Nev. Admin. Code § 444.146 - Connections for supply and disposal of water
1. No
direct mechanical connection with a domestic water supply may be made to a
public bathing or swimming facility, a chlorinator or the system of piping for
the facility, unless it is protected against backflow in a manner approved by
the health authority. All pools must be equipped with acceptable provisions,
such as overfall fillspouts, surge tanks or receptors, for adding makeup
water.
2. Water used to fill any
pool must be supplied by an overfall fillspout providing an airgap of not less
than 6 inches (15 centimeters) between the flood level at the pool and the
lowest point of the fillspout, or an overfall supply to a surge tank or
receptor wherein the water will freely overflow at deck level or the top of the
surge tank or receptor before coming in contact with the water supply
outlet.
3. Sanitary sewage from the
bathhouse must be discharged into a sewage system approved by the health
authority.