N.H. Admin. Code § Lab 1403.24 - Floor Openings and Open Sides
The employer shall ensure compliance with the following requirements:
(a) Every stairway and
ladder way floor opening shall be guarded by a standard railing on all exposed
sides except at the entrance. The entrance to ladder way openings shall be
guarded to prevent a person from walking directly into the opening;
(b) Every hatchway and chute floor opening
shall be guarded by a hinged floor opening cover equipped with standard
railings to leave only one exposed side or by a removable railing with toeboard
on not more than 2 sides and a fixed standard railing with toeboards on all
other exposed sides; and
(c) Every
floor hole into which persons can accidentally walk shall be guarded by either
a standard railing with standard toeboard on all exposed sides, or a floor hole
cover capable of supporting at least twice the weight of employees, equipment,
and materials that might be imposed on the cover at any one time. All covers
shall be secured to prevent accidental displacement and shall be marked with
the word "hole" or "cover" to provide warning of the hazard.