Minn. R. 1305.1023 - SECTION 1023, INTERIOR EXIT STAIRWAYS AND RAMPS
IBC section 1023.5 is amended to read as follows:
1023.5
Penetrations.
Penetrations into or through interior exit stairways and ramps are prohibited
except for the following:
1. Equipment and
ductwork necessary for independent ventilation or pressurization.
2. Fire protection systems.
3. Security systems that serve the exit
stairway or ramp.
4. Wiring that
serves the exit stairway or ramp.
5. Two-way communication systems that serve
the exit stairway or ramp.
6.
Electrical raceway for fire department communication systems.
7. Electrical raceway serving the interior
exit stairway or ramp and terminating in a steel box not exceeding 16 square
inches (0.010 m2).
Such penetrations shall be protected in accordance with Section 714. There shall not be penetrations or communication openings, whether protected or not, between adjacent interior exit stairways and ramps or exit passageways.
(The exception to Section 1023.5 is deleted.)