Mont. Admin. r. 20.9.616 - FIRE SAFETY
(1) The facility
shall conform to applicable federal, state, and/or local fire safety codes.
Compliance must be documented by the authority having jurisdiction. A fire
alarm and automatic detection system are required and must be approved by the
authority having jurisdiction.
(2)
Written policy, procedure, and practice must specify the facility's fire
prevention regulations and practices. These must include but are not limited to
the following:
(a) provision for an adequate
fire protection service;
(b) a
system of fire inspection and testing of equipment at least quarterly or at
intervals approved by the authority having jurisdiction, following the
procedures stated for variances, exception, or equivalencies;
(c) an annual inspection by local or state
officials or other qualified person; and
(d) availability of fire protection equipment
at appropriate locations throughout the facility.
(3) Written policy, procedure, and practice
must provide for a comprehensive and thorough weekly inspection of the facility
by a designated staff member for compliance with safety and fire prevention
standards. This policy and procedure must be reviewed annually and updated as
needed.
(4) The facility must have
documentation showing that specification for the selection and purchase of
facility furnishings indicate the fire safety performance requirements of the
materials selected.
(5) Facilities
must be designated and maintained as smoke-free buildings. Special containers
must be provided for flammable liquids, for rags used with flammable liquids,
and for other combustible refuse. All receptacles and containers must be
emptied and cleaned daily.
(6) The
facility must have written policy, procedure, and practice governing the
control and use of all flammable, toxic, and caustic materials.
(7) The facility must have a written
evacuation plan prepared in the event of fire or major emergency that is
certified by an independent, outside inspector trained in the application of
appropriate codes. The plan must be reviewed annually, updated as needed, and
reissued to the local fire jurisdiction. The plan must include the following:
(a) location of building/room floor
plan;
(b) use of exit signs and
directional arrows for traffic flow;
(c) location of publicly posted
plan;
(d) monthly drills in all
occupied locations of the facility; and
(e) staff drills when evacuation of dangerous
residents is not permitted.
(8) All facility personnel must be trained in
the implementation of written emergency plans.
(9) Written policy, procedure, and practice
must specify the means for the immediate release of youth from locked areas in
case of emergency and provide for a backup system.
Notes
41-5-1802, MCA; IMP, 41-5-1802, MCA;
State regulations are updated quarterly; we currently have two versions available. Below is a comparison between our most recent version and the prior quarterly release. More comparison features will be added as we have more versions to compare.
No prior version found.