Minn. R. agency 151, ch. 7511, pt. 7511.1026 - SECTION 1026, EMERGENCY ESCAPE AND RESCUE
IFC Section 1026.1 is amended to read:
1026.1
Escape windows. In Group
R and Group I-1 occupancies, escape windows shall be provided, installed and
maintained in sleeping rooms in accordance with this section. Sleeping rooms
located in basements and levels below the fourth story shall have at least one
exterior emergency escape and rescue opening.
Exceptions:
1. An escape window is not required if the
room has a door that leads directly to the exterior of the building.
2. Escape windows installed prior to April
11, 1983, and having a clear opening not less than 20 inches (508 mm) in width,
24 inches (610 mm) in height and 5 square feet (0.46
m2) in area with a finished sill height not more
than 48 inches (1219 mm) above the floor may be allowed to continue.
3. An escape window is not required if the
building is protected throughout by an approved, automatic sprinkler
system.
4. Escape windows need not
be installed from rooms of existing buildings having two separate means of
escape, provided that the means of escape are independent of each other and
they pass through only one adjacent nonlockable room or area.
5. Existing escape windows at single-story
resort buildings installed prior to October 3, 1975, and having a clear opening
not less than 20 inches (508 mm) in width, 20 inches (508 mm) in height and 4.5
square feet (0.41 m2) in area with a finished sill
height not more than 36 inches (914 mm) above the floor may be allowed to
continue.
6. Escape windows are not
required in Group R hotels or motels constructed prior to April 11,
1983.