IFC section 1103.7 and its subsections are deleted entirely and
replaced with the following:
1103.7
Fire alarm systems. An approved fire alarm system shall be
installed in existing buildings and structures in accordance with Sections
1103.7.1 through 1103.7.6.1.
In buildings containing mixed occupancies that are designed as
separated uses (see Section
102.14), fire alarm and
detection systems need only be installed in those occupancies where required by
this section.
In areas protected by an approved, supervised automatic
sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2,
automatic fire detectors required by Section 1103.7 need not be provided. Where
Section 1103.7 requires smoke detectors, such protection shall be
installed.
1103.7.1
Group A,
general. A fire alarm system shall be installed in accordance with
Sections 1103.7.1 through 1103.7.1.3.1 in existing Group A occupancies having
an occupant load of 300 or more.
1103.7.1.1
Exemptions for Group A. A fire alarm system is not required in
Group A occupancies having the following conditions:
1. Assembly areas used solely for worship
purposes.
2. A fire alarm system is
not required when an approved automatic fire-sprinkler system is installed
throughout the building.
3.
Assembly uses located inside Group E occupancies shall have alarms as required
for the Group E occupancy.
4. A-5
occupancies.
1103.7.1.2
Initiation. Initiation of the fire alarm system shall be by
automatic means. Approved automatic fire detectors shall be installed in
laundry rooms, boiler and furnace rooms, mechanical and electrical rooms,
shops, kitchens, trash-collection rooms, storage rooms, and similar
areas.
1103.7.1.3
Notification. The required fire alarm system shall activate an
audible and visible notification appliance at a constantly attended location
within the building for the purposes of initiating emergency action. A
presignal feature and positive alarm sequencing in accordance with NFPA 72 are
permitted. Occupant notification shall be by means of voice announcements,
either live or prerecorded, initiated by the person in the constantly attended
location.
1103.7.1.3.1
Exemption for
voice evacuation. Where no constantly attended location exists, an
automatic fire alarm system providing a general evacuation signal or an
approved emergency voice/alarm communications system is permitted.
1103.7.2
Group E,
general. A fire alarm system shall be installed in accordance with
Sections 1103.7.2 through 1103.7.2.4 in existing Group E occupancies having an
occupant load of 50 or more.
1103.7.2.1
Exemption for single classroom. A fire alarm system is not
required for a building with a maximum area of 1,000 square feet (93
m2) that contains a single classroom and is located
no closer than 20 feet (15,240 mm) from another building.
1103.7.2.2
Initiation.
Initiation of the fire alarm system shall be by manual and automatic means.
Approved automatic fire detectors shall be provided in laundry rooms, boiler
and furnace rooms, mechanical and electrical rooms, shops, laboratories,
kitchens, locker rooms, custodial closets, trash-collection rooms, storage
rooms, lounges, and similar areas.
1103.7.2.2.1
Manual activation.
In buildings protected throughout by an approved, automatic fire sprinkler
system or having an approved fire alarm system equipped with corridor smoke
detection, manual fire alarm boxes are only required in the main office and in
a custodial area.
1103.7.2.3
Travel through adjoining
rooms. Where the only means of egress travel from an interior room or
rooms having an aggregate occupant load of more than ten occupants is through
an adjoining or intervening room, automatic smoke detectors shall be installed
throughout the common atmosphere through which the path of egress travel
passes.
1103.7.2.3.1
Sprinkler
protection. In buildings that are protected throughout by an approved
automatic sprinkler system installed in accordance with Section 903.3.1.1,
smoke detectors are not required in intervening or adjoining rooms.
1103.7.2.4
Notification. Activation of the fire alarm system or automatic
sprinkler system shall initiate a general evacuation signal.
1103.7.3
Group I,
general. A fire alarm system shall be installed in accordance with
Sections 907.2.6 through 907.2.6.4.2 in existing Group I occupancies.
1103.7.4
Group R-1, general. A
fire alarm system shall be installed in accordance with Sections 1103.7.4
through 1103.7.4.4.1 in existing Group R-1 occupancies where:
1. Any sleeping unit or dwelling unit is
located two or more stories above the story containing the lowest level of exit
discharge.
2. Any sleeping unit or
dwelling unit is located more than one story below the highest level of exit
discharge of exits serving the dwelling unit.
3. The building contains 20 or more guest
rooms or dwelling units.
