Minn. R. agency 151, ch. 7511, pt. 7511.6101 - CHAPTER 61, LIQUEFIED PETROLEUM GASES
Chapter 61 is deleted in its entirety and replaced with the following:
CHAPTER 61
LIQUEFIED PETROLEUM GASES
SECTION 6101
NFPA STANDARD NO. 58 INCORPORATED
6101.1
Incorporation by
reference. The storage, handling, transportation, and use of liquefied
petroleum gas and the installation of all equipment pertinent to systems for
such uses shall be designed, constructed, installed, operated, and maintained
in accordance with the provisions of NFPA Standard No. 58, Liquefied Petroleum
Gas Code (Quincy, Massachusetts, 2017). Standard No. 58, as amended by Section
6102, is incorporated by reference, is not subject to frequent change, and is
available at the State Law Library, 25 Rev. Dr. Martin Luther King Jr. Blvd.,
St. Paul, Minnesota 55155.
SECTION 6102
AMENDMENTS TO NFPA STANDARD NO. 58
6102.1
Amendments.
NFPA 58 shall apply to the storage, handling, transportation, and use of
liquefied petroleum gas and the installation of all equipment pertinent to
systems for such uses, except as amended by this section.
1. Section 6.5.3.8 of NFPA Standard No. 58 is
amended to read:
6.5.3.8. No horizontal
separation shall be required between aboveground LP-Gas containers and
underground tanks containing flammable or combustible liquids installed in
accordance with Chapter 57 of the International Fire Code.
2. Section 6.5.3.11 of NFPA Standard No. 58
is amended to read:
6.5.3.11 The minimum
separation between LP-Gas containers and liquefied hydrogen containers shall be
in accordance with Chapter 55 of the International Fire Code.
3. Footnote "b" of Table
6.7.2.1 of NFPA Standard No. 58 is amended to read:
b. Walls constructed of noncombustible
materials having a fire rating of at least one hour as determined by the
Building Code.
4.
Section 6.8.7.1 of NFPA Standard No. 58 is amended to read:
6.8.7.1. Installation of containers on roofs
of buildings shall be prohibited.
5. Section 6.8.7.2 of NFPA Standard No. 58 is
deleted.
6. Section 6.22.11.1 of
NFPA Standard No. 58 is deleted.
7.
Section 6.25.2.1 of NFPA Standard No. 58 is amended to read:
6.25.2.1 Electrical equipment and wiring
shall be of a type specified by and shall be installed in accordance with the
Minnesota Electrical Code for ordinary locations except that fixed electrical
equipment in classified areas shall comply with Section 6.25.2.2.
8. The first sentence of
Section 6.25.2.2 of NFPA Standard No. 58 is amended to read:
6.25.2.2 Fixed electrical equipment and
wiring installed within the classified areas specified in Table 6.25.2.2 shall
comply with Table 6.25.2.2 and shall be installed in accordance with the
Minnesota Electrical Code.
9. Section 10.2.3 of NFPA Standard No. 58 is
amended to read:
10.2.3
Structure or
building heating. Heating shall be by steam or hot water radiation or
other heating transfer medium with the heat source located outside the building
or structure (see Section
6.25, Ignition Source
Control), or by electrical appliances listed for Class I, Group D, Division 2
locations, in accordance with the Minnesota Electrical
Code.