Minn. R. 1305.1022 - SECTION 1022, INTERIOR EXIT STAIRWAYS AND RAMPS
IBC section 1022.5 is amended to read as follows:
1022.5
Penetrations. Penetrations into and openings through interior exit
stairways and ramps are prohibited except for required exit doors, equipment,
and ductwork necessary for independent ventilation or pressurization, sprinkler
piping, standpipes, electrical raceway for fire department communications
systems and electrical raceway serving the interior exit stairway or ramp and
terminating at a steel box not exceeding 16 square inches (0.010
m2). Such penetrations shall be protected in
accordance with section 714. There shall be no penetrations or communicating
openings, whether protected or not, between any other interior exit stairways
and ramps.