally or internally consistent
with the specifications set forth in 522 CMR 7.00: Air Tanks
at least once every two years when the following criteria are met:
1. design MAWP greater than 50 PSI;
and
2. greater than six inches
internal diameter; and
3. internal
volume greater than one cubic foot.
(c)
Massachusetts Tag
Number.
1. Every Boiler, Pressure
Vessel, and Refrigeration and Air Conditioning System which has been inspected
by the Division shall be given a registration number upon a nonferrous metal
tag authorized by the Board. The tag shall be held by nonferrous wire in a
conspicuous place on the unit and no person, except a District Engineering
Inspector, shall remove the tag.
2.
Authorized Inspection Agencies shall be furnished tag numbers by the Chief for
Refrigeration and Air Conditioning systems, or hot water Boiler systems. The
Authorized Inspection Agencies shall furnish tags, authorized by the Board,
upon which shall be the tag number. The tag shall be made of non-ferrous metal
and attached in a conspicuous place on the unit.