N.H. Admin. Code § Inst 603.13 - Installation Close-up and Finishing
(a) Skirting shall
be made out of weather resistant material. It shall not be attached in a manner
that can cause water to be trapped between the siding and trim.
(b) Ventilation shall be provided for the
crawl space with skirting at a minimum of 1 ft 2 of
free area for every 600 ft2. of house area
floor.
(c) Access openings not less
than 18 inches in width and 24 inches in height and not less than 3 square feet
shall exist so water supply and sewer drain connections located under the house
are accessible for inspections. For the purpose of this section, openings shall
include doors, hatches or removable panels.
(d) Dryer vents, water heater overflow
drains,air conditioning condensation drains shall pass through the skirting to
the outside. They shall vent into the atmosphere to ensure moisture is carried
beyond the perimeter of the house.
Notes
#8494, eff 12-24-05; ss by #10155, eff 4-14-12