4. The
building is used as a congregate living facility, dormitory, convent,
monastery, fraternity, sorority, group home, or shelter and has an occupant
load of 20 or more.
1103.7.4.1
Direct exits to exterior. A fire alarm system is not required in
buildings that do not have interior corridors serving guest rooms and where
each guest room has an exit door opening directly to an exterior exit access
that leads directly to the exits.
1103.7.4.2
Initiation.
Initiation of the fire alarm system shall be by automatic means. Approved
automatic fire detectors shall be provided in boiler and furnace rooms, shops,
laundry rooms, mechanical and electrical rooms, trash-collection rooms, storage
rooms, gift shops, locker rooms, and similar areas. Automatic smoke detectors
shall be provided in all common areas and interior corridors serving as
required means of egress.
1103.7.4.2.1
Sprinkler protection. System fire and smoke detectors are not
required when an approved automatic fire-extinguishing system is installed in
accordance with Section 903.3.1.1 or 903.3.1.2 and a manual fire alarm box is
provided at a constantly attended location. When a constantly attended location
is not provided the manual fire alarm box shall be provided at the main
exit.
1103.7.4.3
Notification. Activation of the fire alarm system or automatic
sprinkler system shall initiate a general evacuation signal.
1103.7.4.4
Guest room smoke
alarms. Guest room smoke alarms required by Section 1103.8 shall not be
connected to a fire alarm system.
1103.7.4.4.1
Annunciation
allowed. Connection of such alarms for annunciation is
permitted.
1103.7.5
Group R-2, general. A
fire alarm system shall be installed in accordance with Sections 1103.7.5
through 1103.7.5.3 in existing Group R-2 occupancies where:
1. any sleeping unit or dwelling unit is
located two or more stories above the story containing the lowest level of exit
discharge;
2. any sleeping unit or
dwelling unit is located more than one story below the highest level of exit
discharge of exits serving the dwelling unit;
3. the building contains more than 16
sleeping units or dwelling units; or
4. the building is used as a congregate
living facility, dormitory, convent, monastery, fraternity, sorority, group
home, or shelter and has an occupant load of 20 or more.
1103.7.5.1
Direct exits to
exterior. A fire alarm system is not required in buildings that do not
have interior corridors serving guest rooms and where each dwelling unit has an
exit door opening directly to an exterior exit access that leads directly to
the exits.
1103.7.5.2
Initiation. Initiation of the fire alarm system shall be by
automatic means. Approved automatic fire detectors shall be provided in boiler
and furnace rooms, shops, laundry rooms, mechanical and electrical rooms,
trash-collection rooms, storage rooms, and similar areas. Automatic smoke
detectors shall be provided in all common areas and interior corridors serving
as required means of egress.
1103.7.5.2.1
Sprinkler protection. System fire and smoke detectors are not
required when an approved automatic fire-extinguishing system is installed
throughout the building.
1103.7.5.3
Notification.
Activation of the fire alarm system or automatic sprinkler system shall
initiate a general evacuation signal.
1103.7.5.4
Dwelling unit smoke
alarms. Dwelling unit smoke alarms required by Section 1103.8 shall not
be connected to the building fire alarm system.
1103.7.5.4.1
Annunciation
allowed. Connection of such alarms for annunciation is
permitted.
1103.7.6
Audible alarms. Audible
alarm notification appliances shall be provided and sound a distinctive sound
that is not to be used for any purpose other than that of a fire alarm. The
audible alarm notification appliances shall provide a sound pressure level of
15 decibels (dBA) above the average ambient sound level or 5 dBA above the
maximum sound level having a duration of at least 60 seconds, whichever is
greater, in every occupied space within the building. The maximum sound
pressure level for audible alarm notification appliances shall be 110 dBA at
the minimum hearing distance from the audible appliance. Where the average
ambient noise is greater than 105 dBA, visible alarm notification appliances
shall be provided in accordance with NFPA 72 and audible alarm notification
appliances shall not be required.
1103.7.6.1
Maximum sound pressure. Fire alarm system audibility levels shall
not exceed 35 dB above the average ambient sound level described in Section
907.5.2.1.1 or 35 dB above the peak ambient sound level. The maximum sound
pressure level for audible alarm notification appliances shall be 110 dBA at
the minimum hearing distance from the audible appliance. Where the average
ambient noise is greater than 95 dBA, visible alarm notification appliances
shall be provided in accordance with NFPA 72 and audible alarm notification
appliances shall not be required.