N.H. Admin. Code § Env-Dw 505.08 - Approved Backflow Prevention Devices
(a) Only approved
backflow prevention devices shall be used.
(b) Only the types of backflow prevention
devices listed in Table 505-1 below shall be used for the containment of
on-premise hazards for low and high degree of hazard situations respectively:
Table 505-1
Acceptable Backflow Prevention Devices for Degrees of Hazards
| Low Degree of Hazard | High Degree of Hazard |
| Air gap | Air gap |
| Pressure vacuum breaker | Reduced pressure backflow device |
| Double check valve assembly | A combination of the above |
| Reduced pressure backflow device | |
| A combination of the above |
(c)
A backflow prevention device shall not be installed in a location where it
will:
(1) Be subject to corrosive fumes,
grit, or sticky or abrasive liquids;
(2) Be subject to flooding or mechanical
abuse;
(3) Not be easily accessible
for testing and repair;
(4) Be in a
pit or built into or close to walls or other obstructions; or
(5) Be in a vertical position unless the
backflow prevention device was certified for that orientation.
Notes
(See Revision Note at part heading for Env-Dw 505) #10615, eff 6-1-